ABB RELION 615 Series Protocol Manual

ABB RELION 615 Series Protocol Manual

Iec 60870-5-103 communication protocol
Hide thumbs Also See for RELION 615 Series:
Table of Contents

Advertisement

Quick Links

RELION® PROTECTION AND CONTROL
615 series
IEC 60870-5-103 Communication
Protocol Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION 615 Series

  • Page 1 — RELION® PROTECTION AND CONTROL 615 series IEC 60870-5-103 Communication Protocol Manual...
  • Page 3 Document ID: 1MRS759001 Issued: 2019-04-30 Revision: A Product version: 5.0 FP1 © Copyright 2019 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by the third party testing laboratory Intertek in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............3 This manual..................3 Intended audience................3 Product documentation...............4 Product documentation set............4 Document revision history............. 4 Related documentation..............5 Symbols and conventions..............5 Symbols..................5 Document conventions..............5 Section 2 IEC 60870-5-103 overview..........7 IEC 60870-5-103 standard..............7 Documentation...................
  • Page 8 Table of contents Scaling of Class 2 measurands ..........20 Unsupported analog values............20 Measurand events and registration objects......20 Energy counters................21 Operation principle..............22 Interpretation of the counter values........23 Accessing of non-protocol-mapped data........23 Other IEC 60870-5-103 data............24 Changing of parameter setting group.......... 24 Device identification..............25 Device function type...............
  • Page 9: Section 1 Introduction

    Section 1 1MRS759001 A Introduction Section 1 Introduction This manual The communication protocol manual describes a communication protocol supported by the protection relay. The manual concentrates on vendor-specific implementations. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering the communication setup in a substation from a protection relay's perspective.
  • Page 10: Product Documentation

    Product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version History A/2019-04-30 5.0 FP1 First release Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 615 series Communication Protocol Manual...
  • Page 11: Related Documentation

    1MRS759001 A Introduction 1.3.3 Related documentation Product-specific point list manuals and other product series- and product-specific manuals can be downloaded from the ABB Web site http://www.abb.com/substationautomation. Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text.
  • Page 12 Section 1 1MRS759001 A Introduction The corresponding parameter values are "On" and "Off". • Input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. • This document assumes that the parameter setting visibility is "Advanced". 615 series Communication Protocol Manual...
  • Page 13: Section 2 Iec 60870-5-103 Overview

    Section 2 1MRS759001 A IEC 60870-5-103 overview Section 2 IEC 60870-5-103 overview IEC 60870-5-103 standard IEC 60870-5-103 is defined as a companion standard for the informative element of protection equipment. While the official IEC 60870-5-103 standard dates back to 1997, the protocol has its roots in the VDEW6 communication protocol from the late 1980’s.
  • Page 14: Documentation

    Section 2 1MRS759001 A IEC 60870-5-103 overview single-function protection IED. The 615 series IEDs in turn are multifunctional protection and control IEDs whose internal data model is based on the IEC 61850 standard. Interoperability list The standard requires the IEC 60870-5-103 device to provide an interoperability list, which actually is more an interchangeability list.
  • Page 15: Section 3 Vendor-Specific Implementation

    Section 3 1MRS759001 A Vendor-specific implementation Section 3 Vendor-specific implementation Product series implementation IEC 60870-5-103 is specified for single function protective equipment with a limited set of process data. Some extensions are necessary for supporting the IEDs. • Multiple protection functionality •...
  • Page 16: Communication Link Setup

    Section 3 1MRS759001 A Vendor-specific implementation Table 3: Serial data characteristics Parameter Value Com speed 9600 or 19200 bauds Data bits Parity Even Start bits Stop bits Depending on the IED model and variant, the serial communication cards can host one or several serial channels.
  • Page 17: Diagnostic Counters

    Section 3 1MRS759001 A Vendor-specific implementation The COM port connection type, optical ST or EIA-485 connection, star or loop topology, idle state (light on or light off) and the bias and bus termination are selected with the COM port jumpers. Depending on the communication card, the optical connection may be available only for one COM port (1 or 2).
  • Page 18: Iec 60870-5-103 Process Data

    Section 3 1MRS759001 A Vendor-specific implementation Table 4: Protocol diagnostic counters (I3C01 and I3C02) Attribute Values (range) Default Description Status False = Communication inactive False Status (read) True = Communication active Reset counters False/True False True (reset) Received frames -1...2147483646 Received frames Checksum errors -1...2147483646...
  • Page 19: Asdu 2 Type Fault Number And Relative Time Data

