Gg Fuses - ABB ACS800 Hardware Manual

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

114
ACS800-02
Input current
size
A
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0140-7
126
-0170-7
156
-0210-7
191
-0260-7
217
-0320-7
298
-0400-7
333
-0440-7
377
-0490-7
423
-0550-7
468
-0610-7
533
2
A
s value for -7 units at 660 V
1)
minimum short-circuit current of the installation
Note 1: See also Planning the electrical installation:
fuses, see
NEMA data
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the fuse does not
exceed the melting curve of the fuse mentioned in the table.
ACS800-02
Input current
size
A
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2
201
-0100-2
239
-0120-2
285
-0140-2
391
-0170-2
428
-0210-2
506
-0230-2
599
-0260-2
677
-0300-2
707
Three-phase supply voltage 380 V, 400 V or 415 V
-0140-3
196
-0170-3
237
-0210-3
286
-0260-3
438
-0320-3
501
-0400-3
581
-0440-3
674
-0490-3
705
Technical data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Ultrarapid (aR) fuses
Min. short-
circuit
1)
current
A
A
A
1520
350
68 500
1520
350
68 500
1610
400
74 000
1610
400
74 000
3010
630
275 000
2650
630
210 000
4000
800
465 000
4790
900
670 000
4790
900
670 000
5550
1000
945 000
on page 119.

gG fuses

Min. short-
circuit
1)
current
A
A
3820
250
550 000
4510
315
1 100 000
4510
315
1 100 000
8280
500
2 900 000
8280
500
2 900 000
10200
630
4 000 000
10200
630
4 000 000
13500
800
7 400 000
13500
800
7 400 000
3820
250
550 000
4510
315
1 100 000
4510
315
1 100 000
8280
500
2 900 000
10200
630
4 000 000
10200
630
4 000 000
13500
800
7 400 000
13500
800
7 400 000
Fuse
2
s
V
Manufacturer
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
690
Bussmann
Thermal overload and short-circuit
Fuse
2
A
s
V
Manufacturer
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
500
ABB Control
Type DIN 43620
Size
170M3818
DIN1*
170M3818
DIN1*
170M5808
DIN2*
170M5808
DIN2*
170M5812
DIN2*
170M6810
DIN2*
170M6812
DIN3
170M6813
DIN3
170M6813
DIN3
170M6814
DIN3
protection. For UL recognized
PDM code: 00096931-G, 00556489
Type
IEC size
OFAF1H250
1
OFAF2H315
2
OFAF2H315
2
OFAF3H500
3
OFAF3H500
3
OFAF3H630
3
OFAF3H630
3
OFAF3H800
3
OFAF3H800
3
OFAF1H250
1
OFAF2H315
2
OFAF2H315
2
OFAF3H500
3
OFAF3H630
3
OFAF3H630
3
OFAF3H800
3
OFAF3H800
3

Hide quick links: