14.3.3 GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: SIEMENS
• Controller Type: Depends on Ethernet connection
type.
FETCH/WRITE: SIEMENS S7 (Ethernet)
OP communication: SIEMENS OP (Ethernet)
• I/F: Interface to be used
• Driver: Depends on Ethernet connection type.
FETCH/WRITE: Ethernet (SIEMENS S7), Gateway
OP communication: Ethernet (SIEMENS OP),
Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage environment.
14.3.3 Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
(1) GT16, GT14
3.
4.
Item
GOT NET No.
GOT PLC No.
GOT IP
*1
Address
Click!
Subnet Mask
Default
Gateway
Ethernet
Download Port
*1
No.
GOT
Communication
Port No.
Startup Time
Timeout Time
Delay Time
14. CONNECTION TO SIEMENS PLC
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
*2
(Default: 1)
Set the IP address of the GOT.
(Default: 192.168.3.18)
Set the subnet mask for the sub
network. (Only for connection via
router)
*1
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is
connected. (Only for connection via
*1
router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet
module.
(Default:)
Ethernet (SIEMENS S7), Gateway:
5023
Ethernet (SIEMENS OP), Gateway:
5024
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
14.3 Ethernet Connection
9
10
11
Range
1 to 239
1 to 254
12
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
13
0.0.0.0 to
255.255.255.255
1024 to 5010,
5023 to 65534
(Except for 5011,
5012, 5013, and
14
49153)
1024 to 5010,
5023 to 65534
(Except for 5011,
5012, 5013, and
49153)
15
3 to 255 sec
3 to 90 sec
0 to 10000
16
(
10ms)
14 - 11