3. Receiving, handling, and storage
VM1/A/P circuit-breakers are subject to complete factory
production tests and inspection prior to packaging and
shipment. The shipping package is designed to provide
reasonable protection during shipment and to provide
convenient handling. Accessories such as opening handles
and racking handles are shipped separately from the circuit-
breaker.
The circuit-breaker is shipped in special packing, in the open
position.
Each piece of apparatus is protected by a plastic cover
to prevent any infiltration of water during the loading and
unloading stages and to keep the dust off during storage.

3.1. Receiving and checking

befoRe CaRRying out any oPeRation,
alwayS Make SuRe that the CaPaCitoRS
aRe diSChaRged and that the aPPaRatuS iS
in the oPen PoSition.
On receipt, check the state of the apparatus, integrity of the
packing and correspondence with the nameplate data (see
Fig.1) with what is specified in the order confirmation and in
the accompanying shipping notes.
Also make sure that all the materials described in the shipping
notes are included in the supply.
Should any damage or irregularity be noted in the supply
on unpacking, notify ABB (directly or through the agent or
supplier) as soon as possible and in any case within five days
of receipt.
The apparatus is only supplied with the accessories specified
at the time of ordering and validated in the order confirmation
sent by ABB.
The accompanying documents inserted in the shipping
packing are:
– instruction manual (this document)
– test certification
– identification label
– copy of the shipping documents
– electric wiring diagram.
Other documents which are sent prior to shipment of the
apparatus are:
– order confirmation
– original shipping advice notes
– any drawings or documents referring to special
configurations/conditions.
6
Caution
A
CIRCUIT-BREAKER
1
VM1/A/P 15.12.32
CLASSIFICATION
3
1VC1...............................
SN
MASS
VOLTAGE
LIGHTNING IMPULSE WITHSTAND VOLTAGE
FREQUENCY
NORMAL CURRENT
SHORT TIME WITHSTAND CURRENT
DURATION OF SHORT CIRCUIT
4
SHORT CIRCUIT BREAKING CURRENT
D.C. COMPONENT
RATED INTERRUPTING TIME
INSTRUCTION BOOK
CABLE-CHARGING BREAKING CURRENT
OPERATING SEQUENCE
ELECTRICAL DIAGRAM 1VCD400051 (E0926)
FIG.01 FIG.02 FIG.05 FIG.OS FIG.12
llllllllIIlllllllIlllllllIllllllllllllllllllIlIlllllllIlllllllIllllllllll
B
A3
-RL2
5
AUXILIARY VOLTAGE
Made by ABB, Italy
Caption
A Circuit-breaker rating plate.
B Drive ratingplate.
1 Type of apparatus.
2 Symbols of compliance with Standards.
3 Serial number.
4 Circuit-breaker characteristics.
5 Characteristics of the drive auxiliaries.
fig. 1
Immediately upon receipt of the circuit-breaker(s), examine
the carton(s) to determine if any damage or loss was
sustained during transit. If damage or indication of rough
handling is evident, file a damage claim at once with the
carrier and promptly notify the nearest district office. ABB
is not responsible for damage to goods which occur after
delivery. However, ABB will lend assistance if notified of
claims. Use care in unpacking the circuit-breaker to avoid
damaging any circuit-breaker parts.
Unpack circuit-breakers as soon as possible after receipt.
If unpacking is delayed, difficulty may be experienced in
making a claim for damages not evident upon receipt.
Check the contents of each carton against the packing list
before discarding any packing material. If any discrepancy
is discovered, promptly notify the nearest district office.
Information specifying the purchase order number, carton
number, and part numbers of damaged or missing parts
should accompany the claim.
ANSI C37.04
PR. YEAR 2010
84
kg
15
kV
95
kV
60
Hz
1200
A
31.5
kA
2
s
31.5
kA
< = 40
%
< = 50
ms
1VCD600916R000
A
O-0,3S-CO-3MI N-CO
OPERATING MECHANISM
110 V
110...250 V
100...240 V