ABB Relion 650 series RET650 Product Manual

Transormer protection

Advertisement

Quick Links

®
Relion
650 series
Transformer protection RET650
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 650 series RET650

  • Page 1 ® Relion 650 series Transformer protection RET650 Product Guide...
  • Page 2: Table Of Contents

    10. Logic..............22 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB AB. ABB AB assumes no responsibility for any errors that may appear in this document. © Copyright 2011 ABB AB.
  • Page 3: Series Overview

    • Minimized parameter setting based on theory of symmetrical components . default values and ABB's new global base Low impedance restricted earth-fault value concept. You only need to set those protection function are available as...
  • Page 4 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Disturbance recording is available to allow • Tap changer control (A07) independent post-fault analysis after primary The packages are configured and ready for disturbances. direct use. Analog and tripping IO has been Three packages have been defined for the pre-defined for basic use.
  • Page 5 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 110 kV Bus RET650 A01 - 2 Winding Transformer protection 10AI (8I+2U) 50BF 3I> BF 50/51 3I> 52PD 3I>> 200/1 CC RBRF OC4 PTOC CC RPLD TR PTTR PH PIOC TCM YLTC IdN/I...
  • Page 6 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 110 kV Bus RET650 A05 - 3 Winding Transformer protection 20AI 2*(6I+4U) 110kV/100V Meter. CV MMXN 300/1 50BF 3I> BF 50/51 3I> 52PD 3I>> CC RBRF OC4 PTOC CC RPLD TR PTTR PH PIOC...
  • Page 7 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 T1 Data: T2 Data: 20 MVA 20 MVA 110±11*1.5% / 21 kV 110±11*1.5% / 21 kV 105 / 550 A 105 / 550 A YNd5 YNd5 =11 % =11 % RET650 A07 –...
  • Page 8: Available Functions

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 3. Available functions Main protection functions IEC 61850/ ANSI Function description Transformer Function block name Differential protection T2WPDIF Transformer differential protection, two winding T3WPDIF Transformer differential protection, three winding REFPDIF Restricted earth fault protection, low...
  • Page 9 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Back-up protection functions IEC 61850/ ANSI Function description Transformer Function block name Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51/67 Four step directional phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection...
  • Page 10 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Transformer Function block name SAPTUF Underfrequency function SAPTOF Overfrequency function SAPFRC Rate-of-change frequency protection...
  • Page 11 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Control and monitoring functions IEC 61850/ ANSI Function description Transformer Function block name Control QCBAY Bay control LOCREM Handling of LR-switch positions LOCREMCTRL LHMI control of Permitted Source To Operate (PSTO) TR8ATCC Automatic voltage control for tap...
  • Page 12 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Transformer Function block name Logic SMPPTRC Tripping logic TMAGGIO Trip matrix logic Configurable logic blocks, OR gate INVERTER Configurable logic blocks, Inverter gate PULSETIMER Configurable logic blocks, Pulse...
  • Page 13 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Transformer Function block name CMMXU Phase current measurement VMMXU Phase-phase voltage measurement CMSQI Current sequence component measurement VMSQI Voltage sequence measurement VNMMXU Phase-neutral voltage measurement CNTGGIO Event counter...
  • Page 14 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 IEC 61850/ ANSI Function description Transformer Function block name I103FLTPROT Function status fault protection for IEC60870-5-103 I103IED IED status for IEC60870-5-103 I103SUPERV Supervison status for IEC60870-5-103 I103USRDEF Status for user defined signals for IEC60870-5-103 Metering...
  • Page 15 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Designed to communicate IEC 61850/ ANSI Function description Transformer Function block name Station communication IEC 61850 communication protocol, LAN1 DNP3.0 for TCP/IP communication protocol, LAN1 IEC61870-5-103 IEC60870-5-103 serial communication via ST GOOSEINTLKRCV Horizontal communication via...
  • Page 16 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Basic IED functions IEC 61850/ Function description Function block name Basic functions included in all products INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list SNTP Time synchronization TIMESYNCHGEN...
  • Page 17: Differential Protection

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 the station. An adaptive stabilizing feature is 4. Differential protection included for heavy through-faults. Stabilization is included for inrush currents as Transformer differential protection well as for overexcitation condition. Adaptive T2WPDIF/T3WPDIF stabilization is also included for system recovery inrush and CT saturation for...
  • Page 18: Current Protection

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 voltage dependent resistor externally to the Four step residual overcurrent IED. protection EF4PTOC HZPDIF can be used as high impedance REF The four step residual overcurrent protection protection.
  • Page 19: Voltage Protection

