Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Section 1 1MRS756879 D Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
Content updated to correspond to the product version D/2013-02-21 4.0 FP1 Content updated to correspond to the product series version Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
Section 1 1MRS756879 D Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 1 1MRS756879 D Introduction 1.4.3 Functions, codes and symbols Table 1: RED615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage Three-phase non-directional overcurrent PHHPTOC1 3I>> (1) 51P-2 (1) protection, high stage PHHPTOC2...
Page 15
Section 1 1MRS756879 D Introduction Function IEC 61850 IEC 60617 IEC-ANSI Master trip TRPPTRC1 Master Trip (1) 94/86 (1) TRPPTRC2 Master Trip (2) 94/86 (2) Control Circuit-breaker control CBXCBR1 I <-> O CB I <-> O CB Disconnector control I <-> O DCC DCXSWI1 I <->...
Section 2 1MRS756879 D DNP3 data mappings Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in the IED. The data points are unmapped as a default on the DNP3 level. The point lists describe a superset of all DNP3 data available through the standard configuration/s including the optional functionalities.
Section 2 1MRS756879 D DNP3 data mappings Function block DE01 DE02 DE03 RESCMMXU1 ● ● RESVMMXU1 ● ● = available in the device variant, o = optionally available in the device variant Binary inputs Table 3: Explanations of the binary input table columns Column name Description IEC 61850...
Section 2 1MRS756879 D DNP3 data mappings 2.3.4.2 LD0.RESCMMXU1 Residual current limit supervision Table 15: LD0.RESCMMXU1 Residual current limit supervision IEC 61850 name SA name Description Values LD0.RESCMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning 2.3.4.3 LD0.RESVMMXU1 Residual voltage limit supervision Table 16: LD0.RESVMMXU1 Residual voltage limit supervision IEC 61850 name...
Section 2 1MRS756879 D DNP3 data mappings 2.3.6.3 DR.RDRE1 Disturbance recorder Table 50: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Values DR.RDRE1 .RcdMade.stVal DR recording made 1=Made 2.3.6.4 LD0.PCSRTPC1 Protection communication supervision Table 51: LD0.PCSRTPC1 Protection communication supervision IEC 61850 name SA name Description...
Section 2 1MRS756879 D DNP3 data mappings IEC 61850 name SA name Description Values .Q6.stVal Input 6 signal 0/1=Off/On .Q7.stVal Input 7 signal 0/1=Off/On .Q8.stVal Input 8 signal 0/1=Off/On 2.3.7.3 LD0.SPCGGIO2 Multipurpose binary outputs - status (2) Table 54: LD0.SPCGGIO2 Multipurpose binary outputs - status (2) IEC 61850 name SA name Description...
Section 2 1MRS756879 D DNP3 data mappings IEC 61850 name SA name Description Values .SPCSO1.stVal X130-Output 1 1/0=ON/OFF .SPCSO2.stVal X130-Output 2 1/0=ON/OFF .SPCSO3.stVal X130-Output 3 1/0=ON/OFF Binary outputs Table 59: Explanations of the binary output table columns Column name Description IEC 61850 Original IED data object identification.
Section 2 1MRS756879 D DNP3 data mappings 2.4.2 Switchgear functions 2.4.2.1 CTRL.CBCSWI1 Circuit breaker control Table 62: CTRL.CBCSWI1 Circuit breaker control IEC 61850 name SA name Description Type CTRL.CBCSWI1 .Pos.Oper.ctlVal Circuit breaker control On/Off 2.4.2.2 CTRL.DCCSWI1 Controllable disconnector (1) control Table 63: CTRL.DCCSWI1 Controllable disconnector (1) control IEC 61850 name...
Section 2 1MRS756879 D DNP3 data mappings IEC 61850 name SA name Description Type .SPCS12.ctlVal Output 12 control On/Off .SPCS13.ctlVal Output 13 control On/Off .SPCS14.ctlVal Output 14 control On/Off .SPCS15.ctlVal Output 15 control On/Off .SPCS16.ctlVal Output 16 control On/Off 2.4.5.2 LD0.SPCGGIO2 Multipurpose binary outputs (2) The binary outputs may be configured either as pulse- or persistent-type outputs.
Section 2 1MRS756879 D DNP3 data mappings 2.5.1 System functions 2.5.1.1 CTRL.LLN0 Local remote station off Table 74: CTRL.LLN0 Local remote station off IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.LLN0 Off=0; Loc=1; Rem=2; .LocRem.stVal Station=3 0…3 0,3,0,3 2.5.1.2 LD0.LPHD1 System values Table 75:...
Section 2 1MRS756879 D DNP3 data mappings IEC 61850 name SA name Description Values Arg 1,2,3,4 0/1/3=Off/Ok/ .ISCSO5.stVal LED 5 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO6.stVal LED 6 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO7.stVal LED 7 state Alarm 0,3,0,3 0/1/3=Off/Ok/ .ISCSO8.stVal LED 8 state Alarm 0,3,0,3 0/1/3=Off/Ok/...
Section 2 1MRS756879 D DNP3 data mappings 2.5.3.4 LD0.RESVMMXU1 Residual voltage (1) Table 90: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESVMMXU1 0.00..4.00 .PhV.res.instCVal.mag U0_INST Residual voltage [xUn] 0,4,0,400 2.5.3.5 LD0.HAEFMHAI1 Current harmonics Table 91: LD0.HAEFMHAI1 Current harmonics IEC 61850 name SA name...
Section 2 1MRS756879 D DNP3 data mappings 2.5.5.2 DR.RDRE1 Disturbance recorder values Table 94: DR.RDRE1 Disturbance recorder values IEC 61850 name SA name Description Values Arg 1,2,3,4 DR.RDRE1 .FltNum.stVal Number of recordings 0…65535 0,65535,0,65535 .MemUsed.stVal Rec. memory used 0…100 [%] 0,100,0,100 RED615 Point List Manual...
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 95: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: RED615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 46
Section 3 1MRS756879 D DNP3 protocol implementation DNP3 device profile document ○ Sometimes ● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages" Timeouts while waiting for: Data link ○ None ○ Fixed at ____ ○...
Section 3 1MRS756879 D DNP3 protocol implementation DNP3 device profile document ○ Configurable ○ When device restarts ○ Only certain objects ○ When status flags change ○ Sometimes (attach explanation) ○ ENABLE/DISABLE UNSOLICITED No other options are permitted. function codes supported Default counter object/variation: Counters roll over at: ●...
Page 48
Section 3 1MRS756879 D DNP3 protocol implementation Table 96: Implementation table OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Object Variation Function codes Qualifier codes number number Description Function codes (dec) Qualifier codes (hex) (dec) (hex) Binary 1 (read) 00, 01 (start-stop) input –...
Page 49
Section 3 1MRS756879 D DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) 16-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 (default) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) 32-bit...
Page 50
Section 3 1MRS756879 D DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Time delay 129 (response) 07 (limited qty) fine (qty = 1) Not defined Class 0 1 (read) 06 (no range, or all) data Class 1 1 (read) 06 (no range, or all)
Section 4 1MRS756879 D Glossary Section 4 Glossary Application function block library CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day. DNP3 A distributed network protocol originally developed by Westronic.