ABB Relion 650 series ANSI Manual

ABB Relion 650 series ANSI Manual

Iec 61850 communication protocol
Hide thumbs Also See for Relion 650 series ANSI:
Table of Contents

Advertisement

®
Relion
Protection and Control
650 series ANSI
IEC 61850 Communication protocol manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 650 series ANSI

  • Page 1 ® Relion Protection and Control 650 series ANSI IEC 61850 Communication protocol manual...
  • Page 3 Document ID: 1MRK 511 281-UUS Issued: October 2016 Revision: A Product version: 1.3 © Copyright 2013 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction................9 This manual....................9 Intended audience..................9 Product documentation................10 Product documentation set..............10 Document revision history..............11 Related documents................11 Symbols and conventions...............13 Symbols.....................13 Document conventions..............13 Functions included in 650 series IEDs..........14 Section 2 Introduction to IEC 61850............21 Related documentation to IEC 61850..........22 Section 3 Substation Configuration description Language (SCL)..
  • Page 8 Table of contents Tap changer control and supervision, 6 binary inputs TCMYLTC (84)................59 Logical nodes for control.................61 Bay control CBAY................61 Bay control QCBAY..............61 Logical node for interlocking SCILO (3)..........63 Switch controller CSWI..............64 Switch controller SCSWI.............. 64 Logical nodes for conversion functions...........66 Integer to Boolean converter FCVB...........66 Integer to Boolean 16 conversion with logic node representation IB16FCVB.............66...
  • Page 9 Table of contents Instantaneous phase overcurrent protection 3-phase output PHPIOC (50)................94 Instantaneous residual overcurrent protection EFPIOC (50N)..94 Local acceleration logic PLAL............95 Local acceleration logic ZCLCPLAL..........95 Protection scheme PSCH..............96 Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH (85)..........96 Current reversal and WEI logic for distance protection 3- phase ZCRWPSCH (85)...............98...
  • Page 10 Table of contents Thermal overload protection, one time constant, Celsius LCPTTR(26)................129 Thermal overload protection, one time constant, Fahrenheit LFPTTR(26)................131 Thermal overload protection, two time constants TRPTTR (49) 132 Time undercurrent PTUC..............134 Time delayed 2-step undercurrent protection UC2PTUC (37)... 134 Undervoltage PTUV.................137 Two step undervoltage protection UV2PTUV (27).....
  • Page 11 Table of contents Pole discordance protection RPLD ..........155 Pole discrepancy protection CCRPLD (52PD)......155 Power swing detection RPSB............156 Power swing detection ZMRPSB (68)........156 Autoreclosing RREC................157 Autorecloser for 3-phase operation SMBRREC (79)....157 Autorecloser for 1/3-phase operation STBRREC (79)....161 Synchronising RSYN............... 165 Synchronism check, energizing check, and synchronizing SESRSYN (25)................
  • Page 12 Table of contents Logical nodes for sensors and monitoring..........203 Circuit breaker monitoring SCBR............ 203 Breaker close/trip circuit monitoring TCSSCBR......203 Circuit breaker condition monitoring SSCBR......204 Insulation medium supervision (gas) SIMG........208 Insulation gas monitoring function SSIMG (63)......208 Insulation medium supervision (liquid) SIML........210 Insulation liquid monitoring function SSIML (71)......
  • Page 13 Table of contents Section 9 Glossary................227 650 series ANSI Communication protocol manual...
  • Page 15: Section 1 Introduction

    Section 1 1MRK 511 281-UUS A Introduction Section 1 Introduction This manual The communication protocol manual describes the communication protocols supported by the IED. The manual concentrates on the vendor-specific implementations. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an IED perspective.
  • Page 16: Product Documentation

    Section 1 1MRK 511 281-UUS A Introduction Product documentation 1.3.1 Product documentation set Engineering manual Installation manual Commissioning manual Operation manual Application manual Technical manual Communication protocol manual IEC07000220-3-en.vsd IEC07000220 V3 EN Figure 1: The intended use of manuals throughout the product lifecycle The engineering manual contains instructions on how to engineer the IEDs using the various tools available within the PCM600 software.
  • Page 17: Document Revision History

    Section 1 1MRK 511 281-UUS A Introduction during the testing phase. The manual provides procedures for the checking of external circuitry and energizing the IED, parameter setting and configuration as well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service.
  • Page 18 Section 1 1MRK 511 281-UUS A Introduction Documents related to REL650 Identity number Application manual 1MRK 506 334-UUS Technical manual 1MRK 506 335-UUS Commissioning manual 1MRK 506 336-UUS Product Guide 1MRK 506 337-BUS Type test certificate 1MRK 506 337-TUS Application notes for Circuit Breaker Control 1MRG006806 Documents related to RET650 Identity number...
  • Page 19: Symbols And Conventions

    Section 1 1MRK 511 281-UUS A Introduction 650 series manuals Identity number Communication protocol manual, DNP 3.0 1MRK 511 280-UUS Communication protocol manual, IEC 61850–8–1 1MRK 511 281-UUS Communication protocol manual, IEC 60870-5-103 1MRK 511 282-UUS Cyber Security deployment guidelines 1MRK 511 285-UUS Point list manual, DNP 3.0 1MRK 511 283-UUS...
  • Page 20: Functions Included In 650 Series Ieds

    Section 1 1MRK 511 281-UUS A Introduction • Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. • Push button navigation in the LHMI menu structure is presented by using the push button icons.
  • Page 21 Section 1 1MRK 511 281-UUS A Introduction IEC 61850 or Function ANSI Function description name ZGCPDIS Underimpedance protection for generators and transformers LEXPDIS Loss of excitation OOSPPAM Out-of-step protection LEPDIS Load enchroachment Table 2: Backup protection functions IEC 61850 or Function ANSI Function description name...
  • Page 22 Section 1 1MRK 511 281-UUS A Introduction IEC 61850 or Function ANSI Function description name OEXPVPH Overexcitation protection LOVPTUV Loss-of-voltage check STEFPHIZ 59THD 100% Stator ground fault protection, 3rd harmonic based Frequency protection SAPTUF Underfrequency function SAPTOF Overfrequency function SAPFRC Rate-of-change frequency protection Table 3: Control and monitoring functions...
  • Page 23 Section 1 1MRK 511 281-UUS A Introduction IEC 61850 or Function ANSI Function description name ECRWPSCH Current reversal and weak end infeed logic for residual overcurrent protection Logic SMPPTRC Tripping logic, common 3-phase output SPTPTRC Tripping logic, phase segregated output TMAGGIO Trip matrix logic Configurable logic blocks, OR...
  • Page 24 Section 1 1MRK 511 281-UUS A Introduction IEC 61850 or Function ANSI Function description name CMSQI Current sequence component measurement VMSQI Voltage sequence measurement VNMMXU Phase-neutral voltage measurement CNTGGIO Event counter L4UFCNT Event counter with limit supervision DRPRDRE Disturbance report AxRADR Analog input signals BxRBDR...
  • Page 25 Section 1 1MRK 511 281-UUS A Introduction Table 5: Basic IED functions IEC 61850 or Function Function description name Basic functions included in all products INTERRSIG Self-supervision with internal event list ACTVGRP Parameter setting groups TESTMODE Test mode functionality CHNGLCK Change lock function ATHSTAT Authority status...
  • Page 27: Section 2 Introduction To Iec 61850

    Section 2 1MRK 511 281-UUS A Introduction to IEC 61850 Section 2 Introduction to IEC 61850 The general scope of the IEC 61850 protocol standard is designed to support the communication of all functions being performed in the substation. Its’ main goal is interoperability;...
  • Page 28: Related Documentation To Iec 61850

