ABB RELION 610 Series Product Manual

Feeder protection

Advertisement

Quick Links

RELION® 610 SERIES
Feeder Protection
REF610
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION 610 Series

  • Page 1 — RELION® 610 SERIES Feeder Protection REF610 Product Guide...
  • Page 2: Table Of Contents

    24. Document revision history........... 26 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    REF610 is also used as back-up protection for motors, transformers and generators in utility and industry applications. ® systems. REF610 is a member of ABB’s Relion protection and Further, the 610 series protection relays are suitable for control product family and part of its 610 product series. The employment in marine and offshore environments.
  • Page 4: Protection Functions

    Feeder Protection 1MRS756295 G REF610 Product version: C 3. Protection functions protection of the switchgear, busbar system and cable The protection relay offers overcurrent and thermal overload terminals. protection, earth-fault and phase-discontinuity protection for The numerical feeder protection relays of the 610 series cable feeders, and three-pole, multi-shot autoreclose functions support a wide range of standard communication protocols, for overhead-line feeders.
  • Page 5: Application

    Feeder Protection 1MRS756295 G REF610 Product version: C 4. Application GUID-416CF20D-7FAB-4438-AB02-E62119B61063 V1 EN Figure 2. Substation O/C and E/F protection based on 610 series protection relays. Equipped with an optional hardware module REF610 also provides fast and selective arc fault protection.
  • Page 6: Measurement

    Feeder Protection 1MRS756295 G REF610 Product version: C GUID-3DF1D683-0319-4A79-958D-252F4D745A96 V1 EN Figure 3. Substation feeder O/C and E/F protection, and substation busbar protection based on 610 series protection relays. The operate time of the busbar protection has been speeded up using the principle of upstream interlocking. The connection of the CTs to REF610 depends on the available be a cable line and a sensitive earth-fault protection be number and types of CTs in the feeder cubicle.
  • Page 7: Event Recorder

    Feeder Protection 1MRS756295 G REF610 Product version: C and eight digital signal channels. The analog channels can be and in its open position. It also detects loss of circuit-breaker set to record the curve form of the currents measured. The control voltage.
  • Page 8 Feeder Protection 1MRS756295 G REF610 Product version: C Table 2. Optional communication modules and protocols Protocol Bus connection modules and gateways ● ● ● DNP3 ● IEC 60780-5-103 ● ● ● GUID-047CEFC9-339A-4C81-A6FD-2EB4ABEFA164 V1 EN Modbus (RTU and ● ● ● Protection relay ASCII) IEC 61850...
  • Page 9: Technical Data

    Feeder Protection 1MRS756295 G REF610 Product version: C 13. Technical data Table 3. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth Case 149.3 mm Weight Protection relay 3.5 kg Spare unit 1.8 kg Table 4.
  • Page 10 Feeder Protection 1MRS756295 G REF610 Product version: C Table 6. Measuring range Description Value Measured currents on phases I and I as multiples of the rated 0... 50 × I currents of the energizing inputs Earth-fault current as a multiple of the rated current of the energizing input 0...
  • Page 11 Feeder Protection 1MRS756295 G REF610 Product version: C Table 10. Power outputs PO1, PO2 and PO3 Description Value Rated voltage 250 V AC/DC Continuous carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R <...
  • Page 12 Feeder Protection 1MRS756295 G REF610 Product version: C Table 15. Environmental tests Description Reference Dry heat test (humidity <50%) According to IEC 60068-2-2 Dry cold test According to IEC 60068-2-1 Damp heat test, cyclic (humidity >93%) According to IEC 60068-2-30...
  • Page 13 Feeder Protection 1MRS756295 G REF610 Product version: C Table 16. Electromagnetic compatibility tests Description Type test value Reference EMC immunity test level meets the requirements listed below 1 MHz burst disturbance test, class III IEC 60255-22-1, IEC 61000-4-18 • Common mode 2.5 kV 1.0 kV •...
  • Page 14 Feeder Protection 1MRS756295 G REF610 Product version: C Table 17. Insulation tests Description Type test value Reference Dielectric tests IEC 60255-5 • Test voltage 2 kV, 50 Hz, 1 min Impulse voltage test IEC 60255-5 • Test voltage 5 kV, unipolar impulses, waveform 1.2/50 μs, source energy 0.5 J Insulation resistance measurements IEC 60255-5...
  • Page 15 Feeder Protection 1MRS756295 G REF610 Product version: C Protection functions Table 19. Three-phase overcurrent protection (I>, I>>, I>>>) Feature Stage I> Stage I>> Stage I>>> Set start value, I>, I>> and I>>> • at definite-time characteristic 0.30...5.00 x I 0.50...35.0 x I 0.50...35.0 x I •...
  • Page 16 Feeder Protection 1MRS756295 G REF610 Product version: C Table 20. Non-directional earth-fault protection (I >, I >>) Feature Stage I > Stage I >> Set start value, I > and I >> • At definite-time characteristic 1.0...100% I 5.0...800% In •...
  • Page 17 Feeder Protection 1MRS756295 G REF610 Product version: C Table 21. Three-phase thermal overload protection for cables (θ>) Feature Value Set full load current, I 0.30...1.50 x I θ Set alarm level, θ > 50...100% Trip level, θ > 100% Time constant, τ 1...200 min Operate time accuracy I/I >1.2...
  • Page 18 Feeder Protection 1MRS756295 G REF610 Product version: C Table 24. Autoreclose function (O → I) Feature Value Trigger pulse Any start/trip signal Number of shots 0...3 CB closing time 0.1...10 s Start delay of stage I> 0...300 s Start delay of stage I >...
  • Page 19: Mounting Methods

