  • Page 1 ® Relion 615 series Transformer Protection and Control RET615 DNP3 Point List Manual...
  • Page 3 Document ID: 1MRS756881 Issued: 2012-05-11 Revision: C Product version: 4.0 © Copyright 2012 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    Table of contents Table of contents Section 1 Introduction...............5 This manual..................5 Intended audience................5 Product documentation...............5 Product documentation set............5 Document revision history.............6 Related documentation..............6 Symbols and conventions..............7 Symbols..................7 Document conventions..............7 Functions, codes and symbols............8 Section 2 DNP3 data mappings.............11 Overview...................11 Supported functions................11 Point list for RET615 Ver.4.0 TE01-08..........13 Binary inputs................13 LD0.ARCSARC1 Fault arc protection stage 1......13...
  • Page 8 Table of contents CTRL.LLN0 Local/remote state (also present in DNP IIN- bits)..................18 LD0.LLN0 Settings supervision..........18 LD0.LREFPDIF1 Low-impedance restricted earth-fault protection (1)................18 LD0.MAPGAPC1 Multipurpose analog protection function (1)................19 LD0.MAPGAPC2 Multipurpose analog protection function (2)................19 LD0.MAPGAPC3 Multipurpose analog protection function (3)................19 LD0.MAPGAPC4 Multipurpose analog protection function (4)................19 LD0.MAPGAPC5 Multipurpose analog protection function (5)................19...
  • Page 9 Table of contents LD0.ROVPTOV1 Residual overvoltage protection (1)...24 LD0.ROVPTOV2 Residual overvoltage protection (2)...24 LD0.SEQRFUF1 Fuse failure protection........24 LD0.SPCGGIO2 Multipurpose binary outputs - status (2)...................25 LD0.SSCBR1 Circuit-breaker condition monitoring....25 LD0.T2PTTR1 Thermal protection (2)........26 LD0.TCSSCBR1 Trip circuit supervision (1)......26 LD0.TCSSCBR2 Trip circuit supervision (2)......26 LD0.TR2PDIF1 Transformer differential protection....26 LD0.TRPPTRC1 Global conditioning (1)........26 LD0.TRPPTRC2 Global conditioning (2)........27...
  • Page 10 Table of contents CTRL.DCSXSWI3 Disconnector 3, 4-pole (2 bit) position values................35 CTRL.DCXSWI1 Controllable disconnector 1, 4-pole (2 bit) position values..............35 CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2 bit) position values..............35 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values..................35 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values..................36 CTRL.ESXSWI1 Controllable earth switch 1, 4-pole (2 bit) position values..............36...
  • Page 11: Section 1 Introduction

    Section 1 1MRS756881 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
  • Page 12: Document Revision History

    B/2010-06-11 Content updated to correspond to the product version C/2012-05-11 Content updated to correspond to the product version Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual...
  • Page 13: Symbols And Conventions

    Section 1 1MRS756881 C Introduction Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 14: Functions, Codes And Symbols

    Section 1 1MRS756881 C Introduction 1.4.3 Functions, codes and symbols Table 1: RET615 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent PHLPTOC1 3I> (1) 51P-1 (1) protection, low stage PHLPTOC2 3I> (2) 51P-1 (2) Three-phase non-directional overcurrent PHHPTOC1 3I>>...
  • Page 15 Section 1 1MRS756881 C Introduction Function IEC 61850 IEC 60617 IEC-ANSI Multi-purpose protection MAPGAPC1 MAP (1) MAP (1) MAPGAPC2 MAP (2) MAP (2) MAPGAPC3 MAP (3) MAP (3) MAPGAPC4 MAP (4) MAP (4) MAPGAPC5 MAP (5) MAP (5) MAPGAPC6 MAP (6) MAP (6) Control Circuit-breaker control...
  • Page 17: Section 2 Dnp3 Data Mappings

    Section 2 1MRS756881 C DNP3 data mappings Section 2 DNP3 data mappings Overview This document describes the DNP3 data points and structures available in RET615 Ver.4.0. The data points are unmapped as a default on the DNP3 level.The point lists describe a superset of all data available through the standard configurations A, B, C, D, E, F, G, and H including the optional functionalities.
  • Page 18 Section 2 1MRS756881 C DNP3 data mappings IEC 61850 TE01 TE02 TE03 TE04 TE05 TE06 TE07 TE08 ROVPTOV1 (HV) ● ● ● ● ROVPTOV2 (HV) ● ● ● ● PHPTUV1 (HV) ● ● ● ● PHPTUV2 (HV) ● ● ● ●...
  • Page 19: Point List For Ret615 Ver.4.0 Te01-08