    Section 2 1MRK 511 281-UUS A Introduction to IEC 61850 Detailed information regarding the IEC61850 implementation of the IED 650 is described inside the conformance documents. • MICS, Modeling Information Conformance Statement, contains the declaration of the used logical node types. •...
  • Page 29 Section 2 1MRK 511 281-UUS A Introduction to IEC 61850 Document ID Title IEC 61850-5 Communication networks and systems in First edition 2003-07 substations - Ref. number: IEC 61850-5:2003(E) Part 5: Communication requirements for functions and devices models IEC 61850-6 Communication networks and systems in First edition 2004-03 substations -...
  • Page 30 Section 2 1MRK 511 281-UUS A Introduction to IEC 61850 IEC 61850 PICS 650 series 1.2 - IEC 61850 PICS: 1MRG006609 Protocol implementation conformance statement IEC 61850 PIXIT 650 series 1.2 - IEC 61850 PIXIT: 1MRG006608 Protocol implementation extra information IEC 61850 TICS 650 series 1.2 –...
  • Page 31: Section 3 Substation Configuration Description Language (Scl)

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) Section 3 Substation Configuration description Language (SCL) Three different types of SCL files - SCD, CID and ICD, can be exported from PCM 600. The SCL language is based on XML. However, detailed knowledge of the XML contents is not needed.
  • Page 32: The Substation Section

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) Substation VoltageLevel LNode Communucation Subnetwork Connected AP IED Name AccessPoint Address IED Name AccessPoint Address Services AccessPoint Server Authentication LDevice DataSet Report Control GOOSE Control Inputs SettingControl DataTypeTemplates LNodeType DOType DOType DAType...
  • Page 33: The Communication Section

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) The communication section The organization of the physical IEDs to the communication network is independent of the substation structure. The IEC 61850 standard defines the communication network with no relation to an existing media or protocol. The mapping to an existing media and protocol is specified in IEC 61850–8–1.
  • Page 34: The Ied Section

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) The IED section The IED section describes the complete IED as it is needed for IEC 61850 communication and signal engineering. The data type template part of an IED may be seen as part of the IED, even when separated in its own section.
  • Page 35 Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) Subnetwork Server SB1.LD0 Logical Node LLN0 Data LPHD SXCBR1 SCSWI1 SXSWI1 Health Data SCSWI2 NamePlt Attribute SXSWI2 ctlVal SCSWI3 stVal SXSWI3 OpCnt SCSWI4 BlkOpn SXSWI4 BlkCls Origin ctlModel SCSWI5 CBOpCap CVMMXU1 Control...
  • Page 36: Tool Concept

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) select the requested signals (DOs) and link them to the client IEDs as receiver. When using a dataset for MMS, the requested signals are DOs but when creating a dataset for GOOSE messaging, DAs are used.
  • Page 37 Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) • Included in PCM600 is the new IEC61850 Configuration tool which allows the user to define data sets and control blocks for both Client Server and GOOSE communication. • The IEC61850 Configuration tool gives the user the possibility to make the IEC61850 engineering without export / import step.
  • Page 38: Engineering Concept In Iec 61850-6

    Section 3 1MRK 511 281-UUS A Substation Configuration description Language (SCL) Engineering concept in IEC 61850-6 • Top-down approach means that the system engineering tool has ICD files available for each IED to be included in the system configuration. The ICD files may be of the template type and represent a pre-configured IED.
  • Page 39: Section 4 Communication Profile

    Section 4 1MRK 511 281-UUS A Communication profile Section 4 Communication profile The IEC 61850 standard is conceptually written to be independent of an existing communication media and message transmission concept. Out of this, a specific communication profile is decided and has been commonly used. The profile contains: •...
  • Page 40 Section 4 1MRK 511 281-UUS A Communication profile Generic Generic Object Core Sampled Substation Oriented Time ACSI Status Values Substation Services Sync Event (Multicast) Event TimeSync GOOSE GSSE MMS Protocol Suite (SNTP) TCP/IP ISO CO GSSE UDP/IP T-Profile T-Profile T-Profile ISO/IEC 8802-2 LLC ISO/IEC 8802-3 Ethertype ISO/IEC 8802-3...
  • Page 41: Section 5 Supported Services

    Section 5 1MRK 511 281-UUS A Supported services Section 5 Supported services IEC 61850-7-2 describes the services in the standard. IEC 61850-8-1 describes how the services are applied in the communication. The conformance documents contain the description of the supported services in the IED. Services that are not mentioned in this chapter or in the conformance document are not supported by the IED 650.
  • Page 42 Section 5 1MRK 511 281-UUS A Supported services UnBuffered reporting as well as Buffered reporting is supported. Note that the parameters BufTm and IntPrd shall have the relation BufTm < IntPrd. For best efficiency, the BufTm should have IntPrd as common denominator, for example: n*BufTm = IntPrd, n is an arbitrary number.
  • Page 43 Section 5 1MRK 511 281-UUS A Supported services • SPGGIO - IEC61850 generic communication I/ O functions • DPGGIO - IEC61850 generic communication I/ O functions • MVGGIO - IEC61850 generic communication I/ O functions Control Of the different control sequences, the ‘direct-with-normal-security’ and ‘SBO-with- enhanced’...
  • Page 45: Section 6 Data Sets And Control Blocks

    Section 6 1MRK 511 281-UUS A Data sets and control blocks Section 6 Data sets and control blocks Data sets IEC 61850 has defined data sets and report control blocks to transmit signals for monitoring purposes. Data sets are also used for GOOSE messages in horizontal communication among IEDs.
  • Page 46: Report Control Block (Urcb/Brcb)

    Section 6 1MRK 511 281-UUS A Data sets and control blocks • All data objects or their data attributes can be selected for a data set. • Only those data attributes of a data object can/will be selected which have the same function constraint (FC).
  • Page 47 Section 6 1MRK 511 281-UUS A Data sets and control blocks • When integrity is selected in the trigger option attribute, it is needed to define an integrity period to force the transmission of all data listed in the DataSet. This is done by the attribute Integrity period.
  • Page 48 Section 6 1MRK 511 281-UUS A Data sets and control blocks • This trigger forces the transmission of all process values defined in the data set when a timer value (the integrity period) expires. • general interrogation • This trigger is forced by the clients (= station level IED; NCC gateway, station HMI, ...).
  • Page 49 Section 6 1MRK 511 281-UUS A Data sets and control blocks NCC GW 1 NCC GW m Client 1 Client 2 Client m IHSI1 ITCI1 ITCI2 Subnetwork Server 1 LLN0 DATA-SET LD0/LLN0.AppPos IED 1 LD0/SXCBR1.Pos FC=ST LD0/SXSWI1.Pos FC=ST LD0/SXSWI2.Pos FC=ST LD0/SXSWI3.Pos FC=ST LD0/SXSWI4.Pos FC=ST en06000107.vsd...
  • Page 50: Goose Control Blocks (Gocb)

    Section 6 1MRK 511 281-UUS A Data sets and control blocks GOOSE Control Blocks (GoCB) Data-set Data-set Data-set Subnetwork Comm. Comm. Server Server GoCB GoCB Input Input GoCB GoCB Input Input GoCB GoCB Input Input DataSet DataSet DataSet DataSet DataSet DataSet en06000109.vsd IEC06000109 V2 EN...
  • Page 51 Section 6 1MRK 511 281-UUS A Data sets and control blocks The GOOSE service model of IEC 61850-7-2 provides the possibility for fast and reliable system-wide distribution of input and output data values. This implementation uses a specific scheme of re-transmission to achieve the appropriate level of reliability. When a GOOSE server generates a SendGOOSEMessage request, the current data set values are encoded in a GOOSE message and transmitted on the multicast association.
  • Page 52 Section 6 1MRK 511 281-UUS A Data sets and control blocks Figure shows the GOOSE concept for three IEDs which interchange GOOSE messages between each other. To send GOOSE messages a GoCB must be defined and a data set is needed that contains the data objects of single data attributes to be sent.
  • Page 53: Section 7 Logical Node Data Model

