ABB ACS550-01 User Manual page 41

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

ACS550 User's Manual
Code
Name
0127
2
PID
OUTPUT
0128
1
PID
SETPNT
0129
2
PID
SETPNT
0130
1
PID
FBK
0131
2
PID
FBK
0132
1
PID
DEVIATION
0133
2
PID
DEVIATION
0134
COMM RO WORD
0135
1
COMM VALUE
0136
2
COMM VALUE
0137
1
PROCESS VAR
0138
2
PROCESS VAR
0139
3
PROCESS VAR
0140
RUN TIME
0141
MWH COUNTER
0142
REVOLUTION CNTR
0143
(
)
DRIVE ON TIME
HI
0144
(
)
DRIVE ON TIME
LO
0145
MOTOR TEMP
Group 03: Actual Signals
0301
1
FB CMD WORD
0302
2
FB CMD WORD
0303
1
FB STS WORD
0304
2
FB STS WORD
0305
1
FAULT WORD
0306
2
FAULT WORD
0307
3
FAULT WORD
Group 04: Fault History
0401
LAST FAULT
0402
1
FAULT TIME
0403
2
FAULT TIME
0404
SPEED AT FLT
0405
FREQ AT FLT
0406
VOLTAGE AT FLT
0407
CURRENT AT FLT
0408
TORQUE AT FLT
0409
STATUS AT FLT
0410
1-3
DI
AT FLT
0411
4-6
DI
AT FLT
Range
-100...100%
Unit and scale defined by par. 4006/
4106 and 4007/4107
Unit and scale defined by par. 4206 and
4207
Unit and scale defined by par. 4006/
4106 and 4007/4107
Unit and scale defined by par. 4206 and
4207
Unit and scale defined by par. 4006/
4106 and 4007/4107
Unit and scale defined by par. 4206 and
4207
0...65535
-32768...+32767
-32768...+32767
-
-
-
0...499.99 kh
0...9999 MWh
Days
hh.mm.ss
-10...200 °C/ 0...5000 Ohm
-
-
-
-
-
-
-
fault codes
(panel displays as text)
Date dd.mm.yy /
power-on time in days
Time hh.mm.ss
-
-
-
-
-
-
000...111 (0...7 decimal)
000...111 (0...7 decimal)
Resolution
Default
0.1%
-
-
-
-
-
-
-
-
-
-
-
1
0
1
0
1
0
1
1
1
0.01 kh
0 kh
1 MWh
-
1 day
0
1 = 2s
0
1
0
-
-
-
-
-
-
1
0
1
0
1
0
1
0
1
0
1
0
2 s
0
1 rpm
0
0.1 Hz
0
0.1 V
0
0.1 A
0
0.1%
0
1
0
1
0
1
0
41