    Section 2 1MRS756881 C DNP3 data mappings IEC 61850 TE01 TE02 TE03 TE04 TE05 TE06 TE07 TE08 CMMXU2 (LV) ● ● ● ● ● ● ● ● CSMSQI1 (HV) ● ● ● ● ● ● ● ● RESCMMXU1 (HV) ● ●...
  • Page 20: Ld0.Arcsarc2 Fault Arc Protection Stage 2

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.2 LD0.ARCSARC2 Fault arc protection stage 2 Table 5: LD0.ARCSARC2 Fault arc protection stage 2 IEC 61850 name SA name Description Values LD0.ARCSARC21 .FADet.stVal ARC_FLT_DET Arc detected 1=Detected LD0.ARCPTRC21 .Op.general OPERATE Operate 1=Operate 2.3.1.3 LD0.ARCSARC3 Fault arc protection stage 3 Table 6:...
  • Page 21: Ctrl.dxxxxx1 Controllable Disconnector (1)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.5 CTRL.Dxxxxx1 Controllable disconnector (1) Table 8: CTRL.Dxxxxx1 Controllable disconnector (1) IEC 61850 name SA name Description Values CTRL.DCCILO1 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled .ItlByPss.stVal ITL_BYPASS Interlocking bypass 1=Bypassed CTRL.DCCSWI1 .Pos.stSeld...
  • Page 22: Ld0.Cmmxu1 Phase Currents (1) Limit Supervision

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.8 LD0.CMMXU1 Phase currents (1) limit supervision Table 11: LD0.CMMXU1 Phase currents (1) limit supervision IEC 61850 name SA name Description Values LD0.CMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning .LoAlm.stVal LOW_ALARM Low alarm...
  • Page 23: Ld0.Eflptoc1 Non-Directional Earth-Fault And Sensitive Earth-Fault Protection - Low Stage 1

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.12 LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1 Table 15: LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1 IEC 61850 name SA name Description Values LD0.EFLPTOC1 Low stage (1) .Op.general OPERATE...
  • Page 24: Ld0.Ledptrc1 Global Protection Signals

    Section 2 1MRS756881 C DNP3 data mappings IEC 61850 name SA name Description Values .SPCSO9.stVal LED 9 state 0/1=Off/On .SPCSO10.stVal LED 10 state 0/1=Off/On .SPCSO11.stVal LED 11 state 0/1=Off/On 2.3.1.16 LD0.LEDPTRC1 Global protection signals Table 19: LD0.LEDPTRC1 Global protection signals IEC 61850 name SA name Description...
  • Page 25: Ld0.Mapgapc1 Multipurpose Analog Protection Function (1)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.20 LD0.MAPGAPC1 Multipurpose analog protection function (1) Table 23: LD0.MAPGAPC1 Multipurpose analog protection function (1) IEC 61850 name SA name Description Values LD0.MAPGAPC1 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start 2.3.1.21 LD0.MAPGAPC2 Multipurpose analog protection function (2)
  • Page 26: Ld0.Mapgapc6 Multipurpose Analog Protection Function (6)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.25 LD0.MAPGAPC6 Multipurpose analog protection function (6) Table 28: LD0.MAPGAPC6 Multipurpose analog protection function (6) IEC 61850 name SA name Description Values LD0.MAPGAPC6 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start 2.3.1.26 LD0.MDSOPT1 Generic operation time supervision...
  • Page 27: Ld0.Nsptoc1 Negative-Sequence Overcurrent Protection (1)

    Section 2 1MRS756881 C DNP3 data mappings IEC 61850 name SA name Description Values .Q6.stVal Input 6 signal 0/1=Off/On .Q7.stVal Input 7 signal 0/1=Off/On .Q8.stVal Input 8 signal 0/1=Off/On 2.3.1.29 LD0.NSPTOC1 Negative-sequence overcurrent protection (1) Table 32: LD0.NSPTOC1 Negative-sequence overcurrent protection (1) IEC 61850 name SA name Description...
  • Page 28: Ld0.Phiptoc1 Phase Overcurrent Protection - Instantaneous Stage 1

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.33 LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1 Table 36: LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1 IEC 61850 name SA name Description Values LD0.PHIPTOC1 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start...
  • Page 29: Ld0.Phptov2 Phase Overvoltage Protection - Stage 2

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.38 LD0.PHPTOV2 Phase overvoltage protection - stage 2 Table 41: LD0.PHPTOV2 Phase overvoltage protection - stage 2 IEC 61850 name SA name Description Values LD0.PHPTOV2 .Op.general OPERATE Stage operate 1=Operate .Str.general START Stage start 1=Start 2.3.1.39 LD0.PHPTUV1 Phase undervoltage protection - stage 1...
  • Page 30: Ld0.Rescmmxu2 Residual Current Limit Supervision

