ABB Relion 615 Series Engineering Manual
ABB Relion 615 Series Engineering Manual

ABB Relion 615 Series Engineering Manual

Ansi
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

®
Relion
Protection and Control
615 series ANSI
Engineering Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 615 Series

  • Page 1 ® Relion Protection and Control 615 series ANSI Engineering Manual...
  • Page 3 Document ID: 1MAC108982-MB Issued: 2011-04-15 Revision: A Product version: 4.0 © Copyright 2011 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
  • Page 6 (EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7 Safety information Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage. Only a competent electrician is allowed to carry out the electrical installation. National and local electrical safety regulations must always be followed.
  • Page 9: Table Of Contents

    Table of contents Table of contents Section 1 Introduction................5 This manual....................5 Intended audience..................5 Product documentation................6 Product documentation set..............6 Document revision history..............7 Related documentation................8 Symbols and conventions.................8 Safety indication symbols..............8 Manual conventions................8 Section 2 IED engineering process.............11 Monitoring and control system structure..........13 Standard configuration concept..............14 Workflow....................16 Section 3 PCM600 tool................19...
  • Page 10 Table of contents Technical key..................50 IEC 61850 naming conventions to identify an IED......51 Setting the technical key..............53 COM600 project..................56 Importing a 615 series IED in a COM600 project......56 Using the Web HMI.................60 IED User Management................61 Section 5 Protection and control engineering........65 Application Configuration tool..............65 Function blocks..................66 Signals and signal management............67...
  • Page 11 Table of contents HMI display raster layout and text font selection......89 Text handling................89 Adding static text................89 Adding a measurand..............90 Adding a busbar................91 Adding symbols into a display page..........92 Drawing lines to create links............93 Bay configuration engineering............94 Creating a complete HMI display page.........94 Linking process objects..............96 Section 7 IEC 61850 communication engineering......99 IEC 61850 protocol references and pre-conditions........99...
  • Page 13: Section 1 Introduction

    Section 1 1MAC108982-MB A Introduction Section 1 Introduction This manual The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols.
  • Page 14: Product Documentation

    Section 1 1MAC108982-MB A Introduction Product documentation 1.3.1 Product documentation set Engineering manual Engineering manual Engineering manual Installation manual Installation manual Installation manual Commissioning manual Commissioning manual Commissioning manual Operation manual Operation manual Operation manual Service manual Service manual Service manual Application manual Application manual Application manual...
  • Page 15: Document Revision History

    Some of the manuals are not available yet. 1.3.2 Document revision history Document revision/date Product series version History A/2011-04-15 First release Download the latest documents from the ABB web site http:// www.abb.com/substationautomation. 615 series ANSI Engineering Manual...
  • Page 16: Related Documentation

    Section 1 1MAC108982-MB A Introduction 1.3.3 Related documentation Product series- and product-specific manuals can be downloaded from the ABB web site http://www.abb.com/substationautomation. Symbols and conventions 1.4.1 Safety indication symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
  • Page 17 Section 1 1MAC108982-MB A Introduction • Parameter names are shown in italics, for example: The function can be enabled and disabled with the Operation setting. • Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "Enabled" and "Disabled". •...
  • Page 19: Section 2 Ied Engineering Process

    Section 2 1MAC108982-MB A IED engineering process Section 2 IED engineering process PCM600 is used for various tasks in the IED engineering process. • IED engineering management • Organizing the bay IEDs in the structure of the substation by defining voltage levels and bays below the substation.
  • Page 20 Section 2 1MAC108982-MB A IED engineering process • Monitoring the selected signals of an IED for commissioning or service purposes by using the Signal Monitoring tool and Event Viewer tool. GUID-AEEFCDDD-591F-4555-A6D5-78FC69BF623F V2 EN Figure 2: Organization of PCM600 in different management tasks There are also additional functions for managing projects and organizing user rights.
  • Page 21: Monitoring And Control System Structure

    Section 2 1MAC108982-MB A IED engineering process Monitoring and control system structure The monitoring and control system for electrical substations contains a number of IEDs for various purposes. See PCM600 documentation for the recommended size of a project. Larger projects can be divided into several PCM600 projects. NCC-GW PCM600 Station level...
  • Page 22: Standard Configuration Concept

    Section 2 1MAC108982-MB A IED engineering process • Project • Substation = name of the substation • Voltage level = identifies to which grid type or part the IED belongs in the substation • Bay = bay within the voltage level •...
  • Page 23 Section 2 1MAC108982-MB A IED engineering process Some of the standard configurations offers very wide functionality in means of number of different functions available as part of the product configuration. It is possible to use all of the offered functions at the same time. However, if unused function blocks are removed from the configuration with the Application Configuration, more resources in the IED can be used for other purposes, for example :...
  • Page 24: Workflow

