■2. GT2512F-S, GT2510F-V, GT2508F-V
Open an installation hole on the control panel with the dimensions as shown below.
D
Fitting
installation
Model
position
(on the
GOT)
Long side
of the GOT
GT2512F-S
Short side
of the GOT
Long side
of the GOT
GT2510F-V
Short side
of the GOT
Long side
of the GOT
GT2508F-V
Short side
of the GOT
The C to F dimensions show the measurements for installing fittings on the control panel.
Additionally, install studs on the control panel.
For information on how to install studs, refer to the following.
6.3 Stud
Horizontal
A
Back of the control panel
A
B
269(10.59)
214(8.43)
(+2(0.08), 0(0))
(+2(0.08), 0(0))
234(9.21)
187(7.36)
(+2(0.08), 0(0))
(+2(0.08), 0(0))
194(7.64)
158(6.22)
(+2(0.08), 0(0))
(+2(0.08), 0(0))
Vertical
E
F
Back of the control panel
C
D
28(1.10)
17(0.67)
36(1.42)
10(0.39)
35(1.38)
18(0.71)
28(1.10)
33(1.30)
32(1.26)
10(0.39)
51(2.01)
14(0.55)
28(1.10)
14(0.55)
32(1.26)
10(0.39)
32(1.26)
14(0.55)
6.2 Panel Cut Dimensions
B
C
Unit: mm (inch)
Panel
E
F
thickness
26(1.02)
44(1.73)
33(1.30)
1.5(0.06)to
4(0.16)
51(2.01)
29(1.14)
47(1.85)
6 - 5