The only connections remaining is the serial cable between the Anybus Module and the Maguire
WSB Control this is connected to the 9 way D connectors on the Anybus module(see figure 11) and
the Maguire WSB Control (see Figure 12).

Figure 11: Anybus Serial Connector

Settings Required in the Maguire WSB Control

Communications Settings

Standard communications settings for WSB control will need to be altered. Communications settings
between the gateway and the WSB are as follows:
Baud:
2400
Data Bits:
8
Parity:
None
Stop Bits:
1
WSB Address: 001
To change the settings on the on the WSB carry out the following:
Press * followed by 22222.
Press * followed by 95 and select the baud rate by pressing the * key, once selected press
exit.
Press * followed by 66 and set the WSB Communications address to 001 using the keypad,
press exit once setting is entered.
All relevant settings have now been changed in the WSB.