    Section 2 1MAC108982-MB A IED engineering process Workflow Start Create plant structure and insert IED objects Project ACT/ Configure IED functionality Save the work between the different steps Parametrization Create single line diagram for local HMI IEC 61850 Supported protocols Export SCL files from Export PCM600...
  • Page 25 Section 2 1MAC108982-MB A IED engineering process Setting up a PCM600 project • The plant structure is built according to the substation structure. See PCM600 documentation for the recommended size of a project. Larger projects can be divided into several PCM600 projects. •...
  • Page 26 Section 2 1MAC108982-MB A IED engineering process • The communication engineering details are protocol dependent. • The connectivity package creates the IEC 61850 configuration for vertical communication automatically and it is directly suitable, in most cases, for IEC 61850 client configuration. A station configuration tool, for example CCT600, is used for horizontal communication.
  • Page 27: Section 3 Pcm600 Tool

    Section 3 1MAC108982-MB A PCM600 tool Section 3 PCM600 tool Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all stages of the IED life cycle. • Planning • Engineering • Commissioning • Operation and disturbance handling •...
  • Page 28 Section 3 1MAC108982-MB A PCM600 tool PCM600 can be used for different purposes throughout the IED life cycle. A set of special tools is available for different applications. The applications can be organized into groups. • IED product engineering • IED communication engineering per protocol •...
  • Page 29: Connectivity Packages

    • IED Connectivity Package REM615 ANSI Ver. 4.0 or later • IED Connectivity Package RET615 ANSI Ver. 4.0 or later Download connectivity packages from the ABB web site http:// www.abb.com/substationautomation PCM600 projects A typical project in PCM600 contains a plant structure including one or several IED objects, where each IED object contains the engineering data created or modified using the different PCM600 tools.
  • Page 30: Communication Between Pcm600 And The Ied

    Section 3 1MAC108982-MB A PCM600 tool With PCM600, it is possible to do various tasks. • Open existing projects • Import projects • Create new projects • Export projects • Delete projects • Rename projects • Copy and paste projects The extension of the exported project file is .pcmp.
  • Page 31 Section 3 1MAC108982-MB A PCM600 tool Table 1: Ports that must be open in the firewall for different protocols Protocol TCP port File Transfer Protocol (FTP) 20, 21 IEC 61850 Web Server HTTP Simple Network Time Protocol (SNTP) Modbus TCP DNP TCP 20000 615 series ANSI...
  • Page 33: Section 4 Setting Up A Project

    Section 4 Setting up a project Installing connectivity packages Close PCM600. Run the ABB IED Connectivity Package RE_6xx Ver. n.msi installer. (n = version number) To install the connectivity package, follow the steps in the installation software guide. Activating connectivity packages The IED connectivity package has to be installed before activating the connectivity packages.
  • Page 34 Section 4 1MAC108982-MB A Setting up a project GUID-7A72A86C-7F41-4342-AAF3-CF34E8279B4E V1 EN Figure 6: Help menu – Update Manager The Update Manager shows the IEDs that are compatible with the installed PCM600 version. Select IED Connectivity Package RE_615 ANSI Ver. n (n = version number) to use 615 series products.
  • Page 35: Setting Up Communication Between Pcm600 And The Ied

    Section 4 1MAC108982-MB A Setting up a project GUID-B3D2C177-2737-425F-B4E4-22F4D4326343-ANSI V1 EN Figure 7: Activating the connectivity package PCM600 recognizes the installed connectivity package(s) during startup and the corresponding IED types are available in PCM600 when starting a new project. The ANSI 2.0 and 4.0 IED versions can be in the same PCM600 project only if the project was created with ANSI 4.0 connectivity package.
  • Page 36: Setting Up The Pc Or Workstation For Point-To-Point Access To The Ied's Front Port

    Section 4 1MAC108982-MB A Setting up a project The IED front port IP address is fixed to 192.168.0.254 and it cannot be modified. Set the IP address for the IED rear port and the corresponding subnet mask via the LHMI path: Configuration/Communication/Ethernet/Rear port. Default IP address for the IED rear port Corresponding subnet mask 192.168.2.10...
  • Page 37 Section 4 1MAC108982-MB A Setting up a project RJ-45 PCM600 IEC09000096-1-en.vsd IEC09000096 V1 EN Figure 8: Point-to-point link between the IED and PCM600 using a cross- over Ethernet cable From the Start menu, select Settings/Network Connections. IEC09000355-1-en.vsd IEC09000355 V1 EN Figure 9: Selecting network connections The Network connections dialog box is displayed.
  • Page 38 Section 4 1MAC108982-MB A Setting up a project IEC09000356-1-en.vsd IEC09000356 V1 EN Figure 10: Selecting local area connection properties The Local Area Connection Properties dialog box is displayed. IEC09000357-1-en.vsd IEC09000357 V1 EN Figure 11: Local Area Connection Properties From the list of configured components, select the Internet Protocol (TCP/IP) using this connection and click Properties.
  • Page 39: Creating A New Project

