Technical Data Supervision Control Board - Bosch Praesideo 3.5 Installation And User Instructions Manual

Digital public address and emergency sound system
Table of Contents

Advertisement

Praesideo 3.5 | Installation and User Instructions | 4 | Amplifiers
For example, the ID selectors in figure 12.8 show
address 2C.
E
C
A
8
S701
figure 12.8: ID selectors
Make sure that the maximum number of EOL and
Loudspeaker Supervision boards is not exceeded.
PRS-1P500 can have a maximum of 80 boards, of
which 16 can be LBB4443/00 EOL boards or
LBB4441/00 with line supervision enabled.
PRS-2P250 can have a maximum of 40 boards per
channel, of which 16 can be LBB4443/00 EOL
boards or LBB4441/00 with line supervision
enabled.
PRS-4P125 can have a maximum of 20 boards per
channel, of which 16 can be LBB4443/00 EOL
boards or LBB4441/00 with line supervision
enabled.
Note
The number of EOL supervision boards are
limited to 16 per channel as the boards are
polled more frequently than the loudspeaker
supervision boards to comply to the standards
for emergency sound systems.
The multi channel interface can have up to 16
supervision boards connected to each basic amplifier
channel of the multi channel interface. The
maximum number of boards in total across all
channels is 80, of which 64 can be LBB4443/00 EOL
boards or LBB4441/00 with line supervision
enabled. Do not to exceed the maximum number of
supervision boards related to the maximum output
power of the amplifier channel; see section 12.6.5.
Bosch Security Systems | 2011-02
2
E
2
4
C
6
A
6
8
S700
12.5
Technical data supervision
control board
12.5.1 Physical characteristics
Dimensions (H x W x D):
60 x 50 x 17 mm
Weight:
4
30 g
Connection:
20 pole flatband cable and connector
Installation:
Plastic brackets for horizontal or vertical installation
are delivered with the amplifier.
12.5.2 Climate conditions
Temperature:
-5 to 55 °C (operating)
-20 to 70 °C (non-operating)
Relative humidity:
15 to 90%, non-condensing (operating)
5 to 95%, non-condensing (non-operating)
Air pressure:
600 to 1100 hPa
12.5.3 EMC and Safety
Electromagnetic compatibility:
EN55103-1/FCC-47 part 15B
EN55103-2
EN50121-4
EN50130-4
Electrical safety:
IEC60065 (CB-scheme)
EN60065
Approvals:
CE marking
EN60849, EN54-16 and ISO7240-16
IEC60945
12.5.4 Mean time between failure
MTBF:
50,000 hours at +55 °C
(The MTBF doubles for every 10 °C decrease in
temperature.)
en | 195