External Controller shall be connected to 1-pole switch with min 3.0 mm contact gap. (connection refer to
Diagram 5.2). Its cable must be (2 x min 0.5 mm
sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no. 17 and 18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
10 Must install Solar Connection PCB ! (optional) to indoor unit when Solar Pump Station is utilized. Refer
Solar Connection PCB's installation instruction for detail of installation.
11 Solar Three-way Valve cable shall be (3 x min 0.5 mm
sheathed cable.
Solar Pump Station cable shall be (2 x min 0.5 mm
12
cable. Strongly recommended install with maximum length of 10 meter only.
12.3.4.1
Connecting Requirement
The equipment's power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S
greater than or equal to 3050kW (for WH-SDC12C6E5/UD12CE5**, WH-SDC14C6E5/UD14CE5** and
WH-SDC16C6E5/UD16CE5**) at the interface point between the user's supply and the public system. It is the
responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network
operator if necessary, that the equipment is connected only to a supply with a short-circuit power S
or equal to 3050 kW.
The equipment's power supply 1 shall be connected to a suitable supply network, with the following maximum
permissible system impedance Z
WH-SDC12C6E5/UD12CE5**, WH-SDC14C6E5/UD14CE5** and WH-SDC16C6E5/UD16CE5** : 0.244 Ω
Please liaise with supply authority to ensure that the power supply 1 is connected only to a supply of that
impedance or less.
The equipment's power supply 2 complies with IEC/EN 61000-3-12.
The equipment's power supply 2 shall be connected to a suitable supply network, with the following maximum
permissible system impedance Z
WH-SDC12C6E5/UD12CE5**, WH-SDC14C6E5/UD14CE5** and WH-SDC16C6E5/UD16CE5** : 0.236 Ω
Please liaise with supply authority to ensure that the power supply 2 is connected only to a supply of that
impedance or less.
The equipment's power supply 3 complies with IEC/EN 61000-3-12.
The equipment's power supply 3 shall be connected to a suitable supply network, with the following maximum
permissible system impedance Z
WH-SDC12C6E5/UD12CE5**, WH-SDC14C6E5/UD14CE5** and WH-SDC16C6E5/UD16CE5** : 0.464 Ω
Please liaise with supply authority to ensure that the power supply 3 is connected only to a supply of that
impedance or less.
2
), double insulation layer of PVC-sheathed or rubber-
2
), of double insulation PVC-sheathed or rubber-sheathed
at the interface for models:
max
at the interface for models:
max
at the interface for models:
max
63
.
rms
2
), double insulation layer PVC-sheathed or rubber-
is
sc
greater than
sc