Security functions of the CP
The CP supports the following Security functions:
● Encrypted telecontrol communication
You configure the interval of the key exchange between the CPU and telecontrol server in
STEP 7 in the parameter group "Ethernet interface (X1) > Advanced options > Transfer
settings".
● Configuring authorized phone numbers on the CP
To authorize nodes allowed to establish a connection to the CP during telecontrol
communication.
● Telecontrol password
To authenticate the CP with the telecontrol server
● STARTTLS / SMTPS
For the secure transfer of e-mails
● NTP (secure)
For secure transfer during time-of-day synchronization (with telecontrol communication
disabled)
● HTTPS
For secure access to the Web server of the CPU
Note
Plants with security requirements - recommendation
If you have systems with high security requirements, use the secure protocols NTP (secure)
and HTTPS.
1.4

Performance data and configuration limits

Number of simultaneous connections for telecontrol communication
● 1 reserved connection for user data exchange with the telecontrol server
Number of simultaneous TeleService connections
● Max. 1 TeleService connection
Number of simultaneous connections for S7 communication and Open User Communication
A maximum total of 22 connection resources for S7 communication and Open User
Communication (OUC)
CP 1242-7 GPRS V2