ABB Relion 615 series Installation Manual
Hide thumbs Also See for Relion 615 series:
Table of Contents

Advertisement

®
Relion
Protection and Control
615 series
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 series

  • Page 1 ® Relion Protection and Control 615 series Installation Manual...
  • Page 3 Document ID: 1MRS756375 Issued: 2012-05-11 Revision: K Product version: 4.0 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7 Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
  • Page 9: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Section 2 Environmental aspects.............9 Sustainable development..............9 Disposing of the IED................9 Section 3 Unpacking, inspecting and storing.........11 Removing transport packaging............11 Inspecting the product..............11 Identifying the product..............11...
  • Page 10 Table of contents Rack mounting the IED in a combiflex 19" equipment frame (Type RHGT 19" 4U variant C)............34 Mounting lens sensors for an arc protection system....36 Replacing a Strömberg SP_J40 series relay by a 615 series IED..................38 Replacing two Strömberg SP_J3 series relays by a 615 series IED..................39 Replacing a Strömberg SP_J3/J6 series relay in 19"...
  • Page 11 Table of contents Section 9 Glossary.................73 615 series Installation Manual...
  • Page 13: Section 1 Introduction

    Section 1 1MRS756375 K Introduction Section 1 Introduction This manual The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. Intended audience This manual addresses the personnel responsible for installing the product hardware.
  • Page 14: Document Revision History

    Content updated to correspond to the product series version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation. 615 series Installation Manual...
  • Page 15: Symbols And Conventions

    Section 1 1MRS756375 K Introduction Symbols and conventions 1.4.1 Symbols The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury. The caution icon indicates important information or warning related to the concept discussed in the text.
  • Page 16 Section 1 1MRS756375 K Introduction The function can be enabled and disabled with the Operation setting. • Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE.
  • Page 17: Section 2 Environmental Aspects

    Section 2 1MRS756375 K Environmental aspects Section 2 Environmental aspects Sustainable development Sustainability has been taken into account from the beginning of the product design including the pro-environmental manufacturing process, long life time, operation reliability and disposing of the IED. The choice of materials and the suppliers have been made according to the EU RoHS directive (2002/95/EC).
  • Page 18 Section 2 1MRS756375 K Environmental aspects electronic waste. These handlers can sort the material by using dedicated sorting processes and dispose of the product according to the local requirements. Table 2: Materials of the IED parts Parts Material Case Metallic plates, parts and screws Steel Plastic parts , LCP...
  • Page 19: Section 3 Unpacking, Inspecting And Storing

    Section 3 1MRS756375 K Unpacking, inspecting and storing Section 3 Unpacking, inspecting and storing Removing transport packaging IEDs require careful handling. Examine the delivered products to ensure that they have not been damaged during the transport. Remove the transport packing carefully without force. Attach the protective film (supplied with the IED) on the top side of the unit for the installation phase.
  • Page 20: Returning An Ied Damaged In Transit

    If damage has occurred during transport, appropriate actions must be taken against the latest carrier. Please inform the nearest ABB office or representative. Notify ABB immediately if there are any discrepancies in relation to the delivery documents. Storing If the IED is stored before installation, it must be done in the original transport packaging in a dry and dust free place.
  • Page 21: Section 4 Mounting

    Section 4 1MRS756375 K Mounting Section 4 Mounting Checking environmental conditions and mounting space The mechanical and electrical environmental conditions at the installation site must be within the limits described in the technical manual. • Avoid installation in dusty, damp places. Avoid places susceptible to rapid temperature variations, powerful vibrations and shocks, surge voltages of high amplitude and fast rise time, strong induced magnetic fields or similar extreme conditions.
  • Page 22: Installing The Plug-In Unit

    Section 4 1MRS756375 K Mounting A070577 V4 EN Figure 1: Detaching a plug-in unit from the case The IED features an automatic short-circuit mechanism in the CT connector. Therefore, detaching the plug-in unit will not open the secondary circuit of the CT which could cause dangerously high voltages.
  • Page 23 Section 4 1MRS756375 K Mounting Before fitting the plug-in unit into the case, check that the unit and the case have the same serial number. GUID-BCE48661-E92A-460E-8E72-4F0EA261FB9E V1 EN Figure 2: Serial number in the case 1 Rating label with serial number Forcing a non-suitable plug-in unit into the case can break both the plug-in unit and the case and may cause danger.
  • Page 24: Sealing The Plug-In Unit

