ABB ACS550-01 User Manual page 97

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

ACS550 User's Manual
Code Description
4023 PID SLEEP LEVEL
Sets the motor speed / frequency that enables the PID sleep
function – a motor speed / frequency below this level, for at least
the time period 4024
function (stopping the drive).
• Requires 4022 = 7
• See figure: A = PID output level; B = PID process feedback.
4024 PID SLEEP DELAY
Sets the time delay for the PID sleep function – a motor speed /
frequency below 4023
enables the PID sleep function (stopping the drive).
• See 4023
PID SLEEP LEVEL
4025 WAKE-UP DEVIATION
Defines the wake-up deviation – a deviation from the setpoint
greater than this value, for at least the time period 4026
, re-starts the PID controller.
DELAY
• Parameters 4006 and 4007 define the units and scale.
• Parameter 4005 = 0,
Wake-up level = Setpoint - Wake-up deviation.
• Parameter 4005 = 1,
Wake-up level = Setpoint + Wake-up deviation.
• Wake-up level can be above or below setpoint.
• See 4023
PID SLEEP LEVEL
See figures:
• C = Wake-up level when parameter 4005 = 1
• D = Wake-up level when parameter 4005 = 0
• E = Feedback is above wake-up level and lasts longer than 4026
-
– PID function wakes up.
WAKE
UP DELAY
• F = Feedback is below wake-up level and lasts longer than 4026
-
– PID function wakes up.
WAKE
UP DELAY
4026 WAKE-UP DELAY
Defines the wake-up delay – a deviation from the setpoint greater
than 4025
-
WAKE
UP DEVIATION
the PID controller.
• See 4023
PID SLEEP LEVEL
4027 PID 1 PARAM SET
Defines how selections are made between PID Set 1 and PID Set 2.
PID parameter set selection. When set 1 is selected, parameters 4001...4026 are used.
When set 2 is selected, parameters 4101...4126 are used.
0 =
1 – PID Set 1 (parameters 4001...4026) is active.
SET
1 =
1 – Defines digital input
DI
• Activating the digital input selects PID Set 2.
• De-activating the digital input selects PID Set 1.
2...6 =
2...
6 – Defines digital input
DI
DI
• See
1 above.
DI
7 =
2 – PID Set 2 (parameters 4101...4126) is active.
SET
-1 =
1(
) – Defines an inverted digital input
DI
INV
• Activating the digital input selects PID Set 1.
• De-activating the digital input selects PID Set 2.
-2...-6 =
2(
)...
DI
INV
DI
• See
1(
) above.
DI
INV
enables the PID sleep
PID SLEEP DELAY
.
INTERNAL
for at least this time period
PID SLEEP LEVEL
above.
above.
, for at least this time period, re-starts
above.
1 as the control for PID Set selection.
DI
2...
6 as the control for PID Set selection.
DI
DI
6(
) – Defines an inverted digital input
INV
P 4023
Setpoint
-
WAKE
UP
1 as the control for PID Set selection.
DI
2...
6 as the control for PID Set selection.
DI
DI
t < P 4024
t > P 4024
B
P 4025
Stop
P 4025
Setpoint
P 4025
E
P 4025
Setpoint
P 4025
97
A
t
P 4026
t
Start
C
}
4005 = 1
}
4005 = 0
D
t
C
P 4026
D
t
P 4026
F
Start-Up

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-u1

Table of Contents