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 CCRBRF can be current based, contact based, functions can alternatively be used to check or an adaptive combination of these two the direction of active or reactive power flow principles.
  • Page 20: Frequency Protection

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 outages or as long-time delayed back-up to 7. Frequency protection primary protection. UV2PTUV has two voltage steps, where step Underfrequency protection SAPTUF 1 is settable as inverse or definite time delayed.
  • Page 21: Secondary System Supervision

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 motor driven load tap changer. The functions 8. Secondary system provide automatic regulation of the voltage supervision on the secondary side of transformers or alternatively on a load point further out in the network.
  • Page 22: Logic

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 other means, such as binary inputs and Logic rotating switch for function SPGGIO function blocks. The commands can selection and LHMI presentation be pulsed or steady. SLGGIO AutomationBits AUTOBITS The logic rotating switch for function selection and LHMI presentation function...
  • Page 23: Monitoring

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 • GATE function block is used for whether Integer to Boolean 16 conversion or not a signal should be able to pass from IB16A the input to the output. Integer to boolean 16 conversion function •...
  • Page 24 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Disturbance report DRPRDRE, always disturbance. This information is used in the included in the IED, acquires sampled data of short perspective to get information via the all selected analog input and binary signals local HMI in a straightforward way.
  • Page 25 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Disturbance recorder DRPRDRE Station battery supervision SPVNZBAT The Disturbance recorder function supplies fast, complete and reliable information about The station battery supervision function disturbances in the power system. It SPVNZBAT is used for monitoring battery facilitates understanding system behavior and terminal voltage.
  • Page 26: Metering

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 The function contains a blocking 13. Human Machine functionality. It is possible to block the interface function outputs, if desired. Local HMI 12. Metering Pulse counter logic PCGGIO Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses coming from an external...
  • Page 27: Basic Ied Functions

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 • Status indication LEDs • SNTP • Alarm indication LEDs which can • IRIG-B indicate three states with the colors • DNP green, yellow and red, with user •...
  • Page 28: Station Communication

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 tripping applications in substations, as Authority check ATHCHCK defined by the IEC 61850 standard. The IED interoperates with other IEC 61850-compliant To safeguard the interests of our customers, IEDs, tools, and systems and simultaneously both the IED and the tools that are accessing reports events to five different clients on the...
  • Page 29: Hardware Description

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 This is typically used for sending apparatus Flush mounting the IED position indications for interlocking or reservation signals for 1-of-n control. GOOSE can also be used to exchange any boolean, integer, double point and analog measured values between IEDs.
  • Page 30 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Rack mounting the IED Wall mounting the IED IEC09000678.ai IEC09000678 V1 EN Figure 11. Wall mounting the IED 270 mm 190.5 mm IEC09000676.ai 252.5 mm 296 mm IEC09000676 V1 EN ∅6.8 mm Figure 9.
  • Page 31: Connection Diagrams

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 17. Connection diagrams Module Slot Rear Position pCOM X0, X1, X4, X9,X304 pPSM X307, X309, X410 X101, X102 X103, X104 X331, X334 X336, X339 1MRK006501-FB 2 PG 1.1 IEC V1 EN Figure 13.
  • Page 32 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Module Slot Rear Position pCOM X0, X1, X4, X9,X304 pPSM X307, X309, X410 X101, X102 X321, X324 X326, X329 X331, X334 X336, X339 1MRK006501-GB 2 PG 1.1 IEC V1 EN Figure 14.
  • Page 33 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Connection diagrams for RET650 A01 1MRK006501-GB 5 PG 1.1 IEC V1 EN Figure 17. Power supply module (PSM), 110-250V DC 1MRK006501-GB 3 PG 1.1 IEC V1 EN Figure 15.
  • Page 34 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Connection diagrams for RET650 A05 1MRK006501-GB 7 PG 1.1 IEC V1 EN Figure 19. Binary input/output (BIO) option (Terminal X321, X324) 1MRK006501-FB 3 PG 1.1 IEC V1 EN Figure 21.
  • Page 35 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-FB 5 PG 1.1 IEC V1 EN Figure 23. Power supply module (PSM), 110-250V DC 1MRK006501-FB 7 PG 1.1 IEC V1 EN Figure 25. Analog input module (AIM) 1MRK006501-FB 6 PG 1.1 IEC V1 EN Figure 24.
  • Page 36 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-EB 4 PG 1.1 IEC V1 EN Figure 29. Power supply module (PSM) 1MRK006501-FB 9 PG 1.1 IEC V1 EN 48-125V DC Figure 27. Binary input/output (BIO) option (Terminal X336, X339) Connection diagrams for RET650 A07 1MRK006501-EB 5 PG 1.1 IEC V1 EN...
  • Page 37 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 1MRK006501-EB 8 PG 1.1 IEC V1 EN Figure 33. Binary input/output (BIO) option (Terminal X326, X329) 1MRK006501-EB 6 PG 1.1 IEC V1 EN Figure 31. Transformer module (TRM) 1MRK006501-EB 7 PG 1.1 IEC V1 EN Figure 32.
  • Page 38: Technical Data