    The IEC 61850 standard does not describe the functionality and way of operation. Each supplier has to describe this separately. ABB has described their function blocks that represent a logical node and all other function blocks in the technical manuals. This chapter in the communication protocol manual has two purposes: •...
  • Page 54: Logical Nodes For Automatic Control

    Section 7 1MRK 511 281-UUS A Logical node data model to be included in each LN. This clause describes the general handling of the data objects within the 650 series products. The mandatory data objects as defined in IEC 61850-7-4 as part of the Common Logical Node are Mode, Behavior, Health and NamePlate.
  • Page 55 Section 7 1MRK 511 281-UUS A Logical node data model Table 6: TR8ATCC (90) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 56 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LoTapPos b_dINS Tap position for minimum voltage Tap position for minimum voltage CircA b_dMV mag.f ICIRCUL Circulating current ICIRCUL Circulating current ICIRCUL Circulating current LodA...
  • Page 57 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description ParOp c_dSPC PARALLEL Transformer operates in parallel mode LTCId v1_dINS stVal Identity of the transformer Identity of the transformer Identity of the transformer ParSet v1_dINS stVal...
  • Page 58 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LVA2On v1_dSPC Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 stVal Setting LVAConst2 is used (service value) Setting LVAConst2 is used (service value) Setting LVAConst2 is used (service value)
  • Page 59 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LVAReset v1_dSPC Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 ForceMast v1_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum...
  • Page 60 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description T3ParGr v1_dSPS T3PG Transformer 3 included in parallel group T3PG Transformer 3 included in parallel group T4ParGr v1_dSPS stVal T4PG Transformer 4 included in parallel group T4PG Transformer 4 included in parallel...
  • Page 61 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description HiVArFwd v1_dSPS stVal QGTFWD Reactive power above the set limit powerReactiveForw QGTFWD Reactive power above the set limit powerReactiveForw QGTFWD Reactive power above the set limit powerReactiveForw HiVArRv v1_dSPS...
  • Page 62 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description HrHuntAlm v1_dSPS HOURHUNT Number of commands within the latest hour exceeded maximum level HOURHUNT Number of commands within the latest hour exceeded maximum level HuntAlm v1_dSPS stVal...
  • Page 63 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LodARe V11_dMV ATCCOUT Group connection to YLTCIN BusV V12_dMV mag.f ATCCOUT Group connection to YLTCIN ATCCOUT Group connection to YLTCIN ATCCOUT Group connection to YLTCIN SetV V13_dMV...
  • Page 64 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description BndCtrSng v2_dMV Voltage setpoint single BndCtrPar v2_dMV mag.f VSETPAR Average voltage setpoint used in parallel mode VSETPAR Average voltage setpoint used in parallel mode VSETPAR Average voltage setpoint used in...
  • Page 65: Tap Changer Control And Supervision, 6 Binary Inputs Tcmyltc (84)

    Section 7 1MRK 511 281-UUS A Logical node data model 7.2.1.2 Tap changer control and supervision, 6 binary inputs TCMYLTC (84) LN type LN prefix LN class Function block name TCMYLTC (revision 1) TCM YLTC TCMYLTC (84) Table 7: TCMYLTC (84) Logical node data DO name DO type DA name...
  • Page 66 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description HiTapPos v1_dINS Tap position for the highest voltage Tap position for the highest voltage LoTapPos v1_dINS stVal Tap position for the lowest voltage Tap position for the lowest voltage Tap position for the lowest voltage OpRs...
  • Page 67: Logical Nodes For Control

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description TapChgFlt v1_dSPS TCERRAL Alarm for none or illegal tap position change TapPosFlt v1_dSPS stVal POSERRAL Alarm that indicates a problem with the position indication POSERRAL Alarm that indicates a problem with the...
  • Page 68 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 LocSwPos v1_dINS stVal Position of the Local/Remote switch Position of the Local/Remote switch Position of the Local/Remote switch SrcOpPrm...
  • Page 69: Logical Node For Interlocking Scilo (3)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description v1_dSPS stVal Remote operation allowed Remote operation allowed Remote operation allowed 7.3.2 Logical node for interlocking SCILO (3) LN type LN prefix LN class Function block name SCILO (revision 1) S CILO SCILO (3)
  • Page 70: Switch Controller Cswi

    Section 7 1MRK 511 281-UUS A Logical node data model 7.3.3 Switch controller CSWI 7.3.3.1 Switch controller SCSWI LN type LN prefix LN class Function block name SCSWI (revision 1) S CSWI SCSWI Table 10: SCSWI Logical node data DO name DO type DA name Signal...
  • Page 71 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test...
  • Page 72: Logical Nodes For Conversion Functions

    Section 7 1MRK 511 281-UUS A Logical node data model Logical nodes for conversion functions 7.4.1 Integer to Boolean converter FCVB 7.4.1.1 Integer to Boolean 16 conversion with logic node representation IB16FCVB LN type LN prefix LN class Function block name IB16FCVB (revision 0) IB16 FCVB IB16FCVB...
  • Page 73: Boolean To Integer Converter Fcvi

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description ISCSO b_dINC Integer to be converted to bit pattern OUT1 to OUT16 Integer to be converted to bit pattern OUT1 to OUT16 ctlModel Used by CH 7.4.2...
  • Page 74: Logical Nodes For Protection Functions

    Section 7 1MRK 511 281-UUS A Logical node data model Logical nodes for protection functions 7.5.1 Differential protection PDIF 7.5.1.1 Transformer differential protection, two winding T2WPDIF (87T) LN type LN prefix LN class Function block name T2WPDIF (revision 2) T2W PDIF T2WPDIF (87T) Table 13:...
  • Page 75 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpRst v1_dSPS TRIPRES Trip signal from restrained differential protection TRIPRES Trip signal from restrained differential protection OpNSSen v1_dSPS stVal TRNSSENS Trip signal from sensitive negative sequence differential protection TRNSSENS Trip signal from sensitive negative...
  • Page 76: Transformer Differential Protection, Three Winding T3Wpdif (87T)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description ItrFlt v1_dSPS Indication that internal fault has been detected Indication that internal fault has been detected DifAlm v1_dSPS stVal IDALARM General alarm for sustained differential currents IDALARM General alarm for sustained differential...
  • Page 77 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 b_dACT general TRIP Common trip signal TRIP Common trip signal TRIP Common trip signal OpRst v1_dSPS stVal TRIPRES Trip signal from restrained differential...
  • Page 78: Restricted Earth-Fault Protection, Low Impedance Refpdif (87N)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description ExFlt v1_dSPS Indication that external fault/ disturbance has been detected Indication that external fault/ disturbance has been detected ItrFlt v1_dSPS stVal Indication that internal fault has been detected Indication that internal fault has been...
  • Page 79: Generator Differential Protection Genpdif (87G)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 b_dACD general PICKUP General pickup signal PICKUP General pickup signal PICKUP General pickup signal b_dACT general TRIP Common trip signal TRIP...
  • Page 80 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description aINC Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 aINS...
  • Page 81 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpUnRst v1SPS TRIPUNRE Trip signal from unrestrained differential protection OpNSUnRst v1SPS stVal TRNSUNR Trip signal from unrestrained negative sequence differential protection TRNSUNR Trip signal from unrestrained negative sequence differential protection...
  • Page 82: 1Ph High Impedance Differential Protection Hzpdif (87)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpnCTAlm v1SPS stVal OPENCTAL Open CT Alarm output signal. Issued after a delay ... OPENCTAL Open CT Alarm output signal. Issued after a delay ...
  • Page 83: Distance Protection Pdis