    Section 4 1MRS756375 K Mounting A071115 V5 EN Figure 3: Installing a plug-in unit into the case 4.2.3 Sealing the plug-in unit The front panel of the IED has an integrated sealing screw. By default the screw is screwed all the way in and is not used when installing or detaching the plug-in unit. Open the sealing screw about nine turns.
  • Page 25: Securing The Handle

    Section 4 1MRS756375 K Mounting GUID-8158C704-BD99-42EB-A495-6BD015C240CD V1 EN Figure 4: Sealing screw 1 Sealing screw 2 Sealing wire and seal 4.2.4 Securing the handle The front panel of the IED has an integrated sealing screw. By default, the screw is screwed all the way in and not used when installing or detaching the plug-in unit.
  • Page 26: Mounting The Ied

    Section 4 1MRS756375 K Mounting GUID-10D2039E-4C58-4372-B0B2-EDFF0C2A451C V1 EN Figure 5: Sealing screw with spacer 1 Spacer 2 Sealing screw Mounting the IED 4.3.1 Required tools • T25 Torx screwdriver for mounting the case • T20 Torx screwdriver for connecting the protective earthing Only use adjustable torque screwdrivers.
  • Page 27: Flush Mounting The Ied

    Section 4 1MRS756375 K Mounting 4.3.2 Flush mounting the IED All the mounting elements are integrated in the IED. Requirements for installation: • Panel cut-out of 165.5 x 161.5 mm • Depth behind the panel 153 mm An IED equipped with optical connections requires a minimum depth of 180 mm.
  • Page 28 Section 4 1MRS756375 K Mounting A070581 V4 EN Figure 6: Flush mounting a case into a panel cut-out A 165.5 ±1 mm 1 M5 fixing screws B 161.5 ±1 mm Tighten the M5 (T25) screws. The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm.
  • Page 29 Section 4 1MRS756375 K Mounting A070582 V4 EN Figure 7: Flush mounted case, tightening the M5 fixing screws Install the plug-in unit into the case. 615 series Installation Manual...
  • Page 30: Semi-Flush Mounting The Ied

    Section 4 1MRS756375 K Mounting A070584 V4 EN Figure 8: Flush mounted case and plug-in unit 177 mm 177 mm C 164 mm D 201 mm 153 mm 48 mm G 160 mm 4.3.3 Semi-flush mounting the IED A mounting kit is needed for semi-flush mounting the IED. In addition to the detailed mounting instructions, the mounting kit includes: 615 series Installation Manual...
  • Page 31 Section 4 1MRS756375 K Mounting • Raising frame • Gasket • Screws Requirements for installation: • Panel cut-out of 165.5 x 161.5 mm with mounting holes • Depth behind the panel 103 mm • When IP 54 degree of protection (according to IEC 60529) is required for the front side, a gasket has to be used in the installation.
  • Page 32 Section 4 1MRS756375 K Mounting A070590 V4 EN Figure 10: Mounting the case Tighten the M5 screws. The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm. Install the plug-in unit into the case. 615 series Installation Manual...
  • Page 33: Semi-Flush Mounting The Ied Inclined

    Section 4 1MRS756375 K Mounting A070591 V4 EN Figure 11: Semi-flush mounted IED A 186 mm B 177 mm C 201 mm D 103 mm E 98 mm 160 mm Check the allowed minimum bending radius from the optical cable manufacturer.
  • Page 34 Section 4 1MRS756375 K Mounting • Panel cut-out of 167 x 203 mm with mounting holes • Depth behind the panel 107 mm • When IP 54 degree of protection (according to IEC 60529) is required for the front side, a gasket has to be used in the installation. Mount the angle frame into the panel cut-out with four M4 screws.
  • Page 35: Rack Mounting The Ied

    Section 4 1MRS756375 K Mounting A071314 V4 EN Figure 13: IED semi-flush mounted inclined 25 ° 1 M4 screws 221 mm 2 Gasket C 9 mm 4 Case D 107 mm 3 Angled frame 133 mm 5 Plug-in unit 230 mm G 190 mm 4.3.5 Rack mounting the IED...
  • Page 36 Section 4 1MRS756375 K Mounting A070580 V3 EN Figure 14: 19” rack mounting panels A 482.6 mm (19") B 177 mm (4U) Tighten the screws. 615 series Installation Manual...
  • Page 37: Wall Mounting The Ied

