4. Create PLC tags for the input and output data to be transferred in the CPUs.
5. Insert the CPs in the relevant stations.
6. Configure the CPs including the data points and any messages (e-mail / SMS).
Note
Changing the project number or station number for the entire STEP 7 project
If you change the project number or the station number in the "CP identification"
parameter group for a telecontrol CP, these parameters are changed for all CPs in the
STEP 7 project.
7. If required, program the program blocks for S7 communication and Open User
Communication.
8. Save and compile the project.
9. Download the project data to the stations.
Using the "Download to device" function, the STEP 7 project data including the
configuration data of the CPs is downloaded to the relevant CPU.
You will find further information on the individual steps in the following sections and in the
help system of STEP 7.
4.4

Information required for configuration

To configure and commission the CP and the connected telecontrol system, the following
information is required:
General information
The following information is required for the STEP 7 configuration of the CP:
● Own phone number of the CP (required for TeleService)
● Authorized phone numbers
Call numbers of the nodes that can instigate connection establishment by the CP with an
SMS message or call.
● APN
Name of the access point (APN) from the mobile wireless network to the Internet
(information from the mobile wireless network provider)
● APN user name
User name for the access point of the mobile wireless network provider
● APN password
Password for the access point of the mobile wireless network provider
● Node number of the SMS master station (SMSC) when using SMS
● PIN of the SIM card
CP 1242-7 GPRS V2
Operating Instructions, 10/2016, C79000-G8976-C311-02
Configuration and operation
4.4 Information required for configuration