Requirement
● The project to be transferred has been opened in WinCC.
● The project tree is displayed.
● The configuration PC is connected to the HMI device.
● Transfer mode is set on the HMI device.
Procedure
1. Select the "Download to device > Software" command in the shortcut menu of the HMI
device.
2. When the "Extended download to device" dialog opens, configure the "Transfer settings".
Make sure that the "Transfer settings" match the "Transfer settings on the HMI device":
– Select the "Ethernet" protocol.
– Configure the corresponding interface parameters on the configuration PC.
– Make the specific interface or protocol settings on the HMI device as required.
– Click "Download".
You can open the "Extended download to device" dialog at any time using the menu
command "Online > Extended download to device...".
The "Load preview" dialog opens. The project is compiled at the same time. The result
appears in the "Load preview" dialog.
3. Check the displayed default settings and change them, if necessary.
4. Click "Download".
The project is transferred to the selected HMI device. If errors or warnings occur during the
transfer, alarms are displayed in the Inspector window under "Info> Download".
When the transfer is completed successfully, the project is executable on the HMI device.
NOTICE
Deactivating automatic transfer
If you do not deactivate automatic transfer after the commissioning phase, the HMI device
can be inadvertently switched to transfer mode. The transfer mode can trigger unintentional
reactions in the system.
Deactivate automatic transfer and lock access to the transfer settings. Assign a password
in the Control Panel. This locks access to the "Transfer Settings" dialog and prevents
unauthorized changes.
Comfort Panels
Operating Instructions, 07/2017, A5E36770603-AB
With Ethernet or PROFINET you can also configure the network address in the
"Devices & Networks" editor in WinCC. You can find more information on this topic in
the online help of WinCC (TIA Portal).