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.43 LD0.RESCMMXU2 Residual current limit supervision Table 46: LD0.RESCMMXU2 Residual current limit supervision IEC 61850 name SA name Description Values LD0.RESCMMXU2 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning 2.3.1.44 LD0.RESVMMXU1 Residual voltage limit supervision Table 47: LD0.RESVMMXU1 Residual voltage limit supervision IEC 61850 name...
  • Page 31: Ld0.Spcggio2 Multipurpose Binary Outputs - Status (2)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.48 LD0.SPCGGIO2 Multipurpose binary outputs - status (2) Table 51: LD0.SPCGGIO2 Multipurpose binary outputs - status (2) IEC 61850 name SA name Description Values LD0.SPCGGIO2 .SPCS01.stVal Output 1 state 0/1=Off/On .SPCS02.stVal Output 2 state 0/1=Off/On .SPCS03.stVal Output 3 state...
  • Page 32: Ld0.T2Pttr1 Thermal Protection (2)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.50 LD0.T2PTTR1 Thermal protection (2) Table 53: LD0.T2PTTR1 Thermal protection (2) IEC 61850 name SA name Description Values LD0.T2PTTR1 .AlmThm.general ALARM Thermal alarm 1=Alarm .Op.general OPERATE General operate 1=Operate .Str.general START General start 1=Start 2.3.1.51 LD0.TCSSCBR1 Trip circuit supervision (1)
  • Page 33: Ld0.Trpptrc2 Global Conditioning (2)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.55 LD0.TRPPTRC2 Global conditioning (2) Table 58: LD0.TRPPTRC2 Global conditioning (2) IEC 61850 name SA name Description Values .Op.general Operate input signal 1=Operate .Tr.general Trip output signal 1=Trip 2.3.1.56 LD0.VMMXU1 Three-phase voltage limit supervision Table 59: LD0.VMMXU1 Three-phase voltage limit supervision IEC 61850 name...
  • Page 34: Ld0.Xggio100 Physical I/O

    Section 2 1MRS756881 C DNP3 data mappings 2.3.1.59 LD0.XGGIO100 Physical I/O Table 62: LD0.XGGIO100 Physical I/O IEC 61850 name SA name Description Values LD0.XGGIO100 .SPCSO1.stVal X100-Output 1 1/0=ON/OFF .SPCSO2.stVal X100-Output 2 1/0=ON/OFF .SPCSO3.stVal X100-Output 3 1/0=ON/OFF .SPCSO4.stVal X100-Output 4 1/0=ON/OFF .SPCSO5.stVal X100-Output 5 1/0=ON/OFF...
  • Page 35: Binary Outputs

    Section 2 1MRS756881 C DNP3 data mappings IEC 61850 name SA name Description Values .Ind6.stVal X130-Input 6 1/0=ON/OFF .SPCSO1.stVal X130-Output 1 1/0=ON/OFF .SPCSO2.stVal X130-Output 2 1/0=ON/OFF .SPCSO3.stVal X130-Output 3 1/0=ON/OFF 2.3.2 Binary outputs Table 65: Explanations of the binary output table columns Column name Description IEC 61850...
  • Page 36: Ctrl.escswi2 Controllable Earth Switch (1) Control

    Section 2 1MRS756881 C DNP3 data mappings 2.3.2.4 CTRL.ESCSWI2 Controllable earth switch (1) control Table 69: CTRL.ESCSWI2 Controllable earth switch (1) control IEC 61850 name SA name Description Type CTRL.ESCSWI1 .Pos.Oper.ctlVal Earth switch control On/Off 2.3.2.5 LD0.DNPGGIO1 Parameter setting group control Table 70: LD0.DNPGGIO1 Parameter setting group control IEC 61850 name...
  • Page 37: Dr.rdre1 Disturbance Recorder

    Section 2 1MRS756881 C DNP3 data mappings 2.3.2.8 DR.RDRE1 Disturbance recorder Table 73: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Type DR.RDRE1 .MemClr.Oper.ctlVal Clear all records .RcdTrg.Oper.ctlVal Trig recording 2.3.2.9 LD0.SPCGGIO1 Multipurpose binary outputs (1) The binary outputs may be configured either as pulse- or persistent-type outputs. Pulse-type outputs are triggered with the write value "1".
  • Page 38: Ld0.Srgapc1 Multipurpose Binary Outputs - Flip-Flop Resets (1)

    Section 2 1MRS756881 C DNP3 data mappings Table 75: LD0.SPCGGIO2 Multipurpose binary outputs (2) IEC 61850 name SA name Description Type LD0.SPCGGIO2 .SPCS01.ctlVal Output 1 control On/Off .SPCS02.ctlVal Output 2 control On/Off .SPCS03.ctlVal Output 3 control On/Off .SPCS04.ctlVal Output 4 control On/Off .SPCS05.ctlVal Output 5 control...
  • Page 39: Ld0.Srgapc2 Multipurpose Binary Outputs - Flip-Flop Resets (2)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.2.12 LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) Table 77: LD0.SRGAPC2 Multipurpose binary outputs - flip-flop resets (2) IEC 61850 name SA name Description Type .Rs1.ctlVal Reset flip-flop 1 .Rs2.ctlVal Reset flip-flop 2 .Rs3.ctlVal Reset flip-flop 3 .Rs4.ctlVal...
  • Page 40: Ctrl.cbcswi1 Cb 4-Pole (2 Bit) Position Value

