Commissioning the device
4.3 Parameter assignment for Comfort Panel
3. Open the "Set Connection" dialog using the "Set Connection" button.
The following functions are available in the menu bar of this dialog:
4. Press the "Find Controller" button.
The configured communication connections are listed in the "Connection Name" column.
Under "Type", you will find the corresponding S7-1200 or S7-1500 controller. Select the
controller to which you want to establish the communication connection.
The message "No connection available in ProjectSettings.hsf data." is displayed:
– If no project has been loaded
– If there is no communication connection to an S7-1200/S7-1500 in the project
5. If the IP address is to be changed, select the relevant communication connection.
The corresponding IP address is displayed in the "IP address" field.
6. Enter the required IP address in the "IP address" text box.
7. Select "Save".
The change is saved.
154
Save setting
Selected communication connection
List of configured communication connections
Text box for the IP address
Menu
Submenu/Entry
Connection
Save
Exit
Edit
Find Online
Restore to
Project
Function
Saves the selected connection parameters
Close the "Set Connection" dialog
Find controllers in the subnet of your HMI device
Selected PLC
Overwrite IP address of the selected device with the
IP address from the project.
All
Update IP address and device name of the selected
controller
Operating Instructions, 07/2017, A5E36770603-AB
Comfort Panels