    Feeder Protection 1MRS756295 G REF610 Product version: C 14. Mounting methods For routine testing purposes, the relay cases can be equipped Using the appropriate mounting accessories, the standard relay with test switches, type RTXP 18, which can be mounted side case for the 610 series relays can be flush mounted, semi-flush by side with the relay cases.
  • Page 20 Feeder Protection 1MRS756295 G REF610 Product version: C REF610C  Revision Current revision Phase current inputs Earth-fault current input 0.2 A Power supply: H = 110-240 V AC/110-250 V DC, 2xDI (110/125/220/250 VDC), 3xPO, 2xSO 24-60 V DC, 2xDI (24/48/60/110/125/220/250 V DC), 3xPO, 2xSO I/O extension module:...
  • Page 21: Accessories

    Feeder Protection 1MRS756295 G REF610 Product version: C REF610SS  Revision Current revision Phase current inputs Earth-fault current input 0.2 A Power supply: H = 110-240 V AC/110-250 V DC, 2xDI (110/125/220/250 VDC), 3xPO, 2xSO 24-60 V DC, 2xDI (24/48/60/110/125/220/250 V DC), 3xPO, 2xSO I/O extension module:...
  • Page 22: Tools

    Feeder Protection 1MRS756295 G REF610 Product version: C Table 27. Mounting accessories Item Order number Semi-flush mounting kit 1MRS050696 Inclined semi-flush mounting kit 1MRS050831 19” rack mounting kit with cutout for one protection relay 1MRS050694 19” rack mounting kit with cutout for two protection relays 1MRS050695 Surface mounting frame 1MRS050697...
  • Page 23 Feeder Protection 1MRS756295 G REF610 Product version: C Table 32. Supported functions Function CAP 501 CAP 505 CET for SPA- LNT 505 PCM600 ZC 40x Parameter setting ● ● ● Disturbance handling ● ● ● Signal monitoring ● ● ● Disturbance record analysis ●...
  • Page 24: Terminal Diagram

    Feeder Protection 1MRS756295 G REF610 Product version: C 19. Terminal diagram GUID-1F4CD79D-8312-48F4-8952-F8223A95E77F V2 EN Figure 9. Terminal diagram of REF610...
  • Page 25: Approvals

    KEMA has issued a Type test Certificate of Complete type test for the 610 series products. Certificate No. 08-1071, 08-1072 and 08-1073. 22. References www.abb.com/substationautomation portal provides DNV (Det Norske Veritas) has issued a Type Approval information on the entire range of distribution automation Certificate for the 610 series protection relays.
  • Page 26: Document Revision History

    Feeder Protection 1MRS756295 G REF610 Product version: C 24. Document revision history Document revision/date Product version History A/2007-02-10 First release B/2007-06-04 Content updated to correspond to the product version C/2009-10-30 Content updated to correspond to the product version D/2009-12-14 Content updated E/2010-04-20 Order codes corrected F/2011-11-18...
  • Page 28 — ABB Distribution Solutions Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 www.abb.com/mediumvoltage www.abb.com/relion © Copyright 2019 ABB. All rights reserved.