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACT general TRIP Trip signal TRIP Trip signal TRIP Trip signal ImpAlm v1_dSPS stVal ALARM...
  • Page 84 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 Table 19: ZQMPDIS (21) Logical node data (instance 1) DO name...
  • Page 85 Section 7 1MRK 511 281-UUS A Logical node data model Table 21: ZQMPDIS (21) Logical node data (instance 3) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general Z3_PU...
  • Page 86 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD general Z5_PU Start signal Zone5 Z5_PU Start signal Zone5 Z5_PU Start signal Zone5 b_dACT general TRZ5 Trip signal Zone5 TRZ5 Trip signal Zone5 TRZ5 Trip signal Zone5...
  • Page 87: Phase Selection With Load Encroachment, Quadrilateral Characteristic Fdpspdis (21)

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.2.2 Phase selection with load encroachment, quadrilateral characteristic FDPSPDIS (21) LN type LN prefix LN class Function block name FDPSPDIS (revision 1) FDPS PDIS FDPSPDIS Table 25: FDPSPDIS Logical node data DO name DO type DA name...
  • Page 88 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description StrCndA v1_dINS DLECND Pickup for load encroachment and 3I0 StrFwdPhA v1_dSPS stVal FWD_A Fault detected in phaseA - forward direction FWD_A Fault detected in phaseA - forward direction FWD_A...
  • Page 89 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description StrRvGnd v1_dSPS stVal REV_G Ground fault detected in reverse direction REV_G Ground fault detected in reverse direction REV_G Ground fault detected in reverse direction StrNDPhA v1_dSPS...
  • Page 90: Faulty Phase Identification With Load Enchroachment For Mho Fmpspdis (21)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description Str3Ph v1_dSPS FWD_3PH Pick up in forward direction for three- phase fault RelGnd v1_dSPS stVal PHG_FLT Current conditions release of Phase- Ground measuring elements PHG_FLT Current conditions release of Phase-...
  • Page 91: Underimpedance Protection For Generators And Transformers Zgcpdis (21G)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 e_dACD general...
  • Page 92 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 Table 28: ZGCPDIS (21G) Logical node data (instance 1) DO name...
  • Page 93: Loss Of Excitation Lexpdis (40)

    Section 7 1MRK 511 281-UUS A Logical node data model Table 30: ZGCPDIS (21G) Logical node data (instance 3) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general Z3_PU...
  • Page 94 Section 7 1MRK 511 281-UUS A Logical node data model Table 32: LEXPDIS (40) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 95: Load Enchroachment Lepdis

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description PriReact v2_dMV mag.f XOHM Reactance in Primary Ohms XOHM Reactance in Primary Ohms XOHM Reactance in Primary Ohms 7.5.2.6 Load enchroachment LEPDIS LN type LN prefix LN class Function block name LEPDIS (revision 0) LE...
  • Page 96: Directional Overpower Pdop

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description e_dACD neut Ground fault detected General pickup signal General pickup signal 7.5.3 Directional overpower PDOP 7.5.3.1 Directional over-power protection GOPPDOP (32) LN type LN prefix LN class Function block name GOPPDOP (revision 1) GOP...
  • Page 97: Directional Underpower Pdup

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpZ1 v1_dSPS TRIP1 Trip signal from stage 1 OpZ2 v1_dSPS stVal TRIP2 Trip signal from stage 2 TRIP2 Trip signal from stage 2 TRIP2 Trip signal from stage 2 StrZ1...
  • Page 98: Rate Of Change Of Frequency Pfrc

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general BFI_3P General pickup signal BFI_3P General pickup signal BFI_3P General pickup signal...
  • Page 99 Section 7 1MRK 511 281-UUS A Logical node data model Table 36: SAPFRC (81) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 100: Instantaneous Overcurrent Pioc

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.6 Instantaneous overcurrent PIOC 7.5.6.1 Instantaneous phase overcurrent protection 3-phase output PHPIOC (50) LN type LN prefix LN class Function block name PHPIOC (revision 1) PH PIOC PHPIOC (50) Table 37: PHPIOC (50) Logical node data DO name DO type...
  • Page 101: Local Acceleration Logic Plal

    Section 7 1MRK 511 281-UUS A Logical node data model Table 38: EFPIOC (50N) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 102: Protection Scheme Psch

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 OpLosLod...
  • Page 103 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 Behaviour parameter for 61850 LosOfGrd a_dSPS stVal Loss of channel guard signal output from communication scheme logic Loss of channel guard signal output from communication scheme logic Loss of channel guard signal output...
  • Page 104: Current Reversal And Wei Logic For Distance Protection 3- Phase Zcrwpsch (85)

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.8.2 Current reversal and WEI logic for distance protection 3-phase ZCRWPSCH (85) LN type LN prefix LN class Function block name ZCRWPSCH (revision 2) ZCRW PSCH ZCRWPSCH (85) Table 41: ZCRWPSCH (85) Logical node data DO name DO type...
  • Page 105: Scheme Communication Logic For Residual Overcurrent Protection Ecpsch (85)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description ProTx a_dSPS ECHO A signal that indicates channel start (CS) by WEI logic b_dACD general ECHO A signal that indicates channel start (CS) by WEI logic ECHO A signal that indicates channel start...
  • Page 106 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 ProRx a_dSPS...
  • Page 107: Current Reversal And Weak-End Infeed Logic For Residual Overcurrent Protection Ecrwpsch (85)

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.8.4 Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH (85) LN type LN prefix LN class Function block name ECRWPSCH (revision 2) ECRW PSCH ECRWPSCH (85) Table 43: ECRWPSCH (85) Logical node data DO name DO type...
  • Page 108: Sensitive Directional Ground Fault Psde

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TRWEI Trip of WEI logic TRWEI Trip of WEI logic RvABlk b_dACT general IRVL Operation of current reversal logic IRVL Operation of current reversal logic IRVL Operation of current reversal logic...
  • Page 109 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general START General start signal...
  • Page 110: Switch Onto Fault Logic Psof

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpDirResA v1_dSPS stVal TRDIRIN Trip of the directional residual overcurrent TRDIRIN Trip of the directional residual overcurrent TRDIRIN Trip of the directional residual overcurrent AngAV v2_dMV...
  • Page 111: Time Over Current Ptoc

    Section 7 1MRK 511 281-UUS A Logical node data model Table 45: ZCVPSOF Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 112 Section 7 1MRK 511 281-UUS A Logical node data model Table 46: EF4PTOC (51N_67N) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850...
  • Page 113 Section 7 1MRK 511 281-UUS A Logical node data model Table 48: EF4PTOC (51N_67N) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general STDIR...
  • Page 114 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TRST1 Trip signal from step 1 c_dINC stVal Mode status value parameter for 61850 Mode status value parameter for 61850 Mode status value parameter for 61850 Table 51: EF4PTOC (51N_67N) Logical node data (instance 2)
  • Page 115: Four Step Phase Overcurrent Protection 3-Phase Output Oc4Ptoc (51/67)

    Section 7 1MRK 511 281-UUS A Logical node data model Table 53: EF4PTOC (51N_67N) Logical node data (instance 4) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general PU_ST4...
  • Page 116 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 Table 55: OC4PTOC (51_67) Logical node data (instance 1) DO name DO type DA name...
  • Page 117 Section 7 1MRK 511 281-UUS A Logical node data model Table 57: OC4PTOC (51_67) Logical node data (instance 2) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general Start signal from step 2...
  • Page 118 Section 7 1MRK 511 281-UUS A Logical node data model Table 59: OC4PTOC (51_67) Logical node data (instance 4) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general Start signal from step 4...
  • Page 119: Four Step Phase Overcurrent Protection, Phase Segregated Output Oc4Sptoc

