Advertisement

5.3 GOT Side Settings

5.3.1
Setting communication
interface (Communication
settings)
Set the channel of the equipment to be connected to the
GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: MODBUS
• Controller Type: MODBUS
• I/F: Interface to be used
• Driver: MODBUS/TCP, Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

5.3.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be set and
confirmed in [I/F Communication Setting].For details,
refer to the following.
1.1.2 I/F communication setting
5.3.2
Make the settings according to the usage environment.
(1) GT16, GT14
3.
4.
Item
GOT NET No.
GOT PLC
*2
No.
GOT
IP Address
Click!
Subnet Mask
Default
Gateway
*1
Ethernet
Download Port
*1
No.
GOT
Communication
Port No.
Startup Time
Timeout Time
Delay Time
32bit Storage
5. MODBUS(R)/TCP CONNECTION
Communication detail settings
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
(Default: 1)
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
Set the subnet mask for the sub
network.(Only for connection via
router)
*1
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
connected.(Only for connection via
router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet
module.
(Default: 5020)
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
PLC.
(Default: 0ms)
Select the steps to store two words
(32-bit data).
(Default: LH Order)
5.3 GOT Side Settings
1
2
3
Range
4
1 to 239
1 to 247
0.0.0.0 to
255.255.255.255
5
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
6
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
7
5012, 5013 and
49153)
3 to 255sec
3 to 90sec
8
0 to 10000
(
10 ms)
LH Order/HL Order
5 - 3