    Section 4 1MRS756375 K Mounting The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm. Install the plug-in unit into the case. A070579 V4 EN Figure 15: Rack mounted IED 4.3.6 Wall mounting the IED A mounting kit is needed for wall mounting the IED. In addition to the detailed mounting instructions, the wall mounting kit includes: •...
  • Page 38 Section 4 1MRS756375 K Mounting A070593 V4 EN Figure 16: Wall mounting the IED A 430 mm Tighten the screws. The allowed range for the fixing screws’ tightening torque is 0.7...1 Nm. 615 series Installation Manual...
  • Page 39 Section 4 1MRS756375 K Mounting A070592 V4 EN Figure 17: Wall mounted IED A 214 mm B 177 mm C 270 mm Minimum of 50 mm space is needed between two kits. When connecting the wires, a wall-mounted IED can be pulled out and turned 45° (or 90°) degrees downwards or upwards.
  • Page 40: Rack Mounting The Ied And Test Switch Rtxp To A 19" Equipment Frame

    Section 4 1MRS756375 K Mounting A070594 V4 EN Figure 18: Wall mounted IED in rotated position A 455 mm Minimum of 50 mm space is needed above and below the frame for rotating. 4.3.7 Rack mounting the IED and test switch RTXP to a 19” equipment frame A mounting kit is needed for rack mounting the IED in a 19"...
  • Page 41 Section 4 1MRS756375 K Mounting • Mounting panel • Metallic frame for mounting the RTXP 18 or 24 test switch to the panel An IED equipped with optical connections requires a minimum depth of 180 mm. The allowed minimum bending radius has to be checked from the optical cable manufacturer.
  • Page 42: Rack Mounting The Ied In A Combiflex 19" Equipment Frame (Type Rhgt 19" 4U Variant C)

    Section 4 1MRS756375 K Mounting A070588 V4 EN Figure 20: IED and the test switch RTXP 18 mounted into a 19" equipment panel 4.3.8 Rack mounting the IED in a combiflex 19" equipment frame (Type RHGT 19" 4U variant C) A mounting bracket is needed for rack mounting the IED into a combiflex 19"...
  • Page 43 Section 4 1MRS756375 K Mounting A070576 V4 EN Figure 21: Mounting the IED into a 19" combiflex equipment frame 1 RHGT 19" 4U equipment frame, variant C, with support frame 2 Tapping screw ST3.5x13 3 Mounting bracket Install the optional RTXP 18 or 24 test switch. 615 series Installation Manual...
  • Page 44: Mounting Lens Sensors For An Arc Protection System

    Section 4 1MRS756375 K Mounting A070575 V4 EN Figure 22: IED and the test switch 1 RHGT 19" 4U equipment frame, variant C, with support frame 2 Tapping screw ST3.5x13 3 Mounting bracket for mounting with test switch RTXP 18 4.3.9 Mounting lens sensors for an arc protection system Arc protection is used to detect arc situations in air insulated metal-clad switchgear.
  • Page 45 Section 4 1MRS756375 K Mounting A040183 V2 EN Figure 23: Dimensions of the lens sensor A 3.5 mm B 10 mm C ∅ 9.5 mm D 19 mm Fit the lens sensor into the hole and fasten it with a self-tapping M3 screw. Alternatively, the lens sensor can be fastened with a cable tie.
  • Page 46: Replacing A Strömberg Sp_J40 Series Relay By A 615

    Section 4 1MRS756375 K Mounting 4.3.10 Replacing a Strömberg SP_J40 series relay by a 615 series IED Drill new screw holes (∅4.5 mm) to the panel according to the dimensional drawing. GUID-C7CA77AA-74EA-40D2-B98E-84735BCADDA2 V1 EN Figure 25: Screw hole and existing panel cut-out dimensions for replacing a SP_J40 series IED A 442 mm B 183 mm...
  • Page 47: Replacing Two Strömberg Sp_J3 Series Relays By A 615