    Section 3 1MRS759001 A Vendor-specific implementation 3.3.2.1 ASDU 2 type fault number and relative time data In addition to the absolute event time stamp, the ASDU 2 type requires that the message also contains a fault number and relative time data. However, these are not available in the IEC 61850 data model.
  • Page 20: Class 1 Event Overflow

    Section 3 1MRS759001 A Vendor-specific implementation The difference between a readable/writable object and a write-only object is not visible in the Communication Management tool of PCM600. An object is of write-only type if it is located on an IEC 61850 Oper.ctlVal data attribute. In this case, the GI enabling and other possible event configuration settings are meaningless.
  • Page 21: Class 1 Data Message Priorities

    Section 3 1MRS759001 A Vendor-specific implementation 3.3.2.5 Class 1 data message priorities User command responses (highest priority) Class 1 change events Disturbance file transfer messages General interrogation data responses (lowest priority) Disturbance file transfer increases the overall response time for Class 1 change events on the IEC 60870-5-103 interface.
  • Page 22: Analog Events

    Section 3 1MRS759001 A Vendor-specific implementation coding of double-pole objects. The possible values are “00” for None, “01” for OK and “11” for Alarm. In case of a two-position “OK-Alarm” LED, the LED area 2 data can be configured to show normal Off/On DPI-data using the double-point extended value to single- point value conversion.
  • Page 23: Value Interpretation

    Section 3 1MRS759001 A Vendor-specific implementation By default, most of these objects are not in use. The predefined private function types and information numbers for these objects can be edited freely. 3.3.3.2 Value interpretation According to the IEC 60870-5-103 standard, the TypeID 4 value coding format is 32- bit floating point.
  • Page 24: Control Operation Rejections

    Section 3 1MRS759001 A Vendor-specific implementation The relay cannot distinguish if the IEC 60870-5-103 client is of the Station or Remote (NCC) type. However, it is possible to locally reject the control operations on the IEC 60870-5-103 client side based on this indication and information about the client type (NCC or Station).
  • Page 25: Other Class 2 Measurand Frames

    Section 3 1MRS759001 A Vendor-specific implementation relates to current and voltage values only. The allowed scale factors, actually meaning |max values| of per unit coded measurands, are 1.2 or 2.4. The IEDs support all five interchangeable Class 2 measurand frames defined by the standard. Table 6: Interchangeable Class 2 measurand frames Frame...
  • Page 26: Selection Of Class 2 Frame

    Section 3 1MRS759001 A Vendor-specific implementation See the list of available measurands from the product-specific point list manuals. 3.3.5.3 Selection of Class 2 frame The Class 2 frame is selected with parameter Frame1InUse n. The user can select between the user-defined frame 0, standard frames 1 to 5, or IED-dependent frames 6 and 7.
  • Page 27: Energy Counters

    Section 3 1MRS759001 A Vendor-specific implementation Fault records The fault record needs to be separately configured for the desired registration actions. For example, registrations can be defined to be made only at operate (trip) situation, or also at any start on/off situation. The fault record function component contains all registration object values that could have potentially been used by the relay type in question.
  • Page 28: Operation Principle

    Section 3 1MRS759001 A Vendor-specific implementation Table 9: Counter value outlook in detail Octet Description Bits 0...7 = Counter bits 0…7 Bits 0…7 = Counter bits 8…15 Bits 0…7 = Counter bits 16..23 Bits 0…3 = Counter bits 24...27, Bit 4= sign, Bits 5...7 = Not used In practice only the energy values from the internal PEMMTR function are pre- mapped into ASDU 205 values.
  • Page 29: Interpretation Of The Counter Values

    Section 3 1MRS759001 A Vendor-specific implementation in parallel can be connected to a binary output and wired to other units, a broadcast freeze can be achieved. 3.3.6.2 Interpretation of the counter values The ASDU 205 counters are derived from the corresponding IEC 61850 counter objects.
  • Page 30: Other Iec 60870-5-103 Data

    Section 3 1MRS759001 A Vendor-specific implementation Example 2 The legacy protocol default mappings are a selection of the most important signals produced by the IEC 61850-based protection relay applications. The manufacturer’s selection of important signals may not always serve every customer. Any non-protocol-mapped internal signal can be freely connected to a general- purpose input object via the Application Configuration tool.
  • Page 31: Device Identification

    Section 3 1MRS759001 A Vendor-specific implementation 3.4.2 Device identification 3.4.2.1 Device function type The IEC 60870-5-103 standard requires that an IED is identified as a certain Device type. The standard has only the following single functional device types: • 128 distance protection •...
  • Page 32: Time Synchronization