    Section 4 1MAC108982-MB A Setting up a project IEC09000358-1-en.vsd IEC09000358 V1 EN Figure 12: TCP/IP settings Click Obtain an IP address automatically and OK. Close all open dialog boxes and start PCM600. Creating a new project Start PCM600. To see the projects that are currently available in the PCM databases, select File/ Open/Manage Project on the menu bar.
  • Page 40: Building The Plant Structure

    Section 4 1MAC108982-MB A Setting up a project IEC09000375-1-en.vsd IEC09000375 V1 EN Figure 14: Creating a new project In the Project Name box, give a name for the project. The project name should be unique. Optionally, write a description of the project in the Description box. Click Create.
  • Page 41: Inserting An Ied

    Section 4 1MAC108982-MB A Setting up a project • In the Plant Structure view, right-click and select New/ Create from Template. • In the Plant Structure view, right-click and select New/ General and select the element: either IED Group or Substation. On the menu bar, click View/ Object Types.
  • Page 42: Inserting An Ied In Online Mode

    Section 4 1MAC108982-MB A Setting up a project • Insert an IED to offline mode or online mode • Import a template IED that is available in the template library as a .pcmt file • Import a preconfigured IED available as a *.pcmi file From the plant structure it is possible to see whether the inserted IED is in the offline or online mode.
  • Page 43 Section 4 1MAC108982-MB A Setting up a project In the Plant Structure view, right-click the bay and from the list that appears, select New and the IED application area, for example, Motor Protection IEDs and select the IED type to be inserted. GUID-AF88B4EA-85AF-43E8-AED7-D6EF9DD25B9C-ANSI V1 EN Figure 17: Selecting the IED type...
  • Page 44 Section 4 1MAC108982-MB A Setting up a project GUID-C326AA0A-27ED-46DF-8B61-7484B8CB41F1-ANSI V1 EN Figure 18: PCM600: Configuration mode selection Select Online Configuration and click Next. The Communication protocol selection page is displayed. 615 series ANSI Engineering Manual...
  • Page 45 Section 4 1MAC108982-MB A Setting up a project GUID-F8B3A98A-BD75-4E2D-B279-822A2504F1EE-ANSI V1 EN Figure 19: PCM600: Communication protocol selection In the IED protocol list, select the IED communication protocol and click Next. The Communication protocol page is displayed. 615 series ANSI Engineering Manual...
  • Page 46 Section 4 1MAC108982-MB A Setting up a project GUID-3FD49387-3726-4483-AD54-7FBC6D441805-ANSI V1 EN Figure 20: PCM600: Communication port and IP address In the Port list, select the port. • If the rear port is selected, insert the correct IP address (of the physical IED to be configured) into the IP address box.
  • Page 47 Section 4 1MAC108982-MB A Setting up a project GUID-FAC9B045-7D1C-4996-B038-F2DEEEFAD10A V1 EN Figure 21: Communication configuration defined Click Next in the Configuration Wizard. Click Scan to scan/read the order code of the IED. The Order code detection page is displayed. 615 series ANSI Engineering Manual...
  • Page 48 Section 4 1MAC108982-MB A Setting up a project GUID-DAE10A3A-6821-4B06-B33A-670E22FC9834-ANSI V1 EN Figure 22: PCM600: IED order code detection Click Next. The Setup Complete Page dialog box shows the summary of the IED type, version, IP address and the selected order number. 615 series ANSI Engineering Manual...
  • Page 49 Section 4 1MAC108982-MB A Setting up a project GUID-02789F3F-DD47-4CDB-86DE-F9258E01BF50-ANSI V1 EN Figure 23: PCM600: IED setup complete To cancel the insertion, click Cancel. If an error is found on the Setup Complete Page, it is not possible to go back and make modifications. If an error is detected, cancel the insertion by clicking Cancel and insert the IED again.
  • Page 50: Inserting An Ied In Offline Mode

    Section 4 1MAC108982-MB A Setting up a project From the Plant structure view, check that PCM600 has turned online the IED that was inserted to the bay level. You cannot scan data from the IED or proceed further if the IED is not online or if the IP address is not correct.
  • Page 51 Section 4 1MAC108982-MB A Setting up a project GUID-2A8CE4A6-1AA7-4129-A1B5-A739D4BCA4B7-ANSI V1 EN Figure 24: PCM600: Configuration Mode Selection Wizard Select Offline Configuration and click Next. Setting up an IED in the offline mode is similar as in the online mode; however, with offline mode it is not necessary to type the correct IP address in the Communication port and IP address dialog box.
  • Page 52: Inserting An Ied From The Template Directory

    Section 4 1MAC108982-MB A Setting up a project 4.6.3 Inserting an IED from the template directory An IED in the plant structure can be exported as a template (.pcmt file). The template library can be build up of all the exported IED templates. It is also possible to insert an IED from the template library to create a new IED in the plant structure.
  • Page 53: Inserting An Ied By Importing A .Pcmi File

