Field-orientated control

Limitations
Motor overload factor [%]
p0640 = ...
Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to
maximum inverter current or to 400 % of rated motor current (p0305), whichever is the
lower.
=
p0640
max
CO: Upper torque limit
p1520 = ...
Specifies fixed value for upper
torque limitation.
P1520
def
P1520
max
CO: Lower torque limit
p1521 = ...
Enters fixed value of lower
torque limitation.
=
P1521
def
=
P1521
max
Motoring power limitation
p1530 = ...
Defines fixed value for the max. permissible
motoring active power.
P1530
def
P1530
max
Regenerative power limitation
p1531 = ...
Enters fixed value for the max. permissible
regenerative active power
=
P1531
def
=
P1531
max
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
min
(r0209,
4
p0305)
100
p0305
FC-spec.
torque limit
=
1.5 ⋅
r0333
=
±
4 ⋅
r0333
FC-spec.
1.5 ⋅
r0333
±
4 ⋅
r0333
=
2 ⋅
5 .
P
0307
=
3 ⋅
P
0307
-
2.5
P0307
- ⋅
3
P0307
Resultant
Power
|M|
limitation
r1526
r1527
p1530
p1531
Constant
torque
FC-spec.
Power limitation (motoring, regenerative)
P
=
M
2
⋅ π
f
p1531
FC-spec.
p1530
3 Functions
150.0 %
Stall
limitation
Torque limitation
1
1
~
~
2
f
f
Constant
Stall
f
stall
power
power
M
p1530
p1531
|f
|
act
f
113