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.11.3 Four step phase overcurrent protection, phase segregated output OC4SPTOC LN type LN prefix LN class Function block name GEN4PHAR instance 1 (revision 2) GEN4 PHAR OC4SPTOC (51_67) OC4SLLN0 instance 1 (revision 0) LLN0 OC4SPTOC (51_67) PH3PTOC instance 1 (revision 1)
  • Page 120 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 Table 63: OC4SPTOC (51_67) Logical node data (instance 1)
  • Page 121 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 Table 65: OC4SPTOC (51_67) Logical node data (instance 3) DO name DO type DA name...
  • Page 122: Stub Protection Stbptoc (50Stb)

    Section 7 1MRK 511 281-UUS A Logical node data model Table 67: OC4SPTOC (51_67) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dACD general START General start signal phsA STL1 Start signal from phase L1 dirPhsA DIRL1 Direction for phase L1...
  • Page 123: Broken Conductor Check Brcptoc (46)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal...
  • Page 124: Negative Sequence Based Overcurrent Function Dnsptoc (46)118

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general PICKUP Pickup signal of the protection logic PICKUP Pickup signal of the protection logic PICKUP...
  • Page 125 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 Table 71: DNSPTOC (46) Logical node data (instance 1) DO name...
  • Page 126: Negative-Sequence Time Overcurrent Protection For Machines Ns2Ptoc (46I2)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TROC2 Trip signal from step 2 (OC2) c_dINC stVal Mode status value parameter for 61850 Mode status value parameter for 61850 Mode status value parameter for 61850 Table 73: DNSPTOC (46) Logical node data (instance 1)
  • Page 127 Section 7 1MRK 511 281-UUS A Logical node data model Table 74: NS2PTOC (46I2) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850...
  • Page 128: Overfrequency Ptof

    Section 7 1MRK 511 281-UUS A Logical node data model Table 76: NS2PTOC (46I2) Logical node data (instance 2) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general PU_ST2...
  • Page 129: Overvoltage Ptov

    Section 7 1MRK 511 281-UUS A Logical node data model LN type LN prefix LN class Function block name SAPTOF (revision 1) SA PTOF SAPTOF (81) Table 78: SAPTOF (81) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC...
  • Page 130 Section 7 1MRK 511 281-UUS A Logical node data model OV2PTOV instance 1 (revision 1) PTOV OV2PTOV (59) OV2PTOV instance 2 (revision 1) PTOV OV2PTOV (59) PH3PTRC instance 1 (revision 1) PTRC OV2PTOV (59) Table 79: OV2PTOV (59) Logical node data (instance 1) DO name DO type DA name...
  • Page 131 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 Table 81: OV2PTOV (59) Logical node data (instance 2) DO name DO type DA name...
  • Page 132: Two Step Residual Overvoltage Protection Rov2Ptov (59N)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description c_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 7.5.13.2 Two step residual overvoltage protection ROV2PTOV (59N) LN type LN prefix LN class Function block name GEN2LLN0 instance 1 (revision 1)
  • Page 133 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD general PICKUP General pickup signal PICKUP General pickup signal PICKUP General pickup signal b_dACT general TRIP Common trip signal TRIP Common trip signal TRIP Common trip signal...
  • Page 134: Protection Trip Conditioning Ptrc

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT general TRST2 Trip signal from step 2 TRST2 Trip signal from step 2 TRST2 Trip signal from step 2 c_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850...
  • Page 135: Thermal Overload Pttr

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LORs v1_dSPC Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check...
  • Page 136 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description AlmThm a_dSPS stVal ALARM Alarm signal ALARM Alarm signal ALARM Alarm signal b_dACD general PICKUP General pickup signal PICKUP General pickup signal PICKUP General pickup signal b_dACT...
  • Page 137: Thermal Overload Protection, One Time Constant, Fahrenheit Lfpttr(26)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description TmpAmb v2_dMV mag.f TEMPAMB Ambient temperature used in the calculations TEMPAMB Ambient temperature used in the calculations TEMPAMB Ambient temperature used in the calculations 7.5.15.2 Thermal overload protection, one time constant, Fahrenheit LFPTTR(26)
  • Page 138: Thermal Overload Protection, Two Time Constants Trpttr (49)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TRIP Common trip signal b_dMV mag.f TEMP Calculated temperature of the device TEMP Calculated temperature of the device TEMP Calculated temperature of the device TmpRl b_dMV mag.f...
  • Page 139 Section 7 1MRK 511 281-UUS A Logical node data model Table 90: TRPTTR (49) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 140: Time Undercurrent Ptuc

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description TmmRsLO v2_dMV mag.f TRESLO Estimated time to reset of the function (in min) TRESLO Estimated time to reset of the function (in min) TRESLO Estimated time to reset of the function...
  • Page 141 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dACD General pickup signal a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACT general TRIP Common trip signal TRIP Common trip signal...
  • Page 142 Section 7 1MRK 511 281-UUS A Logical node data model Table 93: UC2PTUC (37) Logical node data (instance 2) DO name DO type DA name Signal Mon/C Description a_dACD general PU_ST2 Start of step 2 phsA Start signal for step 2 in L1 phsB Start signal for step 2 in L2 phsC...
  • Page 143: Undervoltage Ptuv

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.17 Undervoltage PTUV 7.5.17.1 Two step undervoltage protection UV2PTUV (27) LN type LN prefix LN class Function block name GEN2LLN0 instance 1 (revision 1) - LLN0 UV2PTUV (27) PH3PTRC instance 1 (revision 1) PTRC UV2PTUV (27) UV2PTUV instance 1 (revision 1)
  • Page 144 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACT general TRIP Common trip signal TRIP Common trip signal TRIP Common trip signal...
  • Page 145: Loss Of Voltage Check Lovptuv (27)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dACD phsC Pickup signal from step2 phase C PU_ST2 Start signal from step 2 PU_ST2 Start signal from step 2 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850...
  • Page 146: Underfrequency Ptuf

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD PICKUP Pickup signal PICKUP Pickup signal b_dACT general TRIP Trip signal TRIP Trip signal TRIP Trip signal 7.5.18 Underfrequency PTUF 7.5.18.1 Underfrequency protection SAPTUF (81) LN type...
  • Page 147: Volts Per Hz Pvph

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACT TRIP Common trip signal BlkLoMg v1_dSPS stVal BLKDMAGN Measurement blocked due to low voltage amplitude BLKDMAGN Measurement blocked due to low voltage amplitude BLKDMAGN Measurement blocked due to low...
  • Page 148: Multipurpose Analog Protection Gapc

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dACD general General pickup signal General pickup signal General pickup signal b_dACT general TRIP Common trip signal TRIP Common trip signal TRIP Common trip signal ExtAlm...
  • Page 149: Out-Of-Step Protection Ppam

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general START Start signal from accidental energizing protection START Start signal from accidental energizing protection START Start signal from accidental energizing...
  • Page 150 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status value parameter for 61850 Mode status value parameter for 61850 Mode status value parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850...
  • Page 151: Ground Fault Protection Phiz

    Section 7 1MRK 511 281-UUS A Logical node data model 7.5.22 Ground fault protection PHIZ 7.5.22.1 100% Stator ground fault protection, 3rd harmonic based STEFPHIZ (59THD) LN type LN prefix LN class Function block name STEFPHIZ (revision 2) STEF PHIZ STEFPHIZ (59THD) Table 104: STEFPHIZ (59THD) Logical node data...
  • Page 152 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description OpUN v1_dSPS TRIP_VN Trip by fund. freq. neutral over-voltage protection TRIP_VN Trip by fund. freq. neutral over-voltage protection Str3rdH v1_dSPS stVal PU_3H Start by one of two 3rd harmonic voltage-based prot.
  • Page 153: Voltage-Restrained Time Overcurrent Pvoc

