ABB REV615 Product Manual

ABB REV615 Product Manual

Capacitor bank protection and control
Hide thumbs Also See for REV615:
Table of Contents

Advertisement

RELION® 615 SERIES
Capacitor Bank Protection and
REV615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB REV615

  • Page 1 — RELION® 615 SERIES Capacitor Bank Protection and Control REV615 Product Guide...
  • Page 2: Table Of Contents

    32. Document revision history........... 57 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    Issued: 2018-12-20 Revision: D 1. Description bus according to IEC 61850-9-2 LE, IEC 60870-5-103, REV615 is a dedicated capacitor bank relay designed for the ® Modbus and DNP3. Profibus DPV1 communication protocol is protection, control, measurement and supervision of capacitor supported by using the protocol converter SPA-ZC 302.
  • Page 4 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 REV615 CAPACITOR BANK PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip...
  • Page 5 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 REV615 CAPACITOR BANK PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Disturbance and fault recorders 2× 3× - Event log and recorded data Master Trip...
  • Page 6 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 2. Supported functions Function IEC 61850 Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC Three-phase non-directional overcurrent protection, high stage PHHPTOC Three-phase non-directional overcurrent protection, instantaneous stage...
  • Page 7: Protection Functions

    4. Application protection for capacitors including compensation for natural REV615 is intended for the protection of capacitor banks used unbalance and a current-based switching resonance for reactive power compensation in utility substations and protection.
  • Page 8 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Standard configuration A is pre-configured for H-bridge The second and third stage of the residual voltage protection in connected capacitor banks. Three-phase current unbalance the standard configuration B can be used as voltage-based protection is used for unbalance.
  • Page 9 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 U12 0. 0 kV REV615 P 0.00 kW Q 0.00 kVAr IL2 0 A Clear Std. conf. ANSI 27/59/59G 3U</3U>/Uo> 3Ith>T 50L/50NL 50P/51P 3I>>> 3I> 3I< 51NC-2 3dI>C 51P/51N 3I>/Io>...
  • Page 10: Supported Abb Solutions

    615 series relays without the optional power systems. To facilitate the system engineering, ABB's single-line diagram feature are used. The Web HMI of relays are supplied with connectivity packages. The...
  • Page 11: Control

    GOOSE communication GOOSE communication GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V4 EN Figure 7. ABB power system example using Relion relays, COM600S and MicroSCADA Pro/System 800xA 6. Control outputs which have originally been configured for other REV615 integrates functionality for the control of a circuit purposes, when applicable, or an external input or output breaker via the front panel HMI or by means of remote controls.
  • Page 12: Measurements

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 7. Measurements • Voltage variation The relay continuously measures the phase currents, the single • Voltage unbalance or three-phase unbalance currents (with the natural unbalance • Current harmonics current compensated), the symmetrical components of the •...
  • Page 13: Condition Monitoring

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 voltage and angle values and a time stamp. The fault recording measurement values at the moment when any protection can be triggered by the start or the trip signal of a protection function starts.
  • Page 14: Self-Supervision

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 14. Self-supervision based authentication system with administrator-programmable The relay’s built-in self-supervision system continuously individual passwords for the viewer, operator, engineer and monitors the state of the relay hardware and the operation of administrator levels.
  • Page 15: Station Communication

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 4. Input/output overview Std. conf. Order code digit Analog channels Binary channels 4 PO + 6 SO 4 PO + 9 SO 4 PO + 2 SO...
  • Page 16 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 application for sampled values shares the voltages to other 615 communication. The network redundancy is based on two series relays, having voltage based functions and 9-2 support. complementary protocols defined in the IEC 62439-3 standard: 615 relays with process bus based applications use IEEE 1588 PRP and HSR protocols.
  • Page 17 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 COM600 Devices not supporting HSR SCADA Ethernet switch Redundancy Redundancy Redundancy IEC 61850 HSR REF620 RET620 REM620 REF615 REF615 GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN Figure 10. High availability seamless redundancy (HSR) solution The choice between the HSR and PRP redundancy protocols switch-over.
  • Page 18 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN Figure 11. Self-healing Ethernet ring solution All communication connectors, except for the front port records are supported.
  • Page 19 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 The relay supports the following high accuracy time • Layer 2 mapping synchronization method with a time-stamping resolution of 4 µs • Peer to peer delay calculation required especially in process bus applications.
  • Page 20: Technical Data