    Section 2 1MRS756881 C DNP3 data mappings 2.3.3.1 CTRL.CBCSWI1 CB 4-pole (2 bit) position value Table 80: CTRL.CBCSWI1 CB 4-pole (2 bit) position value IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.CBCSWI1 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 2.3.3.2...
  • Page 41: Ctrl.dcsxswi2 Disconnector 2, 4-Pole (2 Bit) Position Values

    Section 2 1MRS756881 C DNP3 data mappings 2.3.3.6 CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values Table 85: CTRL.DCSXSWI2 Disconnector 2, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCSXSWI2 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3...
  • Page 42: Ctrl.essxswi2 Earth Switch 2, 4-Pole (2 Bit) Position Values

    Section 2 1MRS756881 C DNP3 data mappings 2.3.3.11 CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values Table 90: CTRL.ESSXSWI2 Earth switch 2, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.ESSXSWI2 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3...
  • Page 43: Ld0.Pemmtr1 Power Measurement And Accumulated Power Values

    Section 2 1MRS756881 C DNP3 data mappings IEC 61850 name SA name Description Values Arg 1,2,3,4 .PhyHealth2.stVal Internal Fault Internal fault code 0…65535 0,65535,0,65535 .WacTrg.stVal Num.of watchdog resets 0…65535 0,65535,0,65535 .WrmStr.stVal Num.of warm starts 0…65535 0,65535,0,65535 2.3.3.16 LD0.PEMMTR1 Power measurement and accumulated power values Table 95: LD0.PEMMTR1 Power measurement and accumulated power values IEC 61850 name...
  • Page 44: Ld0.Resvmmxu1 Residual Voltage (1)

    Section 2 1MRS756881 C DNP3 data mappings 2.3.3.20 LD0.RESVMMXU1 Residual voltage (1) Table 99: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESVMMXU1 0.00..4.00 .PhV.res.instCVal.mag U0_INST Residual voltage [xUn] 0,4,0,400 2.3.3.21 LD0.T2PTTR1 Temperature protection values (2) Table 100: LD0.T2PTTR1 Temperature protection values (2) IEC 61850 name...
  • Page 45: Ld0.Vsmsqi1 Sequence Of Voltage Measurement

    Section 2 1MRS756881 C DNP3 data mappings 2.3.3.24 LD0.VSMSQI1 Sequence of voltage measurement Table 103: LD0.VSMSQI1 Sequence of voltage measurement IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.VSMSQI1 Sequence of voltages 0.00…4.00 .SeqV.c1.cVal.mag I1_DB -Positive magnitude [xUn] 0,4,0,400 0.00…4.00 .SeqV.c2.cVal.mag I2_DB...
  • Page 47: Section 3 Dnp3 Protocol Implementation

    Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 105: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: RET615 Highest DNP level supported: Device function: For requests: Level 2+ ○...
  • Page 48 Section 3 1MRS756881 C DNP3 protocol implementation DNP3 device profile document ○ Sometimes ● Configurable as: "Only when reporting event data", or "When reporting event data or multi-fragment messages" Timeouts while waiting for: Data link ○ None ○ Fixed at ____ ○...
  • Page 49: Dnp3 Implementation Table

    Section 3 1MRS756881 C DNP3 protocol implementation DNP3 device profile document ○ Configurable ○ When device restarts ○ Only certain objects ○ When status flags change ○ Sometimes (attach explanation) ○ ENABLE/DISABLE UNSOLICITED No other options are permitted. function codes supported Default counter object/variation: Counters roll over at: ●...
  • Page 50 Section 3 1MRS756881 C DNP3 protocol implementation Table 106: Implementation table OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Object Variation Function codes Qualifier codes number number Description Function codes (dec) Qualifier codes (hex) (dec) (hex) Binary 1 (read) 00, 01 (start-stop) input –...
  • Page 51 Section 3 1MRS756881 C DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) 16-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) 2 (default) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) 32-bit...
  • Page 52 Section 3 1MRS756881 C DNP3 protocol implementation OBJECT REQUEST (Library will parse) RESPONSE (Library will respond with) Time delay 129 (response) 07 (limited qty) fine (qty = 1) Not defined Class 0 1 (read) 06 (no range, or all) data Class 1 1 (read) 06 (no range, or all)
  • Page 53: Section 4 Glossary

    Section 4 1MRS756881 C Glossary Section 4 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day.
  • Page 56 Contact us ABB Oy Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...