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description v2_dMV mag.f Fund. frequency voltage at generator neutral Fund. frequency voltage at generator neutral Fund. frequency voltage at generator neutral VolAngClc v2_dMV mag.f ANGLE...
  • Page 154 Section 7 1MRK 511 281-UUS A Logical node data model Table 106: VRPVOC (51V) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general STUV...
  • Page 155: System Logical Nodes

    Section 7 1MRK 511 281-UUS A Logical node data model Table 108: VRPVOC (51V) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACD general STOC...
  • Page 156: Logical Nodes For Protection Related Functions

    Section 7 1MRK 511 281-UUS A Logical node data model Logical nodes for protection related functions 7.7.1 Breaker failure RBRF 7.7.1.1 Breaker failure protection 3-phase activation and output CCRBRF (50BF) LN type LN prefix LN class Function block name CCRBRF (revision 1) CC RBRF CCRBRF (50BF) Table 110:...
  • Page 157: Breaker Failure Protection Phase Segregated Activation And Output Csprbrf (50Bf)

    Section 7 1MRK 511 281-UUS A Logical node data model 7.7.1.2 Breaker failure protection phase segregated activation and output CSPRBRF (50BF) LN type LN prefix LN class Function block name CSPRBRF (revision 0) CSP RBRF CSPRBRF (50BF) Table 111: CSPRBRF (50BF) Logical node data DO name DO type DA name...
  • Page 158: Disturbance Recorder Rdre

    Section 7 1MRK 511 281-UUS A Logical node data model LN type LN prefix LN class Function block name CCSRDIF (revision 1) CCS RDIF CCSRDIF (87) Table 112: CCSRDIF (87) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC...
  • Page 159: Fault Locator Rflo

    Section 7 1MRK 511 281-UUS A Logical node data model Table 113: DRPRDRE Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 160: Fuse Failure Supervision Rfuf

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Mode status value parameter for 61850 Mode status value parameter for 61850 a_dINS...
  • Page 161: Pole Discordance Protection Rpld

    Section 7 1MRK 511 281-UUS A Logical node data model Table 115: SDDRFUF Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 162: Power Swing Detection Rpsb

    Section 7 1MRK 511 281-UUS A Logical node data model Table 116: CCRPLD (52PD) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 163: Autoreclosing Rrec

    Section 7 1MRK 511 281-UUS A Logical node data model Table 117: ZMRPSB (68) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter...
  • Page 164: Do Name Do Type Da Name Fc Signal

    Section 7 1MRK 511 281-UUS A Logical node data model LN type LN prefix LN class Function block name SMBRREC (revision 2) SMB RREC SMBRREC (79) Table 118: SMBRREC (79) Logical node data DO name DO type DA name Signal Mon/C Description a_dINC...
  • Page 165 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description Rec32Cnt v1_dINS stVal COUNT3P2 Counting the number of three-phase reclosing shot 2 COUNT3P2 Counting the number of three-phase reclosing shot 2 COUNT3P2 Counting the number of three-phase reclosing shot 2...
  • Page 166 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description RdyRec v1_dSPS READY Indicates that AR is ready for a new sequence READY Indicates that AR is ready for a new sequence ActRec v1_dSPS...
  • Page 167: Autorecloser For 1/3-Phase Operation Stbrrec (79)

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description PrgRec34 v1_dSPS stVal 3PT4 Three-phase reclosing in progress, shot 4 3PT4 Three-phase reclosing in progress, shot 4 3PT4 Three-phase reclosing in progress, shot 4 PrgRec35 v1_dSPS...
  • Page 168 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS Behaviour parameter for 61850 Behaviour parameter for 61850 b_dACT general CLOSECMD Closing command for CB CLOSECMD Closing command for CB CLOSECMD Closing command for CB BlkRec...
  • Page 169 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description Rec35Cnt v1_dINS COUNT3P5 Counting the number of three-phase reclosing shot 5 COUNT3P5 Counting the number of three-phase reclosing shot 5 TotRecCnt v1_dINS stVal COUNTAR...
  • Page 170 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description UnsRec v1_dSPS stVal UNSUCCL Reclosing unsuccessful, signal resets after the reclaim time UNSUCCL Reclosing unsuccessful, signal resets after the reclaim time UNSUCCL Reclosing unsuccessful, signal resets after the reclaim time...
  • Page 171: Synchronising Rsyn

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description WtMst v1_dSPS WFMASTER Signal to Slave issued by Master for sequential reclosing WFMASTER Signal to Slave issued by Master for sequential reclosing PrgRec11 v1_dSPS stVal...
  • Page 172 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description HzInd a_dSPS FRDIFFA Frequency difference out of limit for Auto operation FRDIFFA Frequency difference out of limit for Auto operation AngInd a_dSPS stVal PHDIFFA...
  • Page 173 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description VLin v2_dMV mag.f VLine Line voltage VLine Line voltage VLine Line voltage Table 121: SESRSYN (25) Logical node data (instance 2) DO name DO type DA name...
  • Page 174 Section 7 1MRK 511 281-UUS A Logical node data model Table 122: SESRSYN (25) Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850...
  • Page 175 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description VHiAlm v1_dSPS VOKSC Voltage magnitudes above set limits InadCBCls v1_dSPS stVal INADVCLS Inadvertent circuit breaker closing INADVCLS Inadvertent circuit breaker closing INADVCLS Inadvertent circuit breaker closing Table 123:...
  • Page 176: Logical Nodes For Generic References

    Section 7 1MRK 511 281-UUS A Logical node data model Logical nodes for generic references 7.8.1 Generic process I/O GGIO 7.8.1.1 Select Release SELGGIO LN type LN prefix LN class Function block name SELGGIO (revision 1) SEL GGIO SELGGIO Table 124: SELGGIO Logical node data DO name DO type...
  • Page 177 Section 7 1MRK 511 281-UUS A Logical node data model Table 125: SLGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 178: Selector Mini Switch Vsggio

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SPCCO v2_dSPC Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 ctlModel Used by CH sboTimeout Used by CH sboClass Used by CH 7.8.1.3 Selector mini switch VSGGIO...
  • Page 179: Iec61850 Generic Communication I/O Functions Dpggio

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description DPCSO d_dDPC Oper.origin.orIdent Command parameter for IEC61850 Cancel.origin.orIdent Command parameter for IEC61850 Cancel.ctlNum Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 SBOw.ctlNum Command parameter for IEC61850 Oper.T...
  • Page 180: Single Point Generic Control 8 Signals Spc8Ggio

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 DPCSO...
  • Page 181 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO1 v2_dSPC Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 stVal OUT1 Output 1...
  • Page 182 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO4 v2_dSPC OUT4 Output4 SPCSO5 v2_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T...
  • Page 183: Event Counter Cntggio

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SPCSO8 v2_dSPC Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 stVal OUT8 Output8 OUT8 Output8 OUT8 Output8 7.8.1.6 Event counter CNTGGIO LN type LN prefix LN class Function block name CNTGGIO (revision 1) CNT...
  • Page 184: Event Counter With Limit Supervision L4Ufcnt

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description Cnt3 v1_dBCR VALUE3 Output of counter 3 VALUE3 Output of counter 3 Cnt4 v1_dBCR actVal VALUE4 Output of counter 4 VALUE4 Output of counter 4 VALUE4 Output of counter 4...
  • Page 185 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.T Mode status value parameter for 61850 Oper.Test Mode status value parameter for 61850 Oper.Check Mode status value parameter for 61850 stVal Mode parameter for 61850 Mode parameter for 61850...
  • Page 186: Iec61850 Generic Communication I/O Functions Spggio