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 20. Technical data Table 6. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm (153 + 48 mm)
  • Page 21 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 9. Binary inputs Description Value Operating range ±20% of the rated voltage Rated voltage 24...250 V DC Current drain 1.6...1.9 mA Power consumption 31.0...570.0 mW Threshold voltage 16...176 V DC...
  • Page 22 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 12. Signal outputs and IRF output Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s 15 A Breaking capacity when the control-circuit time constant L/R<40 ms, at...
  • Page 23 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 15. High-speed output HSO with BIO0007 Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R <40 ms, at...
  • Page 24 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 20. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance test IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
  • Page 25 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 20. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC 61000-4-16 IEC 60255-26, class A • Common mode 300 V rms •...
  • Page 26 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 23. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
  • Page 27 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Protection functions Table 27. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 × I PHHPTOC ±1.5% of set value or ±0.002 ×...
  • Page 28 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 29. Non-directional earth-fault protection (EFxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz EFLPTOC ±1.5% of the set value or ±0.002 × I EFHPTOC ±1.5% of set value or ±0.002 ×...
  • Page 29 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 31. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz DEFLPDEF Current: ±1.5% of the set value or ±0.002 × I Voltage ±1.5% of the set value or ±0.002 ×...
  • Page 30 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 32. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start value DEFLPDEF 0.010...5.000 × I 0.005 DEFHPDEF 0.10...40.00 × I 0.01 Directional mode DEFLPDEF and DEFHPDEF...
  • Page 31 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 35. Negative-sequence overcurrent protection (NSPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±1.5% of the set value or ±0.002 × I...
  • Page 32 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 38. Residual overvoltage protection (ROVPTOV) main settings Parameter Function Value (Range) Step Start value ROVPTOV 0.010...1.000 × U 0.001 Operate delay time ROVPTOV 40...300000 ms Table 39. Three-phase undervoltage protection (PHPTUV)
  • Page 33 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 41. Three-phase overvoltage protection (PHPTOV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: f ±2 Hz ±1.5% of the set value or ±0.002 × U...
  • Page 34 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 44. Positive-sequence undervoltage protection (PSPTUV) main settings Parameter Function Value (Range) Step Start value PSPTUV 0.010...1.200 × U 0.001 Operate delay time PSPTUV 40...120000 ms Voltage block value PSPTUV 0.01...1.00 ×...
  • Page 35 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 48. Three-phase thermal overload protection, two time constants (T2PTTR) main settings Parameter Function Value (Range) Step Temperature rise T2PTTR 0.0...200.0°C Max temperature T2PTTR 0.0...200.0°C Operate temperature T2PTTR 80.0...120.0%...
  • Page 36 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 51. Arc protection (ARCSARC) Characteristic Value Operation accuracy ±3% of the set value or ±0.01 × I Operate time Minimum Typical Maximum Operation mode = "Light 9 ms...
  • Page 37 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 55. Three-phase overload protection for shunt capacitor banks (COLPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz, and no harmonics 5% of the set value or 0.002 ×...
  • Page 38 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 58. Current unbalance protection for shunt capacitor banks (CUBPTOC) main settings Parameter Function Value (Range) Step Alarm mode CUBPTOC 1 = Normal 2 = Element counter Start value CUBPTOC 0.01...1.00 ×...
  • Page 39 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 61. Shunt capacitor bank switching resonance protection, current based (SRCPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: fn ±2 Hz Operate value accuracy: ±3% of the set value or ±0.002 ×...
  • Page 40 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 63. Operation characteristics Parameter Value (Range) Operating curve type 1 = ANSI Ext. inv. 2 = ANSI Very. inv. 3 = ANSI Norm. inv. 4 = ANSI Mod inv.
  • Page 41 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Power quality functions Table 64. Voltage variation (PHQVVR) Characteristic Value Operation accuracy ±1.5% of the set value or ±0.2% of reference voltage Reset ratio Typically 0.96 (Swell), 1.04 (Dip, Interruption) Table 65.
  • Page 42 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Condition and supervision functions Table 66. Circuit-breaker condition monitoring (SSCBR) Characteristic Value Current measuring accuracy ±1.5% or ±0.002 × I (at currents in the range of 0.1…10 × I ±5.0%...
  • Page 43 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Measurement functions Table 71. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±0.5% or ±0.002 × I (at currents in the range of 0.01...4.00 ×...
  • Page 44 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 76. Sequence voltage measurement (VSMSQI) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz At voltages in range 0.01…1.15 × U ±1.0% or ±0.002 ×...
  • Page 45 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Other functions Table 80. Pulse timer (PTGAPC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 81. Time delay off (8 pcs) (TOFPAGC)
  • Page 46: Local Hmi

