Bottom view
Port (Silk Screen)
POWER
FE
RS232
AI
DI
DO
S0.In
CAN
COM1–COM3
2
Typical Cable Connection Scenarios
NOTICE
1. If the SmartLogger communicates with an inverter over an AC power cable, the power line
communication (PLC) central controller (CCO) module needs to be connected to the SmartLogger.
In addition, a miniature circuit breaker (MCB) and a knife switch need to be installed between the
PLC CCO module and the busbar to prevent device damage in the case of short circuits.
2. If the SmartLogger communicates with an inverter over an AC power cable, the cable from the
knife switch to the MCB and the cable from the busbar to the knife switch both need to be
prepared by yourself. Recommended cable: three-core armor cable with the operating voltage to
the ground greater than or equal to 600 V and the cross-sectional area of a single core wire being
2
4 mm
.
3. The network cable delivered with the SmartLogger is 2.2 meters long. Determine the installation
position of each component based on the cable length.
Function
Power supply
Fast Ethernet
RS232
Analog input
Digital input
Digital output
Connects to a pulse
output power meter.
CAN
RS485
Description
12 V DC
Connects to a local area network (LAN) switch, router,
power over Ethernet (PoE) or PC.
Connects to an external RS232 device.
4–20 mA and 0–20 mA current input (active), reserved
Connects to a dry contact input.
Relay output
Reserved
Reserved
Supports three RS485 ports that can connect to
devices such as the inverter and environmental
monitoring instrument (EMI).
2