Configuration and operation

4.3 Configuration in STEP 7

Protocol / function Port number (pro-
tocol)
S7 and online
102 (TCP)
connections
SMTP
25 (TCP)
can be set
SSL/TLS
587 (TCP)
can be set
NTP
123 (TCP)
HTTP
80 (TCP)
HTTPS
443 (TCP)
4.3
Configuration in STEP 7
Configuration in STEP 7
You configure the modules, networks and connections in an engineering station in SIMATIC
STEP 7. You will find the required version in the section Requirements for operation
(Page 15).
You can configure a maximum of three CMs/CPs per station. If you insert several CPs in an
S7-1200, you can, for example, establish redundant communications paths.
Configuring communication with the CPU (data point configuration)
CP communication is not programmed using program blocks but configured using data
points.
One requirement for data point configuration is the programming of the assigned CPU and
the input and output data of the station. To assign the user data to be transferred
(input/output data) to the data points, you need to create PLC tags.
Overview of the configuration steps in STEP 7
Notes:
● No Ethernet network needs to be created for the communication via the mobile wireless
network.
● A telecontrol server or a TeleService- gateway cannot be configured in STEP 7.
Follow the steps below when configuring:
1. Create a STEP 7 project.
2. Insert the required SIMATIC stations.
3. Program the CPUs and the relevant inputs and outputs.
40
Default of the port
Port status
Open when the
Open after configuration
function is ena-
bled.
Closed
Open after configuration
Closed
Open after configuration
Closed
Open after configuration
Closed
Open after configuration
Closed
Open after configuration
Operating Instructions, 10/2016, C79000-G8976-C311-02
Authentication
No
No
No
No
Yes
Yes
CP 1242-7 GPRS V2