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 21. Local HMI default single line diagram. The SLD view can also be accessed The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD a small one.
  • Page 47: Mounting Methods

    (PST), a Next-Generation Order Number circuiting the CT secondary circuits when a relay unit is Tool, supports order code creation for ABB Distribution withdrawn from its case. The relay case is further provided with Automation IEC products with emphasis on, but not exclusively a mechanical coding system preventing the current measuring for, the Relion product family.
  • Page 48: Accessories And Ordering Data

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 25. Accessories and ordering data Table 85. Cables Item Order number Optical sensor for arc protection, cable length 1.5 m 1MRS120534-1.5 Optical sensor for arc protection, cable length 3.0 m 1MRS120534-3 Optical sensor for arc protection, cable length 5.0 m...
  • Page 49: Tools

    Web browser Table 87. Tools Description Version PCM600 2.6 (Rollup 20150626) or later Web browser IE 8.0, IE 9.0, IE 10.0 or IE 11.0 REV615 Connectivity Package 5.1 or later...
  • Page 50: Cyber Security

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 88. Supported functions Function Web HMI PCM600 Relay parameter setting ● ● Saving of relay parameter settings in the relay ● ● Signal monitoring ● ● Disturbance recorder handling ●...
  • Page 51: Terminal Diagrams

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 28. Terminal diagrams REV615 X120 X100 1/5A IL1unb 1/5A IL2unb 1/5A IL3unb 1/5A 1/5A 1/5A 1/5A X110 BI 1 TCS1 BI 2 BI 3 TCS2 BI 4 X110...
  • Page 52 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 REV615 X100 X130 BI 1 BI 2 BI 3 BI 4 60 - 210V 60 - 210V 60 - 210V 60 - 210V 60 - 210V X120 1/5A...
  • Page 53: Certificates

    Relion 615 series. Certificate number: 7410570I-OPE/INC products and services. 15-1136. The latest relevant information on the REV615 protection and DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1 control relay is found on the product page. Scroll down the ®...
  • Page 54: Functions, Codes And Symbols

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 31. Functions, codes and symbols Table 89. Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low PHLPTOC1 3I> (1) 51P-1 (1)
  • Page 55 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 89. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Multipurpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3)
  • Page 56 Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 89. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Earthing switch indication ESSXSWI1 I <-> O ES (1) I <-> O ES (1) ESSXSWI2 I <->...
  • Page 57: Document Revision History

    Capacitor Bank Protection and Control 1MRS757952 D REV615 Product version: 5.0 FP1 Table 89. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Time delay off (8 pcs) TOFGAPC1 TOF (1) TOF (1) TOFGAPC2 TOF (2) TOF (2)
  • Page 60 ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 ABB Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 2604386 +91 265 2638922 www.abb.com/mediumvoltage www.abb.com/relion www.abb.com/substationautomation © Copyright 2018 ABB. All rights reserved.

This manual is also suitable for:

Relion 615 series

Table of Contents