Upgrade System Software - Bosch Praesideo 3.5 Installation And User Instructions Manual

Digital public address and emergency sound system
Table of Contents

Advertisement

Praesideo 3.5 | Installation and User Instructions | 8 | Software
Microsoft Windows 2000 [Version 5.00.2195]
(C) Copyright 1985-2000 Microsoft Corp.
C:\>ping 192. 1 68.0. 1 5
Pinging 192. 1 68.0. 1 5 with 32 bytes of data:
Reply from 192. 1 68.0. 1 5: bytes = 32 time<10 ms TTL=128
Reply from 192. 1 68.0. 1 5: bytes = 32 time<10 ms TTL=128
Reply from 192. 1 68.0. 1 5: bytes = 32 time<10 ms TTL=128
Reply from 192. 1 68.0. 1 5: bytes = 32 time<10 ms TTL=128
Ping statistics for 192. 1 68.0. 1 5:
Packets: Sent = 4, Received = 4, Loss = 0 (0% loss)
Approximate round trip in milli-seconds:
Minimum = 0 ms, Maximum = 0 ms, Average = 0 ms
figure 36.3: Correct communication
8 Go to Start > Programs > Bosch > Praesideo > FT
Application to start the Praesideo File Transfer
Application. A screen similar to the one in figure 36.4
appears.
figure 36.4: Connecting to the network controller
9 Enter the IP address of the network controller in the
NCO address field.
10 Enter the correct user name in the Username field and
the correct password in the Password field.
If no software has been transferred to the network
controller before, the default user name is target
and the default password is password.
If software has been transferred to the network
controller before, the default user name is admin
and the default password is admin.
11 Click the Connect to NC button to establish a
connection with the network controller. A
notification appears.
Bosch Security Systems | 2011-02

36.4 Upgrade system software

A number of the system files that have been installed on
the configuration PC (see section 36.2), must be
transferred to the network controller. Proceed as
follows:
1 Click the Upgrade system software button. A screen
similar to the one in figure 36.5 appears.
figure 36.5: File transfer screen
2 Click the Upgrade now button. A notification is
displayed when the file transfer process is finished.
3 Switch the network controller off and then on to
restart.
en | 313