    Section 4 1MAC108982-MB A Setting up a project GUID-62DCC284-90D6-498A-A79A-25E884C61CC8-ANSI V1 EN Figure 26: PCM600: template information Check and verify the template information and click Close to close the window. The Create New Object from Template dialog box is displayed. You can now delete, import or create a template by clicking the corresponding button.
  • Page 54 Section 4 1MAC108982-MB A Setting up a project A .pcmi file can only be selected when the bay is selected in the plant structure. In the Plant Structure view, right-click the bay and from the list that appears, select Export. GUID-9C892D93-9D92-4DB7-A576-B20716E42895 V1 EN Figure 27: Exporting IED configuration...
  • Page 55 Section 4 1MAC108982-MB A Setting up a project GUID-970C33D9-9A83-4C83-AE3E-F237BEEF4F7A-ANSI V1 EN Figure 28: Export dialog box Click Save. A .pcmi file is created in the selected path. In the Plant Structure view, right-click the bay and from the list that appears, select Import.
  • Page 56: Setting The Ied Ip Address In A Project

    Section 4 1MAC108982-MB A Setting up a project GUID-187F89B8-CF8B-457B-A6C2-09E3FF34E929-ANSI V1 EN Figure 29: Importing IED configuration Select the .pcmi file to be imported and click Open. After importing, the IED object is created in the plant structure. After the .pcmi file has been imported, the IP address, the name and the technical key that corresponds to the physical IED have to be changed.
  • Page 57 Section 4 1MAC108982-MB A Setting up a project • On the first page of the wizard when including a new IED into a project. • In the IP address box of the IED's Object Properties dialog box. GUID-0C8D23CA-5BB5-4D36-9B11-245B5465D9E1-ANSI V1 EN Figure 30: Alternative 1: setting the IP address on the first wizard page 615 series ANSI...
  • Page 58: Technical Key

    Section 4 1MAC108982-MB A Setting up a project GUID-B4B71E12-25CB-4B8B-8F9A-90131BD68E4D V1 EN Figure 31: Alternative 2: setting the IP address in IED's Object Properties dialog box The used alternative depends on the time at which the IP address is available. Entering the IP address via the IED Object Properties dialog box is possible at any time.
  • Page 59: Iec 61850 Naming Conventions To Identify An Ied

    Section 4 1MAC108982-MB A Setting up a project PCM600, because data in PCM600 may get lost when importing the SCL files. The technical key must be the same for the communication between the IED and PCM600. The technical key can be read from the IED and updated to PCM600, or the PCM600 technical key can be written to the IED.
  • Page 60 Section 4 1MAC108982-MB A Setting up a project User-oriented textual designation is contained in the desc attribute. Attributes are not allowed to contain carriage return, line feed or tab characters. The semantics of desc must also be relative within an object hierarchy. PCM600 takes care of the two possibilities.
  • Page 61: Setting The Technical Key

    Section 4 1MAC108982-MB A Setting up a project GUID-81D555F9-0F22-4112-BF6D-48F2A3376612-ANSI V1 EN Figure 33: PCM600: IEC 61850 signal designation concept The created technical key for the full path name of the IED would be: AA1J1Q01A1. • AA1 = substation in the project •...
  • Page 62 Section 4 1MAC108982-MB A Setting up a project GUID-EE8F635B-1895-4117-A756-F80FA9027037-ANSI V1 EN Figure 34: PCM600: Setting the technical key on the IED level A dialog box opens to inform about the technical key concept. 615 series ANSI Engineering Manual...
  • Page 63 Section 4 1MAC108982-MB A Setting up a project GUID-6A512EF8-5BDF-4B4A-A721-8152DB9D51A1 V1 EN Figure 35: Techical key information Click OK. The technical key is read from the IED and the Set Technical Key dialog box opens. GUID-177E6088-50E3-4A18-83E6-9777AEACB3C1 V1 EN Figure 36: Setting the technical key In Set Technical Key dialog box, select the techical key to be used.
  • Page 64: Com600 Project

    Section 4 1MAC108982-MB A Setting up a project Do not use a technical key that has more than 10 characters. Click OK to confirm the selection. It is not possible to set a user-defined name or select the Technical key in IED if the value is the same as already given to another IED object in the PCM600 project.
  • Page 65 Section 4 1MAC108982-MB A Setting up a project GUID-01F6FEB6-B57B-4A56-939B-46750205D914 V1 EN Figure 37: Creating a PCM600 project including several 615 devices Export the SCD file from PCM600. In the Plant structure view, select the substation, right-click and select Export. 615 series ANSI Engineering Manual...
  • Page 66 Section 4 1MAC108982-MB A Setting up a project IEC09000687-1-en.vsd IEC09000687 V1 EN Figure 38: Exporting SCD file from PCM600 and importing it to SAB600 Import the SCD configuration into the SAB600 project. In the Project Explorer view, right-click the IEC61850 OPC Server object and select Import.
  • Page 67 Section 4 1MAC108982-MB A Setting up a project GUID-70E8B187-FADA-4657-9BC7-223FDA7374ED V1 EN Figure 39: Importing the SCD configuration into the SAB600 project In the SCL Import view, click Select File to select the SCD file exported from PCM600. 615 series ANSI Engineering Manual...
  • Page 68: Using The Web Hmi

