Input Power (Mains) Connection; Motor Connection - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

130

Input Power (Mains) Connection

Prospective short-
circuit current
Fundamental power
factor (cos phi
Cable Temperature

Motor Connection

Voltage (U
Frequency
Frequency
resolution
Power limit
Field weakening
Switching
frequency
Temperature
Maximum motor
cable length
Technical Data
Input Power (Mains) Connection Specifications
208/220/230/240 VAC 3-phase (or 1-phase) +10% -15% for 230 VAC units
Voltage (U
)
1
400/415/440/460/480 VAC 3-phase +10% -15% for 400 VAC units
Maximum allowed prospective short-circuit current in the supply is 65 kA in
a second providing that the mains cable of the drive is protected with
(IEC 629)
appropriate fuses. US: 65,000 AIC.
Frequency
48...63 Hz
Imbalance
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
)
1
90 °C (194 °F) rating minimum.
Rating
)
0...U
, 3-phase symmetrical, U
2
1
0...500 Hz
0.01 Hz
Current
See section
1.5 x P
hd
10...500 Hz
point
Selectable: 1, 4, or 8 kHz
Cable
90 °C (194 °F) rating minimum.
Rating
Frame Size
R1
R2 - R4
R5 - R6
* Warning! Using a motor cable longer than specified in the chart above may
cause permanent damage to the drive.
Motor Connection Specifications
at the field weakening point
max
Ratings.
f
= 1 or 4 kHz
sw
100 m
200 m
300 m
ACS550 User's Manual
Max. motor cable length
f
= 8 kHz
sw
50 m
100 m
150 m