    Section 4 1MRS756375 K Mounting GUID-B5A98F9F-E10D-4F92-A1ED-73D9B7719916 V1 EN Figure 26: Installation plates for replacing SP_J40 relay 1 Installation plate 2 Torx head screw M5x10 Tighten the screws. Mount the new IED. For ordering numbers, see the ordering number table. 4.3.11 Replacing two Strömberg SP_J3 series relays by a 615 series IED Make a new panel cut-out to the existing mounting panel according to the...
  • Page 48 Section 4 1MRS756375 K Mounting GUID-7D44F5DE-6452-455A-8076-2A67FD463CC7 V1 EN Figure 27: New panel cut-out and screw hole dimensions for replacing two SP_J3 series relays A 155 mm 1 New panel cut-out line B 15 mm C 196 mm D Min. 165,5 mm E Min.
  • Page 49: Replacing A Strömberg Sp_J3/J6 Series Relay In 19" Rack By A 615 Series Ied

    Section 4 1MRS756375 K Mounting GUID-24CF4D5D-1EAE-487A-A1DE-557DF59658B0 V1 EN Figure 28: Installation plate for replacing two SP_J3 relays 1 Installation plate 2 Torx head screw M5x10 Tighten the screws. Mount the new IED. For ordering numbers, see the ordering number table. 4.3.12 Replacing a Strömberg SP_J3/J6 series relay in 19"...
  • Page 50 Section 4 1MRS756375 K Mounting GUID-F1B5DA9A-05ED-419F-A795-6FD6E2A4CF95 V1 EN Figure 29: Screw hole and existing panel cut-out dimensions for replacing a SP_J3/J6 series relay A 446 mm B 196 mm C 460 mm D 114,5 mm 615 series Installation Manual...
  • Page 51: Replacing A Strömberg Sp_J6 Series Relay By A 615 Series Ied

    Section 4 1MRS756375 K Mounting GUID-90BDC1BA-F671-4178-8136-8E8D9E56A7A3 V1 EN Figure 30: Installation plates for replacing SP_J3/J6 relay in 19" rack 1 Installation plate 2 Torx head screw M6x20 3 Hexagon nut M6 Tighten the screws. Mount the new IED with the mounting frame to the installation plate. For ordering numbers, see the ordering number table.
  • Page 52 Section 4 1MRS756375 K Mounting GUID-57FA3F1B-C6EB-43A4-80E8-5D13CD08D9FF V1 EN Figure 31: Screw hole and existing panel cut-out dimensions for a SP_J6 series relay A 186 ± 1 mm B 186 ± 1 mm C 196 mm D 196 mm Mount the installation plate to the existing panel cut-out with M5 thread forming screws.
  • Page 53: Replacing Three Bbc S_ Series Relays By A 615 Series Ied

    Section 4 1MRS756375 K Mounting GUID-2B059F45-1287-4D8D-92A6-E6583B0ADAEB V1 EN Figure 32: Installation plate for replacing SP_J6 relay 1 Installation plate 2 Torx head screw M5x10 Tighten the screws. Mount the new IED. For ordering numbers, see the ordering number table. 4.3.14 Replacing three BBC S_ series relays by a 615 series IED Make a new panel cut-out to the existing mounting panel according to the dimensional drawing.
  • Page 54 Section 4 1MRS756375 K Mounting GUID-A309A8C4-5AB1-4859-91D2-CD8C4556BA7F V1 EN Figure 33: Existing panel cut-out and screw hole dimensions for three BBC S_ series relays A 92 mm B 234 mm C 100 mm D 250 mm 615 series Installation Manual...
  • Page 55 Section 4 1MRS756375 K Mounting GUID-FEC7A3B8-7A65-4ACF-BDEB-DD8BB2BF5F57 V1 EN Figure 34: New panel cut-out for replacing BBC S_ series relays 1 New panel cut-out line Mount the installation plate to the panel cut-out with M5 screws, nuts and washers. Use the existing screw holes. 615 series Installation Manual...
  • Page 56 Section 4 1MRS756375 K Mounting GUID-71136C37-E662-426D-B378-9BF21ADFC51A V1 EN Figure 35: Installation plate for replacing three BBC S_ relays 1 Installation plate 2 Torx head screw M5x16 3 Hexagon nut M5 4 Spring washer Tighten the screws. Mount the new IED. For ordering numbers, see the ordering number table.
  • Page 57: Replacing A Spa 300 Series Relay By A 615 Series Ied

