Issue 10/06
Fig. 3-90
b) P2181 = 2 / 5
Load torque monitoring as anti-stall protection. This means that when a fault
occurs, the actual load torque is above the permissible tolerance bandwidth.
In this case, the load torque characteristic with maximum permissible load
should be determined.
Fig. 3-91
c) P2181 = 3 / 6
Load torque monitoring to detect whether the drive is blocked (stalled) or a
transmission belt has broken. This means that when a fault occurs, the load
torque is either above or below the permissible tolerance bandwidth. In this
case, the load torque characteristic with the minimum and maximum
permissible load should be determined.
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
|Torque| [Nm]
P2185+P2187+P2189
P2190
P2188
P2186
Load torque characteristic with minimum permissible load
|Torque| [Nm]
P2185
P2187
P2189
P2186+P2188+P2190
P2182
Load torque characteristic with maximum permissible load
Rated load
characteristic
Permissible min.
load characteristic
P2182
P2183
P2184
Permissible max.
load characteristic
P2183
P2184
3 Functions
|Frequency|
[Hz]
Rated load
characteristic
|Frequency|
[Hz]
225