Heatsink

The heatsink fins pick up dust from the cooling air. The drive runs into
overtemperature warnings and faults if the heatsink is not clean. In a "normal"
environment (not dusty, not clean) the heatsink should be checked annually, in a
dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Fan).
2. Blow dry clean compressed air from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust. Note: Prevent dust from entering
adjoining equipment.
3. Replace the cooling fan.

Fan

The lifespan of the cooling fan of the drive is about 50 000 hours. The actual lifespan
depends on the running time of the fan, ambient temperature and dust
concentration. See the appropriate ACS800 firmware manual for the actual signal
which indicates the running time of the cooling fan. For resetting the running time
signal after a fan replacement, please contact ABB.
A cooling fan is included in the enclosure extension with a contactor option. Its
lifespan is at least 40 000 h.
Replacement fans are available from ABB. Do not use other than ABB specified
spare parts.