    Section 4 1MAC108982-MB A Setting up a project GUID-6F47B4AD-B956-4F77-A6A2-DE6F4A71D607 V1 EN Figure 40: Creating a new 615 series device into SAB600 project Check the default settings in the SCL Import view and change the settings if they are not suitable. The default settings in the SCL Import dialog should be OK in most cases.
  • Page 69: Ied User Management

    Section 4 1MAC108982-MB A Setting up a project For more information on the WHMI, see the operation manual. 4.11 IED User Management IED user authorization is disabled by default and can be enabled at Main Menu/ Configuration/Authorization in local HMI or WHMI. IED user passwords can be changed in local HMI and using IED User Management tool in PCM600.
  • Page 70 Section 4 1MAC108982-MB A Setting up a project GUID-D0853D4E-D594-454A-9299-997ADF3E0896 V1 EN Figure 42: Object properties When communicating with IED using PCM tools and having IED authentication enabled, the user will be prompted for IED user name and password. When setting the technical key, the user has to give the username and password twice.
  • Page 71 Section 4 1MAC108982-MB A Setting up a project If PCM authentication has been enabled in PCM System Settings, an IED user can be linked to the PCM user being used by checking the Remember me flag in the IED Login dialog. After that the IED Login dialog will not be needed at tool communication in the future, since logging into PCM will then also provide for IED authentication credentials.
  • Page 73: Section 5 Protection And Control Engineering

    Section 5 1MAC108982-MB A Protection and control engineering Section 5 Protection and control engineering Application Configuration tool Application Configuration tool is used to modify an application configuration for an IED. The application configuration is built of function blocks. The function blocks are dedicated to different functions. •...
  • Page 74: Function Blocks

    Section 5 1MAC108982-MB A Protection and control engineering • Insert function blocks, make connections and create variables • Include the hardware I/O channels directly to the application configuration • Calculate the execution order automatically by clicking Calculate execution order on the toolbar. •...
  • Page 75: Signals And Signal Management

    Section 5 1MAC108982-MB A Protection and control engineering GUID-805CB8E5-0BF2-409D-802C-57DC95659075 V1 EN Figure 44: Application Configuration tool: function block overview 1. Connection(s) 2. User-defined function block name 3. Function block, selected (red) 4. Function block name 5. Function block, locked (red) 6.
  • Page 76: Function Block Execution Parameters

    Section 5 1MAC108982-MB A Protection and control engineering Boolean input and output signals may need to be inverted to fulfil the logic. The Application Configuration tool supports the adding of inversion logic to a binary signal. The input signal on glue logic function blocks can only be inverted if a glue logic function block with lower execution order in the same cycle time is available.
  • Page 77: Execution Order And Feedback Loops

    Section 5 1MAC108982-MB A Protection and control engineering GUID-4129D712-CD43-4729-8FE4-27FFE758D151-ANSI V1 EN Figure 45: Application Configuration tool: an example of function block organization parameters The Cycle Time is automatically set to 2.5 ms (50 Hz) or to 2.083 ms (60 Hz) and it cannot be modified.
  • Page 78: Configuration Parameters

    Section 5 1MAC108982-MB A Protection and control engineering GUID-F8162182-FF21-467A-AEB9-23284CB3FABD V1 EN Figure 46: Feedback loop situation with automatically calculated execution orders By setting a smaller execution number than in the AND port to where the NOT port is connected, it is possible to fix the execution order of all functions in a loop so that they are handled in the same task.
  • Page 79: Hardware Channels

    Section 5 1MAC108982-MB A Protection and control engineering It is possible to search and replace variable names in Application Configuration tool. Connect the variables to a destination, for example to a function block or a hardware output channel. The connectivity package automatically removes the orphan variables which are not connected to any destination.
  • Page 80: Validation

    Section 5 1MAC108982-MB A Protection and control engineering GUID-40339889-3049-4C50-BA8F-8C3EB9A54C4D V1 EN Figure 49: Application Configuration tool: HW signal channels There are three types of supported hardware channels. • Binary input channels • Binary output channels • Analog input channels Hardware input channel can be used as often as needed. A hardware binary output channel is taken from the list of available channels when a new channel is requested.
  • Page 81: Validation On Demand

    Section 5 1MAC108982-MB A Protection and control engineering • A connection between two input or two output signals is not possible • A connection between two different data types is not possible: for example, from a binary output to an analog input 5.1.8.2 Validation on demand The validity of an application configuration can be checked by clicking Validate...
  • Page 82: Validation When Writing To The Ied

