Bay control REC670 2.2
Product version: 2.2.1
Table 50. Voltage-restrained time overcurrent protection VRPVOC
Function
Start overcurrent
Reset ratio, overcurrent
Operate time, start overcurrent at 0 to 2 x I
Reset time, start overcurrent at 2 x I
Operate time, start overcurrent at 0 to 10 x
I
set
Reset time, start overcurrent at 10 x I
Independent time delay to operate at 0 to 2 x
I
set
Inverse time characteristics,
see tables
155
and
156
Minimum operate time for inverse time
characteristics
High voltage limit, voltage dependent
operation
Start undervoltage
Reset ratio, undervoltage
Operate time start undervoltage at 2 x U
0
Reset time start undervoltage at 0 to 2 x U
Independent time delay to operate,
undervoltage at 2 x U
to 0
set
Internal low voltage blocking
Overcurrent:
Critical impulse time
Impulse margin time
Undervoltage:
Critical impulse time
Impulse margin time
ABB
GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8
Range or value
(2.0 - 5000.0)% of IBase
> 95%
Min. = 15 ms
set
Max. = 30 ms
to 0
Min. = 15 ms
set
Max. = 30 ms
Min. = 5 ms
Max. = 20 ms
to 0
Min. = 20 ms
set
Max. = 35 ms
(0.00 - 6000.00) s
13 curve types
(0.00 - 60.00) s
(30.0 - 100.0)% of UBase
(2.0 - 100.0)% of UBase
< 105%
to
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
set
Max. = 30 ms
(0.00 - 6000.00) s
(0.0 - 5.0)% of UBase
10 ms typically at 0 to 2 x I
15 ms typically
10ms typically at 2 x U
15 ms typically
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
±0.2% or ±35 ms whichever is greater
See tables
155
and
±0.2% or ±35 ms whichever is greater
±1.0% of U
r
±0.5% of U
r
-
-
-
±0.2% or ±35 ms whichever is greater
±0.25% of U
r
-
set
-
to 0
set
1MRK 511 404-BEN A
156
69