    Section 3 1MRS759001 A Vendor-specific implementation 3.4.3 Time synchronization Time synchronization over IEC 60870-5-103 is supported. This requires that the IED’s global Time Sychronization Source parameter (in Configuration/Time/ Synchronization/Synch source) is set to "IEC 60870-5-103" mode. If some other time synchronization source is configured for the IED, the IEC 60870-5-103 time synchronization messages are rejected.
  • Page 33: Disturbance Recorder Channel Identification

    Section 3 1MRS759001 A Vendor-specific implementation disturbance recorder file does not correspond to any particular fault detected by the IED. The IEC 60870-5-103 directory information octet SOF bits TP, TEST and OTEV are not supported by the IED’s native disturbance recorder file system. These bits are therefore always set to 0.
  • Page 34: Disturbance Recorder Tags Identification

    Section 3 1MRS759001 A Vendor-specific implementation Table 11: Disturbance channel identification ACC Number Signal Phase current IL1-A Phase current IL2-A Phase current IL3-A Neutral current Io-A Phase voltage U1-A or phase-to-phase voltage U12-A Phase voltage U2-A or phase-to-phase voltage U23-A Phase voltage U3-A or phase-to-phase voltage U31-A Neutral voltage Uo-A Private channel numbers...
  • Page 35: Disturbance Recorder Transfer

    Section 3 1MRS759001 A Vendor-specific implementation This rule is followed by the IED if the indication signal in question is solely connected to the disturbance recorder digital channel. If the signal, for example, is OR-ed together with other internal digital signals or if the signal is not present in the normal IEC 60870-5-103 Class 1 data, then the tag identification is always: Function type = 5 Information number = disturbance recorder digital channel number...
  • Page 36: Gi Optimization

    Section 3 1MRS759001 A Vendor-specific implementation The IED includes some possibilities to fasten up and optimize the IEC 60870-5-103 communication. However, it is necessary to verify that these features are accepted by the network and the IEC 60870-5-103 master used. •...
  • Page 37: Troubleshooting

    Section 3 1MRS759001 A Vendor-specific implementation Troubleshooting Table 13: Troubleshooting Condition Cause Remedy Slow or no update of Protocol data is available for active IED applications Select manually the check boxes for clients of all visible data, reports disabled and the IED system. Active IED applications mean the 61850 data sets in the IEC 61850 Configuration tool, function blocks that have been added into the see the engineering guide for detailed instructions.
  • Page 39: Section 4 Iec 60870-5-103 Parameters And Diagnostics

    Section 4 1MRS759001 A IEC 60870-5-103 parameters and diagnostics Section 4 IEC 60870-5-103 parameters and diagnostics Parameter list The IEC 60870-5-103 parameters can be accessed with PCM600 or via the LHMI path Configuration/Communication/IEC 60870-5-103/I3C0n. Some parameters are not visible in the “Basic” setting visibility mode. To view all parameters use “Advanced”...
  • Page 40 Section 4 1MRS759001 A IEC 60870-5-103 parameters and diagnostics Parameter Values (Range) Unit Step Default Description Frame1InUse -1=Not in use 6=Private frame 6 Active Class2 Frame 1 0=User frame 1=Standard frame 2=Standard frame 3=Standard frame 4=Standard frame 5=Standard frame 6=Private frame 6 7=Private frame 7 Frame2InUse -1=Not in use...
  • Page 41: Monitored Data

    Section 4 1MRS759001 A IEC 60870-5-103 parameters and diagnostics Parameter Values (Range) Unit Step Default Description Class1OvInfNo 0...255 Information Number for Class 1 overflow indication Class1OvBackOff 0...500 Backoff Range for Class1 buffer GI Optimize 0=Standard 0=Standard Optimize GI traffic behaviour behaviour 1=Skip spontaneous...
  • Page 43: Section 5 Glossary

    Section 5 1MRS759001 A Glossary Section 5 Glossary Actual channel, related to IEC 60870-5-103 disturbance record Positive acknowledgement 1. Application Configuration tool in PCM600 2. Trip status in IEC 61850 ASCII American Standard Code for Information Interchange ASDU Application-layer service data unit Circuit breaker COMTRADE Common format for transient data exchange for power...
  • Page 44 Section 5 1MRS759001 A Glossary Light-emitting diode LHMI Local human-machine interface Least significant bit Most significant bit Negative acknowledgement Network control center OTEV Disturbance recording triggered from start bit PCM600 Protection and Control IED Manager Reset CU Reset communication unit Reset FCB Reset flow control bit Status of fault...
  • Page 48 — Nanjing SAC Power Grid Automation Co., Ltd. No.39 Shuige Road, Jiangning District 211153 Nanjing, China Phone +86 25 69832000 +86 25 69833000 www.abb.com/substationautomation © Copyright 2019 ABB. All rights reserved.

Table of Contents