3 Functions
3.10

JOG

Parameter range:
Warnings
Faults
Function chart number:
The JOG function is used as follows:
To check the functionality of the motor and drive inverter after commissioning
has been completed (the first traversing motion, checking the direction of
rotation, etc.)
Positioning a drive / a driven load into a specific position
Traversing a drive, e.g. after a program has been interrupted
The drive is traversed using this function by entering fixed frequencies P1058,
P1059. The JOG mode can be selected either using the operator panel (refer to
Section 3.2), digital inputs or also via the serial interfaces (refer to the example). An
ON/OFF command is not used to move the drive, but when the "JOG keys" are
pressed. These "JOG keys" are selected using the BICO parameters P1055 and
P1056.
DIN
BOP
USS
BOP link
USS
COM link
CB
COM link
Fig. 3-52
If both JOG keys are simultaneously pressed, then the instantaneous frequency is
kept (constant velocity phase) and alarm A0923 is output. When a key is pressed,
the drive inverter accelerates the motor to the fixed frequency in the time entered in
P1060. This frequency is only exited after the key has been cancelled and the drive
then brakes down to 0 Hz in the time entered in P1061.
In addition to the explicit parameterization (P1055 and P1056), the JOG
functionality is also enabled via parameter P0700 or P0719 (implicit
parameterization). In this case, if a value is assigned to P0700, the BICO
parameter is appropriately modified.
172
P1055 – P1061
A0923
-
FP5000
"1"
JOG right
P1055
"0"
(0)
"1"
JOG left
P1056
"0"
(0)
f
P1082
P1058
P1059
-P1082
JOG counter-clockwise and JOG clockwise
A0923
MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
Issue 10/06
A0923
t
t