6.2.8

GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YASKAWA
• Controller Type: Set either of the following
GL/PROGIC8
CP9200SH/MP900 series
CP9200(H)
CP9300MS (MC compatible)
MP2000/MP900
MP2000/MP900/CP9200SH series
• I/F: Interface to be used
• Driver: Set either of the following.
<For GT16, GT15 or GT11>
YASKAWA GL/CP9200(SH/H)/CP9300MS
<For GT10>
YASKAWA MP
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
6.2.8 ■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
(1) YASKAWA GL/CP9200(SH/H)/CP9300MS
3.
4.
Item
Transmission
Click!
Speed
Data Bit
Stop Bit
Parity
Retry
Startup Time
Timeout Time
Host Address
Delay Time
6. CONNECTION TO YASKAWA PLC
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the PLC to which the GOT is
connected) in the network of the
GOT.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
6.2 Serial Connection
1
2
3
Range
4800bps,
9600bps,
19200bps,
4
38400bps,
57600bps
8bit (fixed)
1bit (fixed)
5
Even (fixed)
0 to 5times
6
3 to 30sec
3 to 30sec
7
1 to 31
0 to 30
(
10ms)
8
6 - 15

Advertisement