Chapter 18 - Communications

Figure 203: Manual selection of a disturbance record

7.4.6.2
AUTOMATIC EXTRACTION PROCEDURE
There are two methods that can be used for automatically extracting disturbances:
Method 1
Method 1 is simpler and is better at extracting single disturbance records (when the disturbance recorder is polled
regularly).
436
Start
Get number of
disturbances from
register 3x00800
No
Are there
disturbances?
Extract disturbance data
End
V01003
Yes
Get oldest disturbance ID
from register 3x00801
Select required disturbance
by writing the ID value of
the required record to
register 4x00250
Get disturbance time stamp
from registers 3x00930 –
3x00933
P14x
P14xEd1-TM-EN-1