    Section 5 1MAC108982-MB A Protection and control engineering GUID-6C889FF5-800B-44B4-ACC6-6544DFB55BD6 V1 EN Figure 50: Application Configuration tool: validation on demand 5.1.8.3 Validation when writing to the IED When writing the application configuration to the IED, an automatic validation is performed. The validation is the same as the manually demanded validation. Errors abort the writing.
  • Page 83: Configuration Parameter

    Section 5 1MAC108982-MB A Protection and control engineering A common writing from PCM600 to the IED, where parameters are changed in the Parameter Setting tool, overwrites any parameter changes made locally with LHMI. All variables listed and displayed in the parameter list can be sorted into two groups. •...
  • Page 84 Section 5 1MAC108982-MB A Protection and control engineering The Signal Matrix tool cannot be used for adding or removing function blocks, for example, GOOSE receive function blocks. The Application Configuration tool is used for this kind of operations. Binary Inputs Binary Outputs Analog...
  • Page 85 Section 5 1MAC108982-MB A Protection and control engineering logic means inserting a logical gate (OR and AND blocks) between the function blocks and the binary output channel. This can be engineered with the Signal Matrix tool. A binary output channel can only be activated from one function block output. If it is activated from more than one function block output, the glue logic has to be used.
  • Page 86: Load Profile Tool

    Section 5 1MAC108982-MB A Protection and control engineering • Binary inputs • Binary outputs • Analog inputs • Functions • GOOSE Load Profile tool The Load Profile tool is used for downloading load profile records from a specific directory in an IED using FTP, clearing old records by sending a command using parameter dispatcher services in the connectivity package and viewing records by launching an external COMTRADE file viewer, by default Wavewin, an optional third- party application distributed in the PCM600 installer.
  • Page 87 Section 5 1MAC108982-MB A Protection and control engineering GUID-F8120497-31C8-4F8B-BBE8-D1338CF4E4E6 V1 EN Figure 53: Opening the Load Profile tool • To close the Load Profile tool, click the Close button in the tool. The Load Profile tool runs in the same process as PCM600 but in a separate window.
  • Page 88 Section 5 1MAC108982-MB A Protection and control engineering GUID-4B275369-045F-4407-89A2-44071839699D V1 EN Figure 54: Load Profile tool By default, the Load Profile tool uses a LPR subdirectory as a download target directory in the location that PCM600 suggests that is currently C:/PCMDatabases. Thus, the default location is C:/PCMDatabases/LPR.
  • Page 89: Load Profile Tool User Interface

    Section 5 1MAC108982-MB A Protection and control engineering 5.4.2 Load Profile tool user interface GUID-4B275369-045F-4407-89A2-44071839699D V1 EN Figure 55: Load Profile tool interface Table 3: Available actions on the user interface Action Description Local Path Default local path (C:/PCMDataBases/LPR) is the location from which the records are shown on the Load Profile tool.
  • Page 90: Information Fields

    Section 5 1MAC108982-MB A Protection and control engineering Action Description Open Select any record and click Open to view the record in Wavewin, provided that this external software is installed. Additionally, any record row can be double-clicked to view that record. Sort To sort the record rows by any column click a column header.
  • Page 91: Opening And Closing Fault Record Tool

    Section 5 1MAC108982-MB A Protection and control engineering 5.5.1 Opening and closing Fault Record tool • To open the Fault Record tool, click Fault Record Tool on the context menu of an IED node inside the PCM600 project tree. GUID-06441245-E6DA-4C9F-9363-26CE8D521CB2 V1 EN Figure 57: Opening the Fault Record tool •...
  • Page 92: Fault Record Tool Interface

    Section 5 1MAC108982-MB A Protection and control engineering Fault Record tool is a connectivity package tool. The main functionality is divided into three parts – reading the fault record parameters from the IED, displaying their names, values and units on the user interface and saving them to a text file. It is also possible to clear all the fault records from both the tool and the IED and copy the fault records either individually or all at once and paste them to a word processor.
  • Page 93: Section 6 Lhmi Engineering

    Section 6 1MAC108982-MB A LHMI engineering Section 6 LHMI engineering For information on LED operation modes supported by 615 series, see technical manual. Single-line diagram engineering A single-line diagram of the IED can be designed by using the Graphical Display Editor tool of PCM600.
  • Page 94: Display Window And Sequence Order

    Section 6 1MAC108982-MB A LHMI engineering HMI display page Symbol library IED HMI display window window GUID-8843160D-28CC-46D5-8045-445FAAB335B9-ANSI V1 EN Figure 58: Graphical Display Editor: an active view The Graphical Display Editor has a fixed symbol library window on the left side of the view.
  • Page 95: Symbol Library

