Input Power Connection; Motor Connection; Efficiency - ABB ACS800 Hardware Manual

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

124

Input power connection

Voltage (U
)
1
Short-circuit withstand
strength (IEC 60439-1)
Short-circuit current
protection (UL 508,
CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1

Motor connection

Voltage (U
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length

Efficiency

Technical data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
208/220/230/240 VAC 3-phase ± 10% for 230 VAC units
380/400/415 VAC 3-phase ± 10% for 400 VAC units
380/400/415/440/460/480/500 VAC 3-phase ± 10% for 500 VAC units
525/550/575/600/660/690 VAC 3-phase ± 10% for 690 VAC units
Maximum allowable prospective short-circuit current when protected by fuses given in the
IEC data
fuse tables is
for units without enclosure extension: 65 kA (I
for units with enclosure extension:
I
/ 1 sec.
cw
50 kA
US and Canada: According to UL 508C (ACS800-U2 without enclosure extension) and
UL 508A (ACS800-U2 with enclosure extension), the drive is suitable for use on a circuit
capable of delivering not more than 100 kA symmetrical amperes (rms) at 600 V maximum
when protected by fuses given in the
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
0 to U
, 3-phase symmetrical, U
1
DTC mode: 0 to 3.2 · f
FWP
U
Nmains
f
=
· f
FWP
Nmotor
U
Nmotor
f
: frequency at field weakening point; U
FWP
U
: rated motor voltage; f
Nmotor
0.01 Hz
See section
IEC data.
1.5 · P
, 1.1 · P
or P
hd
N
cont.max
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Type code (EMC equipment)
-
+E202 *, +E210 *
* Motor cable longer than 100 m (328 ft) is allowed but then the EMC Directive requirements may not be
fulfilled.
Approximately 98% at nominal power level
).
cc
I
pk
105 kA
NEMA data
fuse table.
at the field weakening point
max
. Maximum frequency 300 Hz.
: mains (input power) voltage;
Nmains
: rated motor frequency
Nmotor
(whichever value is greatest)
Max. motor cable length
DTC control
300 m (984 ft)
100 m (328 ft)
Scalar control
300 m (984 ft)
100 m (328 ft)