8.1.3.6

Technical data

Table 8- 11
Technical data
6SL3055-0AA00-5BAx
Electronics power supply
Voltage
Current (without encoder system)
Current (with encoder system)
Power loss
Encoder system power supply
Voltage
Current
Encoder frequency that can be evaluated
(f
)
encoder
SSI baud rate
2)
Max. encoder cable length
PE/ground connection
Weight
Degree of protection
A controller compares the encoder system supply voltage - sensed via the Remote Sense cables - with the reference
1)
supply voltage of the encoder system, and adjusts the supply voltage for the encoder system at the output of the sensor
module until the required supply voltage is obtained directly at the encoder system (only for 5 V encoder system power
supply).
Only possible for SSI encoders with 5 V supply.
2)
See the diagram "Maximum cable length depending on the SSI baud rate for SSI encoders"
3)
Note
Current controller clock cycle
For a current controller clock cycle of 31.25 µs, use an SMC20 with order number 6SL3055-
0AA00-5BA3.
Figure 8-8
AC Drive
Manual, (GH6), 04/2014, 6SL3097-4AL00-0BP4
Supplementary system components and encoder system integration
Unit
V
DC
A
DC
A
DC
W
V
DC
A
DC
kHz
kBd
m
kg
Maximum cable lengths depending on the SSI baud rate for SSI encoders
Value
24 (20,4 ... 28,8)
≤ 0,20
≤ 0,35
≤ 10
5 V DC (with remote sense)
0.35
≤ 500
100 - 1000
3)
100
At the housing with M4/1.8 Nm screw
0,45
IP20 or IPXXB
8.1 Sensor Modules
1)
359