    Section 6 1MAC108982-MB A LHMI engineering 6.1.1.2 Symbol library The Symbol Library view contains panes that include drawing symbols or elements for creating a single-line diagram, measurements and texts onto a page. Panes can be opened by clicking the name bar of the selected element. The library shows the symbols either in the ANSI standard or IEC standard.
  • Page 96 Section 6 1MAC108982-MB A LHMI engineering Description IEC representation ANSI representation Disconnector – Closed position Disconnector – Bad (faulty) position Truck – Intermediate position Truck – Open position Truck – Closed position Truck – Bad (faulty) position In-feeder Out-feeder Current transformer Voltage transformer Ground symbol Motor...
  • Page 97: Hmi Display Raster Layout And Text Font Selection

    Section 6 1MAC108982-MB A LHMI engineering 6.1.1.4 HMI display raster layout and text font selection The raster on the page changes from symbol presentation to text presentation when a text object is selected and vice versa. The text can be presented in UniCode characters (6 x 12 pixel). The total size of the presented white area (page) represents the visible part of the LHMI display without the header line.
  • Page 98: Adding A Measurand

    Section 6 1MAC108982-MB A LHMI engineering GUID-4D3D2FE7-B26C-4177-BE09-CE3CEBAF71B8 V1 EN Figure 59: Adding a static text field into a LHMI view Edit the text in the Name field in the Object Properties view, or alternatively double-click the text to edit it. 6.1.1.7 Adding a measurand Place a Measurand object into a raster box by dragging-and-dropping.
  • Page 99: Adding A Busbar

    Section 6 1MAC108982-MB A LHMI engineering GUID-4606198B-521D-4804-BBC8-8E041E144026 V1 EN Figure 60: Adding a measurand object to an LHMI view In the Objects Properties view, edit the name, unit and the number of decimals. Unit text specifies the default text used for the measurement's unit. If Unit text is not empty, the unit in the IED is updated dynamically based on the signal it is connected to.
  • Page 100: Adding Symbols Into A Display Page

    Section 6 1MAC108982-MB A LHMI engineering Select Busbar Junction Place Busbar Junctions into symbol and use Rotate display page command from toolbar to get the busbar end to the margin GUID-A58439A5-575C-4EED-A5A9-77FDECAA9D21 V1 EN Figure 61: Graphical Display Editor: drawing a busbar and placing busbar junctions Add a link between one Busbar Junction point and the corresponding symbol or junction point.
  • Page 101: Drawing Lines To Create Links

    Section 6 1MAC108982-MB A LHMI engineering Use X and Y cordinates from the Object Properties window for every symbol to adjust the singleline diagram. GUID-BB90E914-7B02-4D1E-A385-FB6D6305869C-ANSI V1 EN Figure 62: Graphical Display Editor: adding single-line diagram symbols into a display page 6.1.1.10 Drawing lines to create links After the apparatus symbols are placed, lines can be drawn to create links.
  • Page 102: Bay Configuration Engineering

    Section 6 1MAC108982-MB A LHMI engineering Select Line draw icon from toolbar to draw lines between symbols GUID-795A6797-D4D9-4705-A496-C3FBD771C211-ANSI V1 EN Figure 63: Graphical Display Editor: drawing a line between symbols Draw all line elements that are necessary. To finish the line drawing, click Select on the menu bar. 6.1.2 Bay configuration engineering A view with a single-line diagram and measurements contains active living objects.
  • Page 103 Section 6 1MAC108982-MB A LHMI engineering Make a sketch of how to present the single-line diagram. Place the apparatus, transformer and other symbols that are needed for the single- line diagram into the raster boxes. Add Junction points where needed. Link the apparatus symbols with line elements.
  • Page 104: Linking Process Objects

    Section 6 1MAC108982-MB A LHMI engineering 6.1.2.2 Linking process objects To describe a process object within an IED, it needs to be established in the application configuration, configured when given the parameters by the Parameter Setting tool and linked to be displayed in the HMI. Three tools are involved in the described steps.
  • Page 105 Section 6 1MAC108982-MB A LHMI engineering GUID-28A8463E-7A11-47FA-938F-17436CBFB0BD-ANSI V1 EN Figure 65: Graphical Display Editor: input signal selection The ordering number in the selection window of the process objects corresponds to the number given in the Parameter Setting tool tree and to the application function block in the Application Configuration tool.
  • Page 106 Section 6 1MAC108982-MB A LHMI engineering GUID-1DB1A930-A312-4B55-8F68-3D8327A873FB V1 EN Figure 66: Graphical Display Editor: object properties view for text insertion 615 series ANSI Engineering Manual...
  • Page 107: Section 7 Iec 61850 Communication Engineering

    Section 7 1MAC108982-MB A IEC 61850 communication engineering Section 7 IEC 61850 communication engineering IEC 61850 protocol references and pre-conditions To engineer the IEC 61850 protocol interface for the IED, the following additional manuals or knowledge of their contents is required. •...
  • Page 108: Iec 61850 Interface In The Ied

