7.10. Characteristics of the
control module contacts
without potential
The contacts without potential are supplied with
special relays.
For the characteristics of the contacts, please see
the table and curves given below.
notes
– In the case of inductive loads, the contacts must be protected
against overvoltages by means of varistors.
– For the other characteristics, please refer to the IEC
60694.5.4.4.5.4 (Ed. 2.2), Class 3 Standards.
3
10
10
10
Curve a
Maximum power applicable (v d.c. on resistive load).
7
10
6
10
5
10
Cosϕ = 0.4
4
10
1
2
Curve b
electrical life of the contacts at 250 v a.c.
fig. 14
32
2
1
0.1
Cosϕ = 1
Cosϕ = 0.7
3
4
5
Rated voltage
(operating range)
Maximum power applicable
(see curves B and C)
Maximum voltage applicable
Maximum current applicable
Rated current
Maximum contact resistance
Maximum capacity
Maximum closing time
Maximum opening time
Insulation between contacts and coil
Resistance with contacts open
Operating temperature
Storage temperature
Mechanical life
Electrical life
1
7
10
6
10
5
10
4
10
3
10
1
6
Curve C
electrical life of the contacts at 24 v d.c.
0 ... 264 V~ 50/60 Hz
0 ... 280 V–
1500 VA
(V a.c. on resistive load)
(V d.c. on resistive load - curve A)
400 V~ 50/60 Hz
300 V–
6 A
6 A (250 V~ 50/60 Hz - resistive load)
< 100 mohm (measured at 6 V– / 1 A)
< 1.5 pF
< 5 ms
< 3 ms
4000 Vrms (50 Hz / 1 min)
Min. 10
Mohm (measured at 500 V–)
3
- 40 °C ... + 85 °C
- 40 °C ... + 100 °C
5.000,000 operations (at 180 operations/min)
N.O. 50,000 (at 6 operations/min)
N.C. 30,000 (at 6 operations/min)
10
I (A)
τ
= 0 ms
τ
acc. dC 13
2