ABB TDO16AIN Manual

16-channel digital output termination card introduced power triguard sc300e

Advertisement

Quick Links

Triguard SC300E
TDO16AIN
Termination Card Introduced Power
INTRODUCTION
PURPOSE
The TDO16AIN 16-channel digital output termination card acts as an interface between the
digital output circuits of an SC300E chassis and the field devices which they control.
It provides:
Screw terminals for the field wiring
Power supply inputs for the field devices
Fuse protection for the field loops with local and remote indication of fuse failure
Overvoltage protection
Dummy loads for unused digital output channels—to prevent spurious operation of
latent fault detection circuits in the associated digital output module. (Dummy loads
are only to be connected to outputs which are not used).
This document is intended to provide a general understanding of the function of the TDO16AIN,
sufficient to enable basic maintenance operations to be effected in the field.
ASSOCIATED DOCUMENTATION
Reference
008-5102
008-5104
008-5150
16-Channel Digital Output
MDO32BNS 32-Channel Digital Output Module User Manual
PDD24 Power Distribution Panel User Manual
MDO64BNS 64-Channel Digital Output Module User Manual
008-5135
24Vdc
(TDO16AIN)
Issue 6 October 2005
Title

Advertisement

Table of Contents
loading

Summary of Contents for ABB TDO16AIN

  • Page 1 (Dummy loads are only to be connected to outputs which are not used). This document is intended to provide a general understanding of the function of the TDO16AIN, sufficient to enable basic maintenance operations to be effected in the field.
  • Page 2 M3 threaded bush provision for a ring terminal. Allows the field 0V to be commoned for transient suppression protection. Overall size (mm) 162L x 125W x 107H Overall size (inches) 6.4L x 4.9W x 4.2H Weight 0.37kg TDO16AIN October 2005 – Issue 6...
  • Page 3: Environmental Specifications

    Triguard SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc ENVIRONMENTAL SPECIFICATIONS The maximum ambient temperature measured at the hottest point within the Triguard system shall not be greater than 60 degrees centigrade. Temperature operating: +5°C to +60°C Temperature storage: -25°C to +70°C Humidity: 5% to 95% non-condensing at ambient <...
  • Page 4: Technical Description

    TECHNICAL DESCRIPTION PHYSICAL The TDO16AIN comprises a PCB assembly mounted in a moulded carrier that can be snapped onto all commercially available styles of DIN EN mounting rail. Connection to the chassis backplane is via a multicore cable terminated at either end by a DIN41612 connector. Figure 2- 2 shows the TDO16AIN with the DIN41612 connector attached and mounted on rail EN 50022 type NS 35/5.
  • Page 5 Triguard SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc Figure 2-2 Leading dimensions and mounting schematic TDO16AIN October 2005 – Issue 6...
  • Page 6: External Connections

    Chassis connector J1 Connector, 34-way, DIN41612, female Field power supply inputs FS1 to FS4 Header, 2-way, Molex Minifit Jr Alarm output PL1 Header, 2-way, Molex KK Ground terminal TS1 Provision for M3 ring terminal TDO16AIN October 2005 – Issue 6...
  • Page 7: Theory Of Operation

    Triguard SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc THEORY OF OPERATION Figure 2-4 shows a circuit diagram of a typical digital output channel. Power supplies for the termination cards are normally provided by a Power Distribution Panel PDD24. Power for the digital output channels is distributed as shown in Figure 2-3 . Soldered links LK1 to LK4 are normally present, and in low load applications, external power can be connected to any one of the four inputs FS1 to FS4.
  • Page 8 Power distribution panel PDD24 has a Fuse blown alarm indicator with provision for multiple inputs. This facility can be wired to provide fuse blown indication for an entire cabinet. TDO16AIN October 2005 – Issue 6...
  • Page 9 Triguard SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc SUPPLEMENTARY INFORMATION Dummy loads Dummy loads are only to be connected to outputs that are not used. Do not connect a dummy load in parallel with a real output. Digital output channel connections Table 2-2 lists the digital output channel wiring connections and associated fuses for connector J1 and the screw terminals.
  • Page 10 Triguard SC300E SERVICING SCOPE The TDO16AIN contains all-passive circuitry that is extremely robust. Servicing operations will therefore not normally extend beyond the replacement of blown fuses. CAUTION Before replacing a blown fuse, ascertain the cause of failure, and take the appropriate remedial action.
  • Page 11: Service Support

    Triguard SC300E TDO16AIN 16-Channel D/O Termination Card 24Vdc SERVICE SUPPORT SPARE PARTS Spare parts and technical advice can be obtained from your local area offices. LIST OF SPARES Circuit Ref Part No Details F1 to F16 380-0013 1A Indicating fuse...