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 18. Technical data General Definitions Reference The specified value of an influencing factor to which are referred the value characteristics of the equipment Nominal The range of values of an influencing quantity (factor) within which, under range specified conditions, the equipment meets the specified requirements Operative...
  • Page 39 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Analog inputs Table 2. Energizing inputs Description Value Rated frequency 50/60 Hz Operating range Rated frequency ± 5 Hz Current inputs Rated current, I 0.1/0.5 A 1/5 A Thermal withstand capability: •...
  • Page 40 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Auxiliary DC voltage Table 3. Power supply Description Type 1 Type 2 nominal 100, 110, 120, 220, 240 V 48, 60, 110, 125 V DC AC, 50 and 60 Hz 110, 125, 220, 250 V DC variation 85...110% of U...
  • Page 41 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 5. Signal output and IRF output IRF relay change over - type signal output relay Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 10 A Make and carry 0.5 s 30 A...
  • Page 42 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 8. Ethernet interfaces Ethernet interface Protocol Cable Data transfer rate CAT 6 S/FTP or better 100 MBits/s LAN/HMI port (X0) LAN1 (X1) TCP/IP protocol Fibre-optic cable 100 MBits/s with LC connector 1) Only available for the external HMI option.
  • Page 43 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 14. Environmental conditions Description Value Operating temperature range -25...+55ºC (continuous) Short-time service temperature range -40...+70ºC (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25...+55ºC Relative humidity <93%, non-condensing...
  • Page 44 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Type tests according to standards Table 16. Electromagnetic compatibility tests Description Type test value Reference 100 kHz and 1 MHz burst IEC 61000-4-18 disturbance test IEC 60255-22-1, level 3 •...
  • Page 45 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 16. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity IEC 60255-22-7, class A test 300 V rms IEC 61000-4-16 • Common mode 150 V rms •...
  • Page 46 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 17. Insulation tests Description Type test value Reference Dielectric tests: IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min 1 kV, 50 Hz, 1 min, communication Impulse voltage test: IEC 60255-5...
  • Page 47 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 EMC compliance Table 20. EMC compliance Description Reference EMC directive 2004/108/EC Standard EN 50263 (2000) EN 60255-26 (2007)
  • Page 48 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Differential protection Table 21. Transformer differential protection T2WPDIF, T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ± 1.0% of Ir for I < Ir ± 1.0% of Ir for I > Ir Reset ratio >94% Unrestrained differential current...
  • Page 49 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 22. Restricted earth fault protection, low impedance REFPDIF Function Range or value Accuracy Operate characteristic Adaptable ± 1.0% of Ir for I < Ir ± 1.0% of I for I > Ir Reset ratio >95% Base sensitivity function...
  • Page 50 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Current protection Table 24. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (5-2500)% of lBase ±...
  • Page 51 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 25. Four step phase overcurrent protection OC4PTOC Function Setting range Accuracy ± 1.0% of I Operate current (5-2500)% of lBase at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 52 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 26. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 53 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 27. Four step residual overcurrent protection EF4PTOC Function Range or value Accuracy ± 1.0% of I at I £ I Operate current (1-2500)% of lBase ± 1.0% of I at I > I Reset ratio >...
  • Page 54 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 28. Thermal overload protection, two time constants TRPTTR Function Range or value Accuracy Base current 1 and 2 (30–250)% of IBase ± 1.0% of I Operate time: = load current before IEC 60255–8, class 5 + 200 ms overload occurs...
  • Page 55 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 30. Pole discordance protection CCRPLD Function Range or value Accuracy Operate value, current (0-100) % ± 1.0% of I asymmetry level Reset ratio >95% Time delay (0.000-60.000) s ±...
  • Page 56 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 32. Negative sequence based overcurrent function DNSPTOC Function Range or value Accuracy Operate current (2.0 - 5000.0) % of IBase ± 1.0% of I at I <I ±...
  • Page 57 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Voltage protection Table 33. Two step undervoltage protection UV2PTUV Function Range or value Accuracy Operate voltage, low and (1–100)% of UBase ± 0.5% of U high step Reset ratio <105% Inverse time characteristics...
  • Page 58 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 35. Two step residual overvoltage protection ROV2PTOV Function Range or value Accuracy Operate voltage, step 1 (1-200)% of UBase ± 0.5% of U at U < U ±...
  • Page 59 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Frequency protection Table 37. Under frequency protection SAPTUF Function Range or value Accuracy Operate value, start function (35.00-75.00) Hz ± 2.0 mHz Operate value, restore frequency (45 - 65) Hz ±...
  • Page 60 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 39. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, restore enable (45.00 - 65.00) Hz ±...
  • Page 61 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Control Table 41. Voltage control TR8ATCC, TCMYLTC Function Range or value Accuracy Transformer reactance on ATCC side (0.1–200.0)Ω, primary Time delay for lower command (1.0–100.0) s when fast step down mode is activated Voltage control set voltage (85.0–120.0)% of UB2...
  • Page 62 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 41. Voltage control TR8ATCC, TCMYLTC, continued Function Range or value Accuracy Alarm level of reactive power in (-9999.99–9999.99) MVAr ± 1.0% of S forward and reverse direction Time delay for alarms from power (1–6000) s ±...
  • Page 63 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 43. Configurable logic blocks Logic block Quantity with cycle time Range or value Accuracy 5 ms 20 ms 100 ms INVERTER SRMEMORY RSMEMORY GATE PULSETIMER (0.000–90000.000) s ±...
  • Page 64 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 45. Event counter CNTGGIO Function Range or value Accuracy Counter value 0-10000 Max. count up speed 10 pulses/s...
  • Page 65: Time Synchronization

    Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 46. Disturbance report DRPRDRE Function Range or value Accuracy Current recording ± 1,0% of I at I ≤ I ± 1,0% of I at I > Ir Voltage recording ±...
  • Page 66 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 47. Event list DRPRDRE Function Value Buffer capacity Maximum number of events in 1000 the list Resolution 1 ms Accuracy Depending on time synchronizing Table 48. Indications DRPRDRE Function Value Buffer capacity...
  • Page 67 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 51. Disturbance recorder DRPRDRE Function Value Buffer capacity Maximum number of analog inputs Maximum number of binary inputs Maximum number of disturbance reports 100 Maximum total recording time (3.4 s recording time and 340 seconds (100 recordings) maximum number of channels, typical value) at 50 Hz...
  • Page 68 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 55. Circuit breaker condition monitoring SSCBR Function Range or value Accuracy Alarm levels for open and (0-200) ms ± 0.5% ± 25 ms close travel time Alarm levels for number of (0 - 9999) operations...
  • Page 69 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Dimensions Table 60. Dimensions Description Value Width 220 mm Height 265.9 mm (6U) Depth 249.5 mm Weight box <10 kg (6U) Weight LHMI 1.3 kg (6U) Inverse time characteristics Table 61.
  • Page 70 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 62. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è...
  • Page 71 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 64. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01 unless otherwise stated æ...
  • Page 72 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 65. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of Class 5 +40 ms 0.01 unless otherwise stated æ...
  • Page 73 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Table 66. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in Class 5 +40 ms steps of 0.01 æ...
  • Page 74: Ordering

    Configuration alternatives Notes and Rules Single breaker, 2 winding, IEC Single breaker, 3 winding, IEC Tap changer control, IEC ACT configuration ABB standard configuration Selection for position #2. Software options Notes and Rules No option Selection for postition #3 First HMI language...
  • Page 75 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Casing Notes and Rules Rack casing, 6 U 1/2 x 19" Selection for position #5. Mounting details with IP40 of protection from the front Notes and Rules No mounting kit included Rack mounting kit for 6 U 1/2 x 19"...
  • Page 76 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Connection type for Analog modules Notes and Rules Compression terminals Ringlug terminals Analog system Slot position: Transformer module, 6I + 4U, 1/5A, 100/220V Only in A05 and A07 Transformer module, 8I + 2U, 1/5A, 100/220V Only in A01 Slot position:...
  • Page 77 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 LED Label special paper A4, 1 pc Quantity: 1MRK 002 038-CA LED Label special paper Letter, 1 pc Quantity: 1MRK 002 038-DA Manuals Note: One (1) IED Connect CD containing user documentation (Operation manual, Technical manual, Installation manual, Commissioning manual, Application manual, Communication protocol manual, DNP, Communication protocol manual, IEC61850, Communication protocol manual, IEC60870-5-103, Type test certificate, Engineering manual and Point list manual, DNP3, Connectivity packages and LED...
  • Page 78 Transformer protection RET650 1MRK 504 127-BEN - Product version: 1.1 Issued: February 2011 Reference information For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name: Voltage level: Related documents Documents related to RET650 Identity number Application manual...
  • Page 80 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...