Enclosures, Space Requirements; Heat Dissipation Requirements - ABB ACS 601 Hardware Manual

Ac drives, 3 to 150 hp, 2.2 to 110 kw
Hide thumbs Also See for ACS 601:
Table of Contents

Advertisement

Enclosures, Space
Requirements
ACx 600 Type
Enclosure
601
wall-mounted metal frame
1)
not for ACP 601 units
2)
The degrees of protection is specified by listing the IEC standard IP (Ingress Protection) number. The first digit of the IP number
specifies the protection against solid objects and dirt. The second digit specifies the protection against liquids. IP 00 s an open chassis.
NEMA 1 enclosures are comparable to approximately IP 20 and IP 33. NEMA 3R enclosures are comparable to IP 32. NEMA 12 and
NEMA 13 enclosures are cmparable to IP 54 to IP 65. NEMA 4 enclosures are comparable to IP 65 or 66.
First digit of IP number (protection against solid objects)
0
Not protected
1
Protected against solid objects larger than 50 mm (2 in.) dia.
2
Protected against solid objects larger than 12 mm (1/2 in.) dia.
3
Protected against solid objects larger than 2.5 mm (0.1 in.) dia. Protected against downward sprays of water up to 60 degrees
4
Protected against solid objects larger than 1.0 mm (0.04 in.) dia. Protected against light sprays or splashing water from all
5
Dust protected - dust shall not enter the enclosure in sufficient
quantity to interfere with satisfactory operation of equipment.
6
Dust tight
Heat DIssipation
Requirements
ACS/ACC/ACP 601 Drives
The cabinets, degrees of protection and free space requirements of
ACx 600 types are given below.
Degree of
Space
2)
Protection
above
1)
IP 22 /IP 54
12in / 300mm 12in / 300mm 2/2in 50/50mm 0.8/0in 20/0mm
Not protected
Protected against dripping water
Protected against downward sprays of water up to 15 degrees
from vertical.
from vertical.
directions - water shall not enter the enclosure in harmful
quantities.
Protected against low pressure sprays of water from all directions
- water shall not enter the enclosure in harmful quantities.
Protected against heavy seas on shipdecks or strong sprays of
water from all directions - water shall not enter the enclosure in
harmful quantities.
ACx 601 drives are self-cooled. The table below gives the heat
dissipated into the hot air exhausted from the drives. If the drives are
installed in a confined space, the heat must be removed from the area
by ventilation or air conditioning equipment.
Heat Dissipation
ACx 601 Type
Watts
ACx 601-0005
150
ACx 601-0006
180
ACx 601-0009
270
ACx 601-0011
330
ACx 601-0016
480
ACx 601-0020
600
ACx 601-0025
750
ACx 601-0030
900
ACx 601-0040
1200
ACx 601-0050
1500
ACx 601-0060
1800
ACx 601-0070
2100
ACx 601-0100
3000
ACx 601-0120
3600
ACx 601-0140
4200
Appendix A – ACS/ACC/ACP 601 Technical Data
Space
Space on
below
left/right
Second digit of IP number (protection against liquids)
BTU/Hr
512
615
922
1130
1640
2050
2560
3070
4100
5120
6150
7170
10200
12300
14300
ACx=ACS/ACC/ACP
Space in front/
back
A-9