    Section 4 1MRS756375 K Mounting 4.3.15 Replacing a SPA 300 series relay by a 615 series IED Make a new panel cut-out to the existing mounting panel according to the dimensional drawing. GUID-F20D587E-5E99-4593-B9EE-A1B125A95524 V1 EN Figure 36: New panel cut-out and screw hole dimensions for replacing a SPA 300 series relay A Min.
  • Page 58: Replacing A Spa 300 Series Relay In 19" Rack By A 615 Series Ied

    Section 4 1MRS756375 K Mounting GUID-A8741360-1066-494D-9340-3DA0AF81E778 V1 EN Figure 37: Installation plate for replacing SPA 300 relay 1 Installation plate 2 Torx head screw M5x10 Tighten the screws. Mount the new IED. Use a raising frame if needed. For ordering numbers, see the ordering number table. 4.3.16 Replacing a SPA 300 series relay in 19"...
  • Page 59: Section 5 Connecting

    Section 5 1MRS756375 K Connecting Section 5 Connecting Required tools Only use a screwdriver and insert bits for Phillips (PH 1) cross-recessed head screws (M3.5) when handling CT/VT terminals (X120) of screw-compression type. A071178 V2 EN Figure 38: Screwdriver for CT/VT terminals of screw-compression type A MAX ∅5.5 mm B MAX ∅5 mm A071180 V2 EN...
  • Page 60: Connecting Ring-Lug Type Wires

    Section 5 1MRS756375 K Connecting See the application manual for product-specific connection diagrams. 5.2.1 Connecting ring-lug type wires Ring-lug type insulated terminal can be used for signal connector X120. The maximum outside diameter for the M4 ring-lug type terminals is 9 mm. Connecting protective earthing The earth lead must be at least 6.0 mm .
  • Page 61: Connecting Analog Signals

    Section 5 1MRS756375 K Connecting The earth lead should be as short as possible but notice that extra length is required for door mounting. Each IED must have its own earth lead connected to the earth circuit connector. Connect the earth lead to the earth bar. Use either stripped wire screwed between a washer cup and the protective earth screw or a ring-lug.
  • Page 62 Section 5 1MRS756375 K Connecting GUID-CC5FAADB-60C3-43EF-A172-7572FF85FC44 V1 EN Figure 41: Example of AIM0004 card variant (4 I + 3 U with 1/5 A Io channel) GUID-CAB8DAAA-8A15-4AF6-AFC7-CA232D253F3D V3 EN Figure 42: Example of AIM0005 card variant (7 I with 1/5 A Io channel) 615 series Installation Manual...
  • Page 63 Section 5 1MRS756375 K Connecting GUID-7FC759CB-AFC5-4029-972A-BFC8677763F9 V3 EN Figure 43: Example of AIM0006 card variant (5 U) GUID-7473CEBA-AA9C-4F58-8091-F9717AEE7F3A V1 EN Figure 44: Example of AIM0013 card variant (4 I + 3 U with 0.2/1 A Io channel) 615 series Installation Manual...
  • Page 64 Section 5 1MRS756375 K Connecting A071228 V4 EN Figure 45: Example of AIM0016 card variant (4 I with 1/5 A Io channel) A071232 V4 EN Figure 46: Example of AIM0017 card variant (4 I with 0.2/1 A Io channel) 615 series Installation Manual...
  • Page 65 Section 5 1MRS756375 K Connecting A071230 V4 EN Figure 47: Example of AIM0018 card variant (4 I + Uo with 1/5 A Io channel) A071234 V4 EN Figure 48: Example of AIM0019 card variant (4 I + Uo with 0.2/1 A Io channel) 615 series Installation Manual...
  • Page 66: Connecting Rtd And Ma Inputs

    Section 5 1MRS756375 K Connecting 5.4.2 Connecting RTD and mA inputs Connect the wires from the transducers to the correct device according to the connection diagram. Each terminal for RTDs and mA inputs is dimensioned for one 0.5...2.5 mm wire or for two 0.5...1.0 mm wires.
  • Page 67: Connecting Binary Signals

