Mitsubishi Electric GOT1000 Series Connection Manual page 334

Graphic operation terminal
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

RS422 connection diagram 5)
GOT side
SDA
1
SDB
6
RDA
2
RDB
7
SG
5
RSA
3
CSA
4
RSB
8
CSB
9
*1
Connect FG grounding to the appropriate part of a cable shield line.
*2
Terminating resistor should be provided for a PLC which will be a terminal.
RS422 connection diagram 6)
GOT side
SDA
1
SDB1
6
RDA
2
RDB
7
SG
5
RSA
3
CSA
4
RSB
8
CSB
9
*1
Connect FG grounding to the appropriate part of a cable shield line.
*2
Terminating resistor should be provided for a PLC which will be a terminal.
11 - 12
11. CONNECTION TO GE PLC
11.3 Connection Diagram
PLC
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
* 1
PLC
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
SHLD
* 1
1
* 2
terminating resistor 120Ω
* 1
* 2
terminating resistor 120Ω
* 1
PLC
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
PLC
RT
9
RD(B')
11
RD(A')
10
SD(B)
13
SD(A)
12
SG
7
RTS(A)
6
CTS(A')
15
RTS(B)
14
CTS(B')
8
SHLD
1

Advertisement

Table of Contents
loading

Table of Contents