Installation checklist

Checklist

Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person. Read the
instructions
Check
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. See
conditions.
The unit is fixed properly on floor and a vertical non-flammable wall. See
The cooling air will flow freely.
ELECTRICAL INSTALLATION See
The motor and the driven equipment are ready for start. See
and compatibility,
Technical data:
The +E202 EMC filter capacitors are disconnected if the drive is connected to an IT (ungrounded) system.
The capacitors are reformed if stored over one year (refer to ACS 600/800 Capacitor Reforming Guide
[3AFE64059629 (English)].
The drive is grounded properly.
The mains (input power) voltage matches the drive nominal input voltage.
The mains (input power) connections at U1, V1 and W1 and their tightening torques are OK.
Appropriate mains (input power) fuses and disconnector are installed.
The motor connections at U2, V2 and W2 and their tightening torques are OK.
The motor cable is routed away from other cables.
Setting of the fan voltage tranformer
Setting of the auxiliary voltage transformer (option +G304)
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Mains (input power) voltage cannot be applied to the output of the drive (with bypass connection).
Drive, motor connection box and other covers are in place.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
on the first pages of this manual before you work on the unit.
Installation,
Planning the electrical installation, Installation.
Motor
connection.
Technical data:
IEC data
Installation.
Planning the electrical installation: Motor selection
Safety
or
NEMA data
,
Ambient
Installation checklist
97

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-02Acs800-u2

Table of Contents