Control Wiring; Primary Circuit Assembly: (Pole) - ABB VM1 Installation And Service Instructions Manual

Ansi 15 kv, 1200 a, 31.5 ka
Hide thumbs Also See for VM1:
Table of Contents

Advertisement

8.10. Control wiring

During routine maintenance for control wiring, a visual
inspection of the hardware should be performed and a low-
frequency withstand voltage testing performed, and 2-5
manual operations should be conducted. Disconnect control
power before verifying secondary hardware and before low-
frequency withstand voltage testing.
Remove the front cover with a screwdriver. Correct any
loose or missing mounting hardware. Verify the ground wire
connection to the frame and all connectors' alignment and
snugness on the electrical components. Visually inspect the
secondary plug and correct any pins that may have become
displaced.
To verify the integrity of the secondary insulation, perform the
following low-frequency withstand voltage test:
1. Disconnect control power.
2. Connect all pins from the secondary to a test wire.
3. Connect test wire to the high potential lead of the test
machine.
4. Ground the circuit-breaker frame.
5. Start machine with output potential at 0 (zero) VAC RMS.
6. Increase the potential to the required insulation test voltage
(1125VAC RMS).
7. Hold for one minute.
8. Reduce potential to 0 (zero) VAC and turn off machine.
A successful withstand testing indicates satisfactory insulation
strength of the secondary circuit. Failing insulation will not
sustain the voltage across the secondary. Replace the
circuit-breaker control wiring if the insulation fails during low-
frequency withstand voltage testing.
Replace the front cover before operation. Verify the operation
with 2-5 electrical operations in the Test position or with a
remote power supply.

8.11. Primary circuit assembly: (Pole)

During routine maintenance for the primary circuit, a visual
inspection of the hardware and a low-frequency withstand
voltage testing, and lubrication of the primary contacts should
occur as outlined hereinafter.
All insulation material should be clean and free of structural
cracks. Inspect for structural cracks and replace damaged
parts.
Dirt or dust may create a dielectric path to ground on the
insulation. Remove dust and dirt with a clean, lint-free cloth.
Apply distilled water to the cloth to remove any difficult
dirt. DO NOT return the circuit-breaker into service until the
insulation surfaces are completely dry .
Lubrication on the primary contacts should be inspected
during routine maintenance. Use only grease ISOFLEX
TOPAS NB52 (ABB GCE0007249P01001PLCRN).
aPPlying abnoRMally high
voltage aCRoSS a PaiR of oPen
ContaCtS in a vaCuuM May
PRoduCe x-Radiation.
the Radiation May inCReaSe
with the inCReaSe in voltage
and/oR deCReaSe in ContaCt
SPaCing. it iS ReCoMMended
that all oPeRating PeRSonnel
Stand at leaSt one MeteR away
and in fRoM of the CiRCuit-
bReakeR duRing teSting.
We should use stronger language than recommend ("Workers
must stand back at least 1.5 meters ....")
To verify the integrity of the primary insulation, perform the
following low-frequency withstand voltage test:
1. Close the circuit-breaker (no control power supplied)
• Connect the high potential lead to one pole.
• Ground the remaining poles and the circuit-breaker
frame.
2. Start machine with output potential at 0 (zero) VAC.
3. Increase the potential to the required voltage (see Table 3;
note that new condition test is a factory test only and is not
valid for field condition tests.)
4. Hold for one minute.
5. Decrease potential to 0 (zero) VAC and turn off machine.
6. Repeat for the remaining poles.
A successful withstand indicates satisfactory insulation
strength of the primary circuit.
Dielectric Test Value,
Rated max voltage
1 Minute Dry AC rms
New condition
reference c37.06
15 kV
table 3: Primary low-frequency withstand test voltage
Caution
Dielectric Test Value,
1 Minute Dry AC rms
Field condition
reference c37.20.2
36 kV
27 kV
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vm1aVm1p

Table of Contents