Control Cable Ducts - ABB ACS800 Hardware Manual

45 / 60 to 560 / 600 kw
Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

A diagram of the cable routing is shown below.
Input power cable

Control cable ducts

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
90 °
min 200 mm (8 in.)
Control cables
24 V
Not allowed unless the 24 V cable is
insulated for 230 V (120 V) or insulated
with an insulation sleeving for 230 V
(120 V).
Drive
Power cable
230 V
(120 V)
Lead 24 V and 230 V (120 V) control
cables in separate ducts inside the
cabinet.
Motor cable
min 300 mm (12 in.)
Motor cable
min 500 mm (20 in.)
230 V
24 V
(120 V)
Planning the electrical installation
49