    Section 7 1MRK 511 281-UUS A Logical node data model 7.8.1.8 IEC61850 generic communication I/O functions SPGGIO LN type LN prefix LN class Function block name SPGGIO (revision 1) SP GGIO SPGGIO Table 131: SPGGIO Logical node data DO name DO type DA name Signal...
  • Page 187 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check Mode parameter stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal...
  • Page 188: Iec 61850 Generic Communication I/O Functions Mvggio

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description Ind9 c_dSPS OUT9 Output 9 status Ind10 c_dSPS stVal OUT10 Output 10 status OUT10 Output 10 status OUT10 Output 10 status Ind11 c_dSPS stVal...
  • Page 189: Pulse-Counter Logic Pcggio

    Section 7 1MRK 511 281-UUS A Logical node data model Table 133: MVGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 190: Trip Matrix Logic Tmaggio

    Section 7 1MRK 511 281-UUS A Logical node data model Table 134: PCGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 191: Elapsed Time Integrator With Limit Transgression And Overflow Supervision Teiggio

    Section 7 1MRK 511 281-UUS A Logical node data model Table 135: TMAGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 192 Section 7 1MRK 511 281-UUS A Logical node data model Table 136: TEIGGIO Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 193: Logical Nodes For Metering And Measurement

    Section 7 1MRK 511 281-UUS A Logical node data model Logical nodes for metering and measurement 7.9.1 Metering MMTR 7.9.1.1 Function for energy calculation and demand handling ETPMMTR LN type LN prefix LN class Function block name ETPMMTR (revision 3) ETP MMTR ETPMMTR Table 137:...
  • Page 194 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description MaxDmdRs v1_dSPC Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check Command parameter for IEC61850 StrAcc v1_dSPS stVal ACCST Start of accumulating energy values ACCST Start of accumulating energy values...
  • Page 195: Non Phase Related Measurement Mmxn

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description WsAccFwd v2_dBCR actVal EAFACC Accumulated forward active energy value EAFACC Accumulated forward active energy value EAFACC Accumulated forward active energy value WsAccRev v2_dBCR actVal...
  • Page 196 Section 7 1MRK 511 281-UUS A Logical node data model Table 138: CVMMXN Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter Oper.origin.orCat Mode parameter Oper.origin.orIdent Mode parameter Oper.ctlNum Mode parameter Oper.T Mode parameter Oper.Test Mode parameter Oper.Check...
  • Page 197 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dMV rangeC.lLim.f FrLowLim Low limit (physical value) rangeC.llLim.f FrLowLowLim Low Low limit (physical value) rangeC.max.f FrMax Maximum value rangeC.min.f FrMin Minimum value subMag.f Substituted value range...
  • Page 198 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dMV subMag.f Substituted value mag.f Calculated voltage magnitude of deadband value range U_RANGE Calcuated voltage range Calculated voltage magnitude of deadband value Calculated voltage magnitude of deadband value subEna...
  • Page 199 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description VolAmpr a_dMV range Q_RANGE Reactive power range Reactive power magnitude of deadband value Reactive power magnitude of deadband value subEna Enable substitution QDbRepInt Cycl: Report interval (s), Db: In % of range, Int Db: In %s...
  • Page 200: Measurement Mmxu

    Section 7 1MRK 511 281-UUS A Logical node data model 7.9.3 Measurement MMXU 7.9.3.1 Phase current measurement CMMXU LN type LN prefix LN class Function block name CMMXU (revision 1) C MMXU CMMXU Table 139: CMMXU Logical node data DO name DO type DA name Signal...
  • Page 201: Phase-Phase Voltage Measurement Vmmxu

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dWYE rangeC.min.f ILMin Minimum value rangeC.max.f ILMax Maximum value rangeC.max.f ILMax Maximum value rangeC.max.f ILMax Maximum value cVal.mag.f IA Amplitude cVal.mag.f IB Amplitude cVal.mag.f IC Amplitude...
  • Page 202 Section 7 1MRK 511 281-UUS A Logical node data model Table 140: VMMXU Logical node data DO name DO type DA name Signal Mon/C Description a_dDEL rangeC.hhLim.f VLHiHilLim High High limit (physical value) rangeC.hhLim.f VLHiHilLim High High limit (physical value) rangeC.hhLim.f VLHiHilLim High High limit (physical value)
  • Page 203: Phase-Neutral Voltage Measurement Vnmmxu

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dDEL subEna Enable substitution subEna Enable substitution VLDbRepInt Cycl: Report interval (s), Db: In % of range, Int Db: In %s VLDbRepInt Cycl: Report interval (s), Db: In % of range, Int Db: In %s...
  • Page 204 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850...
  • Page 205: Sequence And Imbalance Msqi

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dWYE range VC_RANGE V_C Amplitude range range VA_RANGE V_A Amplitude range range VB_RANGE V_B Amplitude range V_C Amplitude, magnitude of reported value V_B Amplitude, magnitude of reported value...
  • Page 206 Section 7 1MRK 511 281-UUS A Logical node data model Table 142: CMSQI Logical node data DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlVal Mode parameter for 61850 Oper.origin.orCat Mode parameter for 61850 Oper.origin.orIdent Mode parameter for 61850 Oper.ctlNum Mode parameter for 61850 Oper.T...
  • Page 207: Voltage Sequence Measurement Vmsqi

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SeqA a_dSEQ rangeC.max.f I2Max Maximum value subCVal.mag.f Substituted value subCVal.mag.f Substituted value range I2RANG I2 Magnitude range range 3I0RANG 3I0 Magnitude range range I1RANG I1Amplitude range...
  • Page 208 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850...
  • Page 209: Logical Nodes For Sensors And Monitoring

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description SeqV a_dSEQ range V1RANG V1 Magnitude range U2 Amplitude U1 Amplitude 3U0 Amplitude 3U0 Amplitude U1 Amplitude U2 Amplitude subEna Enable substitution subEna Enable substitution subEna...
  • Page 210: Circuit Breaker Condition Monitoring Sscbr

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850...
  • Page 211 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description InaTmdCnt v1_dINS stVal NOOPRDAY The number of days CB has been inactive NOOPRDAY The number of days CB has been inactive NOOPRDAY The number of days CB has been inactive...
  • Page 212 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description RsSprChaTm v1_dSPC Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T Command parameter for IEC61850 Oper.Test Command parameter for IEC61850 Oper.Check...
  • Page 213 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description LonTmAlm v1_dSPS NOOPRALM CB 'not operated for long time' alarm SprChaAlm v1_dSPS stVal SPRCHRAL Spring charging time has crossed the set value SPRCHRAL Spring charging time has crossed the set value...
  • Page 214: Insulation Medium Supervision (Gas) Simg

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description AccAPwrPhB v2_dMV mag.f IACC_B Accumulated currents power (Iyt), phase B IACC_B Accumulated currents power (Iyt), phase B IACC_B Accumulated currents power (Iyt), phase B AccAPwrPhC v2_dMV...
  • Page 215 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850...
  • Page 216: Insulation Medium Supervision (Liquid) Siml

    Section 7 1MRK 511 281-UUS A Logical node data model 7.10.3 Insulation medium supervision (liquid) SIML 7.10.3.1 Insulation liquid monitoring function SSIML (71) LN type LN prefix LN class Function block name SSIML (revision 0) S SIML SSIML (71) Table 147: SSIML (71) Logical node data DO name DO type...
  • Page 217: Logical Nodes For Switchgear

