Input Power Connection; Motor Connection; Efficiency; Cooling - ABB ACS800-04 Hardware Manual

Acs800 series
Hide thumbs Also See for ACS800-04:
Table of Contents

Advertisement

Input power connection

Voltage (U
)
1
Rated conditional short-
circuit current (IEC 60439-1)
Short-circuit current
protection (UL 508C,
CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1

Motor connection

Voltage (U
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length

Efficiency

Cooling

Method
Free space around the unit
Cooling air flow

Degrees of protection

208/220/230/240 VAC 3-phase ± 10% for 230 VAC units
380/400/415 VAC 3-phase ± 10% for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase ± 10% for 500 VAC units
525/550/575/600/660/690 VAC 3-phase ± 10% for 690 VAC units
65 kA when protected by fuses given in the fuse tables
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 100 kA symmetrical amperes (rms) at 600 V maximum when protected by fuses
given in the
NEMA data
fuse table.
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
0 to U
, 3-phase symmetrical, U
1
DTC mode: 0 to 3.2 · f
FWP
U
Nmains
f
=
· f
FWP
Nmotor
U
Nmotor
f
: frequency at field weakening point; U
FWP
U
: rated motor voltage; f
Nmotor
0.01 Hz
See section
IEC data.
1.5 · P
, 1.1 · P
or P
hd
N
cont.max
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Type code (EMC equipment)
-
+E202 *, +E210 *
* Motor cable longer than 100 m (328 ft) is allowed but then the EMC Directive requirements may not
be fulfilled.
Approximately 98% at nominal power level
Internal fan, flow direction from front to top
Refer to ACS800-04/04M/U4 Cabinet Installation [68360323 (English)].
See
IEC data.
IP 00 (UL type: open chassis)
at the field weakening point
max
. Maximum frequency 300 Hz (120 Hz with du/dt or sine filter).
: mains (input power) voltage;
Nmains
: rated motor frequency
Nmotor
(whichever value is greatest)
Max. motor cable length
DTC control
300 m (984 ft)
100 m (328 ft)
Scalar control
300 m (984 ft)
100 m (328 ft)
Technical data
99