Power-loss ride-through function

The power-loss ride-through function is activated when parameter
20.06 UNDERVOLTAGE CTRL is set to ON (default in Standard Control Program).

ACS800-07/U7 units without line contactor

The power-loss ride-through funtion is not in use.

ACS800-07/U7 units with line contactor (+F250)

The power-loss ride-through funtion is enabled by connecting RMIO board terminals
X22:8 and X22:11 with a jumper.
Planning the electrical installation
X2 / RMIO board
X22
1
2
3
4
5
6
7
8
22
9
K13
10
21
11