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description b_dMV TEMP Temperature of the insulation medium LORs v1_dSPC Oper.ctlVal Command parameter for IEC61850 Oper.origin.orCat Command parameter for IEC61850 Oper.origin.orIdent Command parameter for IEC61850 Oper.ctlNum Command parameter for IEC61850 Oper.T...
  • Page 218 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINS stVal Behaviour parameter for 61850 Behaviour parameter for 61850 Behaviour parameter for 61850 BlkCls a_dSPC Oper.ctlVal Special block command value Oper.origin.orCat Special block command value Oper.origin.orIdent...
  • Page 219: Switch Xswi

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description c_dDPC POSITION Apparatus position indication POSITION Apparatus position indication subEna Substitute enable subVal Substituted double position value CBOpCap h_dINS stVal Breaker operating capability 1 = None, 2 = O, 3 = CO, 4 = OCO, 5 = COCO, 6+ = More Breaker operating capability 1 = None,...
  • Page 220 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.ctlNum Mode parameter for 61850 Oper.T Mode parameter for 61850 Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status value parameter for 61850 Mode status value parameter for 61850...
  • Page 221 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dSPS Indication that the function is in local mode (process level) Indication that the function is in local mode (process level) OpCnt b_dINS stVal...
  • Page 222: Logical Nodes For Power Transformers

    Section 7 1MRK 511 281-UUS A Logical node data model 7.12 Logical nodes for power transformers 7.12.1 Tap changer YLTC 7.12.1.1 Tap changer control and supervision, 6 binary inputs TCMYLTC (84) LN type LN prefix LN class Function block name TCMYLTC (revision 5) TCM YLTC TCMYLTC (84)
  • Page 223 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description TapChg b_dBSC TCPOS Integer value corresponding to actual tap position OpCnt b_dINS stVal CNT_VAL Number of operations on tap changer CNT_VAL Number of operations on tap changer CNT_VAL Number of operations on tap changer...
  • Page 224: Logical Nodes For Further Power System Equipment

    Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description InvPosChg v1_dSPS INVALPOS Last position change was an invalid change TapChgFlt v1_dSPS stVal TCERRAL Alarm for none or illegal tap position change TCERRAL Alarm for none or illegal tap position...
  • Page 225 Section 7 1MRK 511 281-UUS A Logical node data model DO name DO type DA name Signal Mon/C Description a_dINC Oper.Test Mode parameter for 61850 Oper.Check Mode parameter for 61850 stVal Mode status parameter for 61850 Mode status parameter for 61850 Mode status parameter for 61850 a_dINS stVal...
  • Page 227: Section 8 Goose Receive Blocks

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks Section 8 GOOSE receive blocks Interlock receive - INTLKRCV 8.1.1 Horizontal communication via GOOSE for interlocking GOOSEINTLKRCV LN type LN prefix LN class Function block name INTGREC instance 1 (revision 0) INT GREC GOOSEINTLKRCV Table 152:...
  • Page 228: Binary Receive - Binrcv

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks DO name DO type DA name Signal Mon/C Description TagApp12 a_dDPS stVal Internal parameter tag to handle 61850 mapping TagApp13 a_dDPS stVal Internal parameter tag to handle 61850 mapping TagApp14 a_dDPS stVal Internal parameter tag to handle 61850 mapping...
  • Page 229: Vctr Receive - Vctrrcv

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks DO name DO type DA name Signal Mon/C Description TagBinOut7 a_dSPS stVal Internal parameter tag to handle 61850 mapping TagBinOut8 a_dSPS stVal Internal parameter tag to handle 61850 mapping TagBinOut9 a_dSPS stVal Internal parameter tag to handle 61850 mapping...
  • Page 230: Double Point Receive (Dp) - Dprcv

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks DO name DO type DA name Signal Mon/C Description In_LodARe V11_dMV Real part of load current (horizontal communication) Real part of load current (horizontal communication) In_BusV V12_dMV mag.f Busbar voltage (horizontal communication) Busbar voltage (horizontal communication)
  • Page 231: Integer Receive - Intrcv

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks Table 155: GOOSEDPRCV Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description TagDPOut a_dDPS stVal Internal parameter tag to handle 61850 mapping Internal parameter tag to handle 61850 mapping Integer Receive - INTRCV 8.5.1...
  • Page 232: Single Point Receive (Sp) - Sprcv

    Section 8 1MRK 511 281-UUS A GOOSE receive blocks Table 157: GOOSEMVRCV Logical node data (instance 1) DO name DO type DA name Signal Mon/C Description TagMVOut a_dMV mag.f Internal parameter tag to handle 61850 mapping Internal parameter tag to handle 61850 mapping Single Point Receive (SP) - SPRCV 8.7.1...
  • Page 233: Section 9 Glossary

    Section 9 1MRK 511 281-UUS A Glossary Section 9 Glossary Alternating current Actual channel Application configuration tool within PCM600 A/D converter Analog-to-digital converter ADBS Amplitude deadband supervision Analog input ANSI American National Standards Institute Autoreclosing ASCT Auxiliary summation current transformer Adaptive signal detection ASDU Application service data unit...
  • Page 234 Section 9 1MRK 511 281-UUS A Glossary COMTRADE Standard Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC60255-24 Cause of transmission Central processing unit Carrier receive Cyclic redundancy check CROB Control relay output block Carrier send Current transformer Communication unit...
  • Page 235 Section 9 1MRK 511 281-UUS A Glossary Electromagnetic interference EnFP End fault protection Enhanced performance architecture Electrostatic discharge F-SMA Type of optical fibre connector Fault number Flow control bit; Frame count bit FOX 20 Modular 20 channel telecommunication system for speech, data and protection signals FOX 512/515 Access multiplexer...
  • Page 236 Section 9 1MRK 511 281-UUS A Glossary IEC 60870-5-103 Communication standard for protective equipment. A serial master/slave protocol for point-to-point communication IEC 61850 Substation automation communication standard IEC 61850–8–1 Communication protocol standard IEEE Institute of Electrical and Electronics Engineers IEEE 802.12 A network technology standard that provides 100 Mbits/s on twisted-pair or optical fiber cable IEEE P1386.1...
  • Page 237 Section 9 1MRK 511 281-UUS A Glossary IRIG-B: InterRange Instrumentation Group Time code format B, standard 200 International Telecommunications Union Local area network Liquid crystal display Local detection device Light-emitting diode LON network tool Miniature circuit breaker MVAL Value of measurement National Control Centre Number of grid faults Numerical module...
  • Page 238 Section 9 1MRK 511 281-UUS A Glossary PT ratio Potential transformer or voltage transformer ratio PUTT Permissive underreach transfer trip Relay characteristic angle RISC Reduced instruction set computer RMS value Root mean square value RS422 A balanced serial interface for the transmission of digital data in point-to-point connections RS485 Serial link according to EIA standard RS485...
  • Page 239 Section 9 1MRK 511 281-UUS A Glossary Trip coil Trip circuit supervision Transmission control protocol. The most common transport layer protocol used on Ethernet and the Internet. TCP/IP Transmission control protocol over Internet Protocol. The de facto standard Ethernet protocols incorporated into 4.2BSD Unix.
  • Page 240 Section 9 1MRK 511 281-UUS A Glossary Coordinated Universal Time is expressed using a 24-hour clock, and uses the Gregorian calendar. It is used for aeroplane and ship navigation, where it is also sometimes known by the military name, "Zulu time." "Zulu" in the phonetic alphabet stands for "Z", which stands for longitude zero.
  • Page 242 Any reproduction, Phone +46 (0) 21 32 50 00 disclosure to third parties or utilization of its contents – in whole or in part – is forbidden without prior written consent of ABB AB. www.abb.com/protection-control © Copyright 2013 ABB.