Input Power (Mains) Cables And Fuses; Cable Terminals - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

ACS550 User's Manual

Input Power (Mains) Cables and Fuses

Branch circuit protection must be provided by the end-user, sized per national and
local electric codes. Recommendations for fuses for short-circuit protection on the
mains cable are below.
ACS550-
x1-
see
below
See note 1
Three-phase supply voltage, 380...480 V
-03A3-4
-04A1-4
-05A4-4
-06A9-4
-08A8-4
-012A-4
-015A-4
-023A-4
-031A-4
-038A-4
-044A-4
-059A-4
-072A-4
-096A-4
-124A-4
-157A-4
-180A-4
Note 1: Mains cable sizing is based on a correction factor of 0.71 (maximum of 4 cables laid on a cable
ladder side by side, ambient temperature 30 °C (86 °F), EN 60204-1 and IEC 364-5-523). For other
conditions, dimension the cables according to local safety regulations, appropriate input voltage and
the load current of the drive. In any case, the cable must be between the minimum limit defined in this
table and the maximum limit defined by the terminal size (see "Cable Terminals" on page 129).
Note 2: Fuse Type: UL Class T. For non-UL installations IEC 269 gG.

Cable Terminals

Brake resistor, mains and motor cable maximum sizes (per phase) accepted a the
cable terminals, and the tightening torques are listed below.
Frame
Size
R1
R2
R3
R4
R5
R6
Mains Cable (min.)
Cu
Al
2
2
(mm
)
(mm
)
1
1.5
14
1.5
14
1.5
14
1.5
14
1.5
14
2.5
12
2.5
10
6.0
8
10
8
16
6
16
6
25
4
35
3
50
70
1
70
95
1/0
95
120
4/0
120
150
250MCM 250
U1, V1, W1
U2, V2, W2
BRK+, UDC+
Maximum
Torque
Wire Size
2
mm
AWG Nm
lb-ft
6
8
1.4
1.0
10
6
1.4
1.0
25
3
1.8
1.3
50
1/0
2.0
1.5
70
2/0
15
11.1
185
350
40
29.5
MCM
Mains Fuses
AWG
A
V
2
2
10
600
10
600
10
600
10
600
10
600
16
600
16
600
25
600
35
600
50
600
50
600
63
600
80
600
125
600
150
600
200
600
600
Earthing PE
Maximum
Torque
Wire Size
2
mm
AWG
Nm
4
10
1.4
10
8
1.4
16
6
1.8
35
2
2.0
70
2/0
15
95
4/0
8
PE Earth Cable
Cu
Al
2
2
(mm
)
(mm
)
2.5
2.5
2.5
2.5
2.5
2.5
4.0
6.0
10
16
16
16
16
25
35
50
70
Control
Maximum
Wire Size
2
lb-ft
mm
AWG
Nm
1.0
1.0
1.5
16
0.4
1.3
1.5
11.1
5.9
Technical Data
129
AWG
12
12
12
12
12
12
10
8
8
6
6
6
6
4
3
1
1/0
Torque
lb-ft
0.3