Figure 29: IEC 60255 IDMT curves

2.1.2

EUROPEAN STANDARDS

The IEC 60255 IDMT Operate equation is:
β
=
t
T
α
op
M
1
and the IEC 60255 IDMT Reset equation is:
β
=
t
T
α
r
1
M
where:
t
is the operating time
op
t
is the reset time
r
T is the Time Multiplier setting
M is the ratio of the measured current divided by the threshold current (I/Is)
β is a constant, which can be chosen to satisfy the required curve characteristic
α is a constant, which can be chosen to satisfy the required curve characteristic
C is a constant for adding Definite Time (Definite Time adder)
L is a constant (usually only used for ANSI/IEEE curves)
The constant values for the IEC IDMT curves are as follows:
Curve Description
IEC Standard Inverse Operate
IEC Standard Inverse Reset
P14xEd1-TM-EN-1
1000.00
100.00
10.00
1.00
0.10
1
E00600
+
 +
L
C
b constant
0.14
8.2
Chapter 6 - Current Protection Functions
Long Time
Inverse (
Standard Inverse (SI)
Very Inverse (VI)
Extremely Inverse (EI)
100
10
Current (multiples of I
)
S
a constant
0.02
6.45
LTI
)
L constant
0
0