    Section 7 1MAC108982-MB A IEC 61850 communication engineering 7.2.1 IEC 61850 interface in the IED GOOSE GOOSE GOOSE Receive Receive Receive GOOSE GOOSE GOOSE Send Send Send with monitoring only part Commands with part Event monitoring handler commands Event queue part IEC08000364.vsd IEC08000364 V1 EN...
  • Page 109: Function View For Iec 61850 In Pcm600

    Section 7 1MAC108982-MB A IEC 61850 communication engineering The concept is based on sending a multicast over the Ethernet. Whoever needs the information, detects the telegram by its source address, reads the telegram and deals with it. The telegrams are multicast sent and not acknowledged by the receiver. IEC 61850 Subnetwork Data-set Data-set...
  • Page 110: Station Configuration Description File Types

    • An IED is already extended by default data sets and report control blocks. They are predefined by ABB. Changes or additional data sets, for example, have to be done with CCT600. •...
  • Page 111: Exporting Scl Files From Pcm600

    Section 7 1MAC108982-MB A IEC 61850 communication engineering SCL files are exported from PCM600. In this case, a SCD file. It is also possible to export other SCL file types. Horizontal and vertical communication is configured using the station configuration tool, for example, CCT600. SCL files are imported to a PCM600 project.
  • Page 112 Section 7 1MAC108982-MB A IEC 61850 communication engineering IEC08000415-ANSI V1 EN Figure 70: IEC 61850: selecting the station Right-click the station and select Export. From the open standard Windows dialog box, select the location to store the file and name it. Click Save.
  • Page 113: Exporting Icd Or Cid Files

    Section 7 1MAC108982-MB A IEC 61850 communication engineering 7.3.1.2 Exporting ICD or CID files Select the IED in the Plant Structure view. Right-click the IED and select Export... The Export dialog box opens. From the Save as type list, select the type of file to export. •...
  • Page 114: Engineering Vertical And Horizontal Communication In Cct600

    Section 7 1MAC108982-MB A IEC 61850 communication engineering 7.3.2 Engineering vertical and horizontal communication in CCT600 For more information on engineering in CCT600, see the IEC 61850 engineering guide. Create a project in CCT600. On the menu, select Tools/ SCL Import/Export/ Import SCL File to import the SCD file created by PCM600.
  • Page 115 Section 7 1MAC108982-MB A IEC 61850 communication engineering IEC09000630-1-en.vsd IEC09000630 V1 EN Figure 75: CCT600 data set default content 3.2. Configure and/or re-configure the default data sets. Reporting data sets can only contain data intended to be used by clients, for example, for event handling. The data set for GOOSE may contain signals on data attribute level.
  • Page 116: Importing Scl Files To Pcm600

    Section 7 1MAC108982-MB A IEC 61850 communication engineering 4.1. Configure GOOSE control blocks for each data set configured for GOOSE messages. One data must be included only once in the GOOSE data set. 4.2. Define the client IEDs for each GOOSE control block. 4.3.
  • Page 117 Section 7 1MAC108982-MB A IEC 61850 communication engineering IEC09000631-1-en.vsd IEC09000631 V1 EN Figure 76: IEC 61850: importing a SCD file In the SCL Import Options dialog box, select how to handle the file during the import. • Click Don't import IEDs of unknown type to protect the existing IEDs in case the SCD file does not match the original configuration in PCM600.
  • Page 118 Section 7 1MAC108982-MB A IEC 61850 communication engineering IEC09000616-ANSI V1 EN Figure 77: Common write menu The engineered data is written to the IED when executing a common Write to IED operation. 615 series ANSI Engineering Manual...
  • Page 119: Importing Icd Or Cid Files

    Section 7 1MAC108982-MB A IEC 61850 communication engineering 7.3.3.2 Importing ICD or CID files Select an existing IED to import IEC 61850 files. From the Files of type list, select the file type of IEC 61850 to be imported (ICD or CID).
  • Page 120 Section 7 1MAC108982-MB A IEC 61850 communication engineering configuration is changed, but no changes are done to the instantiation or deletion of functions that represent a logical node. When a changed configuration is written to the IED, you are asked to update the communication configuration.
  • Page 121: Section 8 Glossary

    Section 8 1MAC108982-MB A Glossary Section 8 Glossary 615 series Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Application Configuration tool in PCM600; Trip status ANSI American National Standards Institute CCT600 Communication Configuration tool Configured IED description...
  • Page 122 Section 8 1MAC108982-MB A Glossary IP address A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a unique IP address that specifies the location for the TCP/IP protocol. Local area network Light-emitting diode LHMI Local human-machine interface...
  • Page 124 Contact us ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone +1 (800) 523-2620 Phone +1 954-752-6700 +1 954 345-5329 www.abb.com/substationautomation...

Table of Contents