Chapter 4 - Installation Checklist; Installation Checklist - ABB ACS 601 Hardware Manual

Ac drives, 3 to 150 hp, 2.2 to 110 kw
Hide thumbs Also See for ACS 601:
Table of Contents

Advertisement

Installation Checklist

MECHANICAL INSTALLATION
Check that the ambient operating conditions are suitable (see Appendix A: environmental
limits, cooling air flow requirements, free space requirements ).
Check that the unit is mounted properly on a vertical non-flammable wall (see Chapter 2 –
Mechanical Installation ).
Check that cooling air flows freely.
Check the applicability of the motor and the driven equipment (see Appendix A: Motor
Connection ).
ELECTRICAL INSTALLATION (see Chapter 3 – Electrical Installation )
If the ACx 600 is connected to an ungrounded power system or a high resistance grounded
power system (over 30 Ohms), check that the EMC filter capacitors are disconnected.
Check that the drive is grounded properly.
Check that the input voltage matches the drive nominal input voltage.
Check that input power connections at U1, V1 and W1 are OK.
Check that appropriate input line fuses are installed.
Check that motor connections at U2, V2 and W2 are OK.
Check motor cable routing.
Check that there are no power factor compensation capacitors connected between the drive
and the motor.
Check that control connections inside the drive are OK.
Check that there are no tools or other foreign objects inside the drive.
With bypass connection, check that input line voltage cannot be applied to the output of the
ACx 600.
ACS/ACC/ACP 601 Drives
Chapter 4 – Installation Checklist
The ACx 600 mechanical and electrical installation should be checked
before start-up. It is advisable to go through the checklist below
together with another person. Study carefully the Safety Instructions on
the first pages of this manual before attempting any work on, or with,
the unit.
ACx=ACS/ACC/ACP
4-1