    Section 5 1MRS756375 K Connecting Connecting binary signals Connect the wires for the binary signals to the correct device according to the connection diagram. Each terminal for binary input and output signal is dimensioned for one 0.5...2.5 mm wire or for two 0.5...1.0 mm wires.
  • Page 68: Connecting Power Supply

    Section 5 1MRS756375 K Connecting GUID-ED2EA005-C136-4DB1-B71F-B828997A6EDB V1 EN Figure 51: Example of BIO0006 card variant (6 BI + 3 BO) Connecting power supply The IED's auxiliary voltage is connected to terminals X100-1 and X100-2. The positive lead is connected to terminal X100-1. The permitted auxiliary voltage range of the IED is marked on top of the IED's LHMI.
  • Page 69: Connecting Communication

    Section 5 1MRS756375 K Connecting A070770 V1 EN Figure 52: Connecting auxiliary voltage Connecting communication Before connecting communication, check that the HW module has the correct communication interfaces. The communication module is located on the left side of the IED when viewing the case from the rear. See the technical manual for product-specific communication interfaces.
  • Page 70 Section 5 1MRS756375 K Connecting Before connecting the auxiliary power, check that the terminal strip is wired and placed correctly. Remove the protective film from the top side of the unit. Check that there is no debris visible in the ventilation holes. GUID-97A2D4BA-29FC-4E2F-8C4D-81EE5E77CF79 V1 EN Figure 53: Removing the protective film...
  • Page 71: Section 6 Removing, Repairing And Exchanging

    IED-specific options can be found from Retrofit Solutions Database on the Internet www.abb.com by following the links within ABB Service Guide or via ABB Product Guide from the product specific Service & Support sheet. Checking IED information The IED information includes detailed information about the device, such as version and serial number.
  • Page 72: Removing The Ied

    A070582 V4 EN Detach the case from the panel cut-out. Sending the IED for repair In case of product problems, contact the nearest ABB office or representative for consultation and instructions. Exchanging the IED To exchange the IED with another identical unit, remove the IED and install the new one.
  • Page 73: Section 7 Technical Data

    Section 7 1MRS756375 K Technical data Section 7 Technical data Case and HMI display variants 7.1.1 Front side of the IED IECA070904 V3 EN Figure 54: Small display 615 series Installation Manual...
  • Page 74 Section 7 1MRS756375 K Technical data IECA070901 V3 EN Figure 55: Large display Table 3: Small display Rows in the view Characters per row Character size Small, mono-spaced (6x12 pixels) Large, variable width (13x14 pixels) 8 or more 1) Depending on the selected language Table 4: Large display Rows in the view...
  • Page 75: Rear Side Of The Ied

    Section 7 1MRS756375 K Technical data 7.1.2 Rear side of the IED A070596 V1 EN Figure 56: Rear view of an 615 series IED with communication module 615 series Installation Manual...
  • Page 76: Dimensions

    Section 7 1MRS756375 K Technical data Dimensions GUID-6BA24DB4-935E-4B81-AEE6-FD8B7FC4140F V2 EN Figure 57: 615 series main dimensions A 177 mm B 177 mm (4U) C 164 mm D 153 mm E 48 mm 160 mm Table 5: Dimensions Description Value Width frame 177 mm case...
  • Page 77: Enclosure Class

    Section 7 1MRS756375 K Technical data Description Value Depth 201 mm (153 + 48 mm) Weight complete IED 4.1 kg plug-in unit only 2.1 kg Enclosure class Table 6: Degree of protection of flush-mounted IED Description Value Front side IP 54 Rear side, connection terminals IP 20 615 series...
  • Page 79: Section 8 Accessories And Ordering Data

    Section 8 1MRS756375 K Accessories and ordering data Section 8 Accessories and ordering data Table 7: Cables Item Order number Cable for optical sensors for arc protection 1.5 m 1MRS120534-1.5 Cable for optical sensors for arc protection 3.0 m 1MRS120534-3.0 Cable for optical sensors for arc protection 5.0 m 1MRS120534-5.0 Table 8:...
  • Page 81: Section 9 Glossary

    Section 9 1MRS756375 K Glossary Section 9 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Current transformer Electromagnetic compatibility Human-machine interface International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600...
  • Page 84 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...