Philips WH-UD16CE5-A-1 Service Manual page 78

Air-to-water hweatpump
Table of Contents

Advertisement

- Tank interval will end and start heating interval timer, IF
* When this condition happen at tank side before case 1 thermo-off. 3WV switch to room side
compulsory and continue until complete room interval.
Tank interval timer finish AND External Room Thermo ON OR
1.
Fulfill above Case 1 of thermo off condition.
2.
3
Backup heater control:
During heating heat up interval.
o
- Follow normal backup heater control operation.
During tank heat-up interval.
o
- Backup heater OFF during this interval.
4
Booster heater control:
During heating heat-up interval.
o
- Booster heater ON/OFF according to booster heater operation control.
During tank heat-up interval.
o
- Once switch from heating heat-up interval to tank heat-up interval, turn off the booster heater and start
counting the BOOSTER HEATER DELAY TIMER.
- Booster heater turn ON after BOOSTER HEATER DELAY TIMER fulfill and tank temperature lower
than tank set temperature.
- BOOSTER HEATER DELAY TIMER is clear when switch to heating heat-up interval.
5
Solar 3 way valve
Solar 3WV operates follow solar operation specification.
o
* Under solar priority is set condition, when solar 3WV is ON, booster heater turn OFF.
* Under solar priority is not set condition, solar 3WV only can ON during heating heat-up interval.
6
2 way valve opens.
78

Advertisement

Table of Contents
loading

Table of Contents