iii. Case 3
- Heat pump THERMO OFF TEMP:
1
Water inlet temperature > 55°C for continuous 60 secs, heat pump OFF.
- Heat pump THERMO ON TEMP:
1
Heat pump THERMO ON TEMP = Water inlet temperature < 55°C.
Booster heater control
- Booster heater turn On and Off follow normal operation.
- Booster heater turn ON condition:
1
During startup time (initialization), Booster heater turn ON after DELAY TIMER.
2
When tank temperature lower than HEATER ON TEMP
3
20 minutes from previous heater off.
- Booster heater turn OFF condition:
1
When tank temperature higher than tank set temperature for continuous 15 secs.
Solar 3 way valve
- Solar pump operates follow solar operation specification.
2 way valve closes
Others
